journal article·2025-12-03Open access

Analysis of the Fire Behavior of Building-Integrated Photovoltaics (BIPV) as Façade Materials

Kye-Won Park, Eun-Goo Jeon, Jong-Jin Jeong, Moo-Joon Kim, Do-Woo Kim

Applied Sciences· Volume 15· Issue 23

Abstract

This study provides a comprehensive analysis of the fire hazards associated with Building-Integrated Photovoltaics (BIPV), using Aluminum Composite Panels (ACP) as a benchmark. Large-scale fire tests, modified from ISO 13785-1, were conducted on vertically installed BIPV modules to observe their fire behavior under conditions simulating a severe fire. The experimental process involved measuring key fire performance indicators, leading to the identification of a cascading failure mechanism. The BIPV modules demonstrated a peak Heat Release Rate (HRR) up to hi times higher (max. 898 kW) and smoke production nearly 10 times greater than the ACP baseline. The analysis reveals a distinct, multi-stage failure sequence that defines the systemic fire hazard of BIPV. Initially, a phenomenon strongly indicative of a chimney effect within the rear air cavity accelerates concealed fire spread. This rapid heating induces thermal stress, leading to extensive specimen damage termed cracking. This cracking event acts as a critical turning point, triggering a rapid release of trapped pyrolyzates and driving the fire to its peak intensity. This chain of events constitutes a unique hazard signature not observed in conventional cladding. The findings conclude that the fire risk of BIPV is a systemic issue, challenging the adequacy of component-level testing and highlighting the need for safety standards that assess the façade as a complete assembly.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire effects on concrete materials · Fire dynamics and safety research · Photovoltaic Systems and Sustainability

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Fire Insurers Laboratories of Korea, 1030 GyeongChoongdae-ro, Ganam-eup, Yeoju-si 12661, Republic of Korea

National Disaster Management Research Institute, 365 Jongga-ro, Jung-gu, Ulsan-si 44538, Republic of Korea

References (13)

Show source-provided references
1. The Path to the Building Integrated Photovoltaics of Tomorrow10.1016/j.egypro.2012.03.010 ↗
2. A state-of-the-art review of fire safety of photovoltaic systems in buildings10.1016/j.jclepro.2021.127239 ↗
3. First developments of a new test to evaluate the fire behavior of photovoltaic modules on roofs10.1016/j.firesaf.2014.11.011 ↗
4. Experimental study of flame spread underneath photovoltaic (PV) modules10.1016/j.firesaf.2020.103027 ↗
5. Impact of flat roof–integrated solar photovoltaic installation mode on building fire safety10.1002/fam.2755 ↗
6. Fire-induced reradiation underneath photovoltaic arrays on flat roofs10.1002/fam.2494 ↗
7. White, N., and Delichatsios, M. (2015). Fire Hazards of Exterior Wall Assemblies Containing Combustible Components, Springer Nature.10.1007/978-1-4939-2898-9 ↗
8. Evaluating the fire risk associated with cladding panels: An overview of fire incidents, policies, and future perspective in fire standards10.1002/fam.2973 ↗
9. Experimental investigations on the influence of ‘chimney-effect’ on fire response of rainscreen façades in high-rise buildings10.1016/j.jobe.2021.103257 ↗
10. A Review for Solar Panel Fire Accident Prevention in Large-Scale PV Applications10.1109/ACCESS.2020.3010212 ↗
11. (2002). Reaction-to-Fire Tests for Façades—Part 1: Intermediate-Scale Test (Standard No. ISO 13785-1:2002). Available online: https://www.iso.org/standard/27183.html.
12. Heat release rate: The single most important variable in fire hazard10.1016/0379-7112(92)90019-9 ↗
13. (2016). Photovoltaic (PV) Module Safety Qualification—Part 1: Requirements for Construction (Standard No. IEC 61730-1:2016). Available online: https://webstore.iec.ch/en/publication/59803.