journal article·2025-08-06Open access

Pilot Protection for Transmission Line of Grid-Forming Photovoltaic Systems Based on Jensen–Shannon Distance

Kuan Li, Qiang Huang, Rongqi Fan

Applied Sciences· Volume 15· Issue 15

Abstract

When faults occur in transmission lines of grid-forming PV systems, the LVRT control and virtual impedance function cause the fault characteristics of grid-forming inverters to differ significantly from those of synchronous generators, which deteriorates the performance of existing protection schemes. To address this issue, this paper analyzes the fault characteristics of PV transmission lines under grid-forming control objectives and the adaptability of traditional current differential protection. Subsequently, a novel pilot protection based on the Jensen–Shannon distance is proposed for transmission line of grid-forming PV systems. Initially, the post-fault current samples are modeled as discrete probability distributions. The Jensen–Shannon distance algorithm quantifies the similarity between the distributions on both line ends. Based on the calculated distance results, internal and external faults are distinguished, optimizing the performance of traditional waveform-similarity-based pilot protection. Simulation results verify that the proposed protection reliably identifies internal and external faults on the protected line. It demonstrates satisfactory performance across different fault resistances and fault types, and exhibits strong noise immunity and synchronization error tolerance. In addition, the proposed pilot protection is compared with the existing waveform-similarity-based protection schemes.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Power Systems Fault Detection · HVDC Systems and Fault Protection · Islanding Detection in Power Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

State Grid Shandong Electric Power Research Institute, Jinan 250003, China

Shandong Smart Grid Technology Innovation Center, Jinan 250002, China

State Grid Shandong Electric Power Company, Jinan 250001, China

Funding

Science and Technology Project of State Grid Shandong Electric Power Company

References (28)

Show source-provided references
1. Fault ride-through strategy for two-stage grid-connected photovoltaic system enabling load compensation capabilities10.1109/TIE.2019.2899546 ↗
2. Overview of wind power intermittency: Impacts, measurements, and mitigation solutions10.1016/j.apenergy.2017.06.098 ↗
3. Operational flexibility and economics of power plants in future low-carbon power systems10.1016/j.apenergy.2015.06.065 ↗
4. Tang, J., Song, G., Wang, X., and Wang, C. (2016, January 25–28). A novel directional relay applicable to power system with wind farms. Proceedings of the 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference, Xi’an, China.
5. Wang, C., Song, G., and Zhang, J. (2016, January 25–28). A novel principle of directional relay for wind power integration based on model recognition in time domain. Proceedings of the 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference, Xi’an, China.
6. Protection challenges under bulk penetration of renewable energy resources in power systems: A review10.17775/CSEEJPES.2017.00030 ↗
7. Transient current similarity based protection for wind farm transmission lines10.1016/j.apenergy.2018.05.012 ↗
8. Protection of inverter-based microgrids from ground faults by an innovative directional element10.1049/iet-gtd.2018.5469 ↗
9. Novel method of fault direction identification for inverter-interfaced power supply access
10. A new two-port network model-based pilot protection for AC transmission lines10.1109/TPWRD.2019.2904310 ↗
11. Impedance differential protection: A new approach to transmission-line pilot protection10.1109/TPWRD.2014.2387689 ↗
12. Research on pilot differential protection based on parameter identification and suitable frequency band of transmission line model
13. Application of Tellegen’s quasi-power protection in double-circuit AC transmission line on the same tower
14. Novel differential protection approach of UHV AC transmission lines based on Tellegen’s quasi-power theorem10.1109/TPWRD.2021.3082855 ↗
15. Cosine similarity based line protection for large-scale wind farms10.1109/TIE.2020.2998756 ↗
16. Improved Euclidean distance based pilot protection for lines with renewable energy sources10.1109/TII.2022.3148318 ↗
17. Influence of inverter interfaced renewable energy generators on directional relay and an improved scheme10.1109/TPEL.2019.2904715 ↗
18. Spearman correlation-based pilot protection for transmission line connected to PMSGs and DFIGs10.1109/TII.2020.3018499 ↗
19. A novel structural similarity based pilot protection for renewable power transmission line10.1109/TPWRD.2020.2973505 ↗
20. Wang, C., Song, G., and Tang, J. (2016, January 7–10). Protection performance of traditional distance relays under wind power integration. Proceedings of the 13th International Conference on Development in Power System Protection, Edinburgh, UK.
21. Impact of inverter-interfaced renewable energy generators on distance protection and an improved scheme10.1109/TIE.2018.2873521 ↗
22. Automatic droop control for a low voltage DC microgrid10.1049/iet-gtd.2014.1228 ↗
23. Fault ride-through control strategy for two-stage grid-forming photovoltaic systems based on power command switching
24. Analytical calculation and influence factor analysis of virtual synchronous machine current during symmetrical short-circuit faults in power grid
25. Analytical calculation of VSG asymmetric short-circuit transient current considering the influence of internal electromotive force variation
26. Pei, X., Tang, G., and Zhang, S. (2018). A novel pilot protection principle based on modulus traveling-wave currents for voltage-sourced converter based high voltage direct current (VSC-HVDC) transmission lines. Energies, 11.10.3390/en11092395 ↗
27. Fault characteristic and protection performance under grid-forming control objective
28. Xue, S., Yang, J., and Chen, Y. (2016). The applicability of traditional protection methods to lines emanating from VSC-HVDC interconnectors and a novel protection principle. Energies, 9.10.3390/en9060400 ↗