journal article·2026-05-01Open access

Mechanical–electrical decoupled failure in glass insulators: Interface and residual strength analysis

Lin Liu, Guohai Lin, Haitao Wang, Zheng Wang, Xiangyang Peng, Qiang Wu, Yazhou Fan, Ji Wu, Yu Wang

AIP Advances· Volume 16· Issue 5

Abstract

This study identifies a new failure mechanism in glass insulators caused by a manufacturing defect: a missing internal thread structure. This defect results in a “mechanical–electrical decoupled failure,” where electrical performance remains intact while mechanical strength is severely reduced. Analysis of a failed insulator from a 220 kV transmission line, together with laboratory tests on 17 units, showed that insulators without threads pass standard electrical tests but retain less than 10% of their strength after failure, compared to over 75% for normal units. Finite element simulations confirmed that electric field distributions stay within safe limits, supporting the decoupling concept. The presence of multiple defective units in the same production batch indicates a quality control problem. Current acceptance tests are unable to detect this hidden defect. Mechanical tests further revealed an unusual failure mode where the steel pin pulls out, rather than the glass breaking. This defect cannot be detected by current factory acceptance procedures, indicating a need to revise mechanical verification protocols and implement enhanced quality control measures for batch-produced glass insulators.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: High voltage insulation and dielectric phenomena · Power Transformer Diagnostics and Insulation · Electrical Fault Detection and Protection

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Guangdong Provincial Key Laboratory of Electric Power Equipment Reliability, Electric Power Science Research Institute of Guangdong Power Grid Co., Ltd. 1 , Guangzhou 510080,

The School of Electrical Engineering and Automation, Wuhan University 2 , Wuhan 430072,

The State Key Laboratory of Power Grid Environmental Protection, Wuhan University 3 , Wuhan 430072,

Funding

Science and Technology Project of China Southern Power Grid Co., LTD.

References (20)

Show source-provided references
1. Evaluation of porcelain and toughened glass suspension insulators removed from service10.1109/tdei.2008.4483466 ↗
2. Failure analysis of polymeric outdoor insulators used in HVDC converter stations10.1016/j.engfailanal.2024.108051 ↗
3. Fatigue fracture of composite insulator sheds utilized in strong wind areas10.1109/tdei.2015.7116360 ↗
4. Failure modes of porcelain and toughened glass suspension insulators
5. Selection considerations: Hardened glass vs. polymer insulators
6. A case study of glass insulator pin failure in 500 kV transmission line10.1016/j.engfailanal.2023.107582 ↗
7. Analysis of the cause of self-explosion of glass insulator of ±800 kV UHVDC line
8. Analysis of cement deterioration in outdoor high-voltage insulator10.3390/ma12244201 ↗
9. Failure analysis on the sealing glass insulator of semiconductor device with low resistance abnormity10.1109/ICEPT.2017.8046594 ↗
10. Ageing studies on transmission line glass insulators using dielectric dissipation factor test10.1109/IPECON.2010.5696973 ↗
11. Novel approaches to assess the mechanical reliability of toughened glass insulators used in transmission lines10.1109/tpwrd.2021.3103894 ↗
12. Prediction of moisture diffusion and failure in glass/steel adhesive joints10.1007/s40940-022-00194-w ↗
13. Evaluation of and replacement strategies for aged high-voltage toughened glass-suspension insulators10.1109/tpwrd.2014.2369457 ↗
14. Effects of broken glass insulator on charge distribution along insulator strings10.1049/cp.2016.1278 ↗
15. Finite element modeling for electric field and voltage distribution along the cap and pin insulators under pollution10.29354/diag/159517 ↗
16. Finite element analysis of disc insulator type and corona ring effect on electric field distribution over 230-kV insulator strings10.14419/ijet.v1i4.330 ↗
17. Failure analysis of decay-like fracture of composite insulator10.1109/tdei.2014.004485 ↗
18. Study on the ultimate load failure mechanism and structural optimization design of insulators10.3390/ma17020351 ↗
19. Interface bonding properties of new and old concrete: A review10.3389/fmats.2024.1389785 ↗
20. Fiber and interface failure characterization of glass fiber reinforced polymer for composite insulators after liquid permeation10.1016/j.polymer.2023.126293 ↗