Research on fault-differentiated resilient recovery technology for adaptive islanding operation of microgrids
Source abstract
Abstract
The fault is caused by the periodic variation in the amplitude and phase angle of the measured impedance under the adaptive islanding operation of the microgrid. A fault differential elastic recovery technology for microgrid adaptive islanding operation is proposed, based on high-frequency measurement of the grounding electrode line and current estimation of the monitored double-circuit line. Under the quantitative feature analysis mode of high-frequency voltage mutation, a fault differential feature detection model for microgrid adaptive islanding operation is established. Through fusion analysis of the voltage distribution along the grounding electrode line under high-impedance fault conditions, the pulse injection method and the single-ended traveling wave method are combined to achieve elastic fusion for fault differentiation. A state feature monitoring model for microgrid adaptive islanding operation is constructed. Using the approach of high-frequency measurement of the grounding electrode line and current estimation of the monitored double-circuit line, the fault model parameters of microgrid adaptive islanding operation are analyzed under the influence of external interference and grounding electrode line parameters. By employing fault feature clustering, fault location, and cluster analysis methods, differential elastic recovery of faults and fault diagnosis detection are realized. Test results show that the proposed method enhances the capability for dynamic fault detection and diagnosis, effectively ensuring normal operation of the microgrid system.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Islanding Detection in Power Systems · Power Systems Fault Detection · Microgrid Control and Optimization
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Key Laboratory of Technology and Equipment for Defense Against Power System Operational Risks 1 , Nanjing 211106,
NARI Technology Co., Ltd. 2 , Nanjing 211106,
Funding
State Key Laboratory of Technology and Equipment for Defense Against Power System Operational Risks
References (15)
Show source-provided references
1. Single-terminal protection of AC transmission lines in AC-DC network based on curvature radius of first traveling wave10.16339/j.cnki.hdxbzkb.2024234 ↗
2. Research on fault ranging of DC transmission line based on LiDAR signal10.20033/j.1003-7241.(2025)05-0121-05 ↗
3. A fault detection method for multi-microgrid considering topological variations based on message passing neural network10.13336/j.1003-6520.hve.20230195 ↗
4. Microgrid fault location based on sniffing strategy slime mould algorithm10.16088/j.issn.1001-6600.2024041301 ↗
5. Microgrid fault diagnosis based on deep transfer learning and LSTM network10.3969/j.issn.1000-1158.2023.04.14 ↗
6. Research on stable control strategy for series-connected hydrogen-electric coupled DC microgrid based on virtual thermal resistor10.13335/j.1000-3673.pst.2025.0673 ↗
7. Fault area determination technology of grid-connected photovoltaic microgrid in 4D coordinate system10.12177/emca.2022.148 ↗
8. Fast super-twisting multi-quasi-resonant sliding mode control for cascaded H-bridge rectifiers in hybrid microgrids10.19912/j.0254-0096.tynxb.2024-0045 ↗
9. Research on fault ride through control method of NPC inverter in island microgrid based on model prediction10.11857/j.issn.1674-5124.2022060145 ↗
10. A microgrid high impedance fault detection based on integrated position peak
11. Control strategy of islanded AC/DC hybrid microgrid power system based on adaptive segmented double-droop10.12204/j.issn.1000-7229.2025.01.008 ↗
12. Improved switch-function based fault section location method for resilient distribution network under complex and multiple faults10.16081/j.epae.202509003 ↗
13. Research on fault identification and location method based on wavelet transform and TKEO10.19783/j.cnki.pspc.241313 ↗
14. Research on DC microgrid fault diagnosis based on CNN-BiLSTM-attention10.13334/j.0258-8013.pcsee.231736 ↗
15. Reliability assessment of grid-connected microgrids considering time-to-failure correction for optical storage systems10.13941/j.cnki.21-1469/tk.2025.11.006 ↗