Abstract

The transmission corridor is often rich in vegetation, including tall and flammable tree species such as arbors. When the clearance between vegetation and transmission lines is less than the insulation safety distance, discharge faults between vegetation and the lines can easily occur. In forested areas with abundant combustible materials, such incidents may initiate wildfires—particularly in the western Sichuan plateau region, where lower atmospheric pressure further increases the susceptibility to tree-conductor faults. To investigate the critical breakdown distance between trees and transmission lines under multiple environmental factors, a three-dimensional finite element model of the tree-conductor system was developed. This model was used to analyze the critical breakdown distance under various atmospheric pressure and humidity conditions, and its accuracy was experimentally validated. Data analysis revealed that the maximum critical breakdown distance between the trees and the transmission line—0.217 m—occurred at an atmospheric pressure of 50 kPa and 0% relative humidity. As pressure decreases, the critical breakdown distance increases. Conversely, when relative humidity increases (below the condensation level), the critical breakdown distance decreases. The error between simulation and experimental results remained within 10%.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Thermal Analysis in Power Transmission · Lightning and Electromagnetic Phenomena · Forest Biomass Utilization and Management

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Electric Power Research Institute, State Grid Sichuan Electric Power Company 1 , Chengdu 610041, Sichuan,

School of Electrical Engineering, Southwest Jiaotong University 2 , Chengdu 611756, Sichuan,

Funding

State Grid Sichuan Electric Power Corporation · Science and Technology Department of Sichuan Province

References (28)

Show source-provided references
1. Analysis of influencing factors and preventive measures for operation safety of transmission lines
2. Research and application status on forest fire risk assessment and monitoring for overhead transmission lines10.12172/202103220002 ↗
3. Electric field and ion current environment of HVdc transmission lines: Comparison of calculations and measurements10.1109/tpwrd.2011.2172003 ↗
4. Conductor design based on electromagnetic environment for ±1100 kV UHVDC transmission lines
5. Power line failures and catastrophic wildfires under extreme weather conditions10.1016/j.engfailanal.2013.07.006 ↗
6. A spatial database of wildfires in the United States, 1992–201110.5194/essd-6-1-2014 ↗
7. Study on the fire environment forming forest fires in Liangshan prefecture10.13466/j.cnki.lyzygl.2020.05.017 ↗
8. Research status and prospects of forest fires caused by electrical faults10.13577/j.jnd.2021.0208 ↗
9. Experimental study on discharge characteristics of medium-voltage lines tree-grounding faults10.19781/j.issn.1673-9140.2022.04.005 ↗
10. Motion analysis of burning particles in flame gap under DC voltage10.13393/j.cnki.issn.1672-948x.2020.02.013 ↗
11. Modeling and experimental verification of high impedance arcing fault in medium voltage networks10.1109/TDEI.2007.344617 ↗
12. Electrical and physical characterization of Earth faults for diverse bush species10.1016/j.jestch.2020.03.002 ↗
13. High impedance fault detection method based on the short-time Fourier transform10.1049/iet-gtd.2018.0093 ↗
14. Development mechanism of carbonized path in 10 kV overhead conductor tree-contact faults10.19421/j.cnki.1006-6357.2024.01.009 ↗
15. Study on the development process and characteristics of tree-to-wire discharge in 10 kV overhead lines10.15961/j.jsuese.202300675 ↗
16. Single-phase tree-contact ground fault model and its detection method for 10 kV overhead conductors10.13334/j.0258-8013.pcsee.210009 ↗
17. Analysis of the influence of vegetation moisture content on the characteristics of single-phase tree-contact ground faults10.19783/j.cnki.pspc.221275 ↗
18. Study on the influence of vegetation size on the characteristics of tree-contact high impedance ground faults10.20168/j.1009-0029.2024.4.457.6 ↗
19. Simulation analysis of early tree-wire faults in distribution lines based on magnetohydrodynamics10.19595/j.cnki.1000-6753.tces.L90108 ↗
20. Study on streamer inception characteristics under positive lightning impulse voltage10.13334/j.0258-8013.pcsee.2012.19.021 ↗
21. Study on the influence of air pressure and humidity on air gap insulation characteristics10.13296/j.1001-1609.hva.2024.01.010 ↗
22. Influence of air humidity on breakdown characteristics of short gaps under non-uniform AC electric field10.13336/j.1003-6520.hve.20190410013 ↗
23. The influence of humidity on positive streamer propagation in long air gap10.1088/1361-6595/aca04c ↗
24. High-voltage test techniques - Part 1: General definitions and test requirements
25. Z. H. Cao , “Study on the influence mechanism of air pressure and humidity on streamer discharge characteristics,” M.S. thesis, School of Electric Power Engineering, Guangzhou University, Guangzhou, China, 2024.
26. Measurement of electric field distribution along composite insulators by integrated optical electric field sensor10.1109/t-dei.2008.4446764 ↗
27. Experimental observation technology for long air gap discharge process10.13334/j.0258-8013.pcsee.2012.10.006 ↗