Analysis and design of current transformers for low-frequency transmission systems using hybrid magnetic materials
Source abstract
Abstract
In low-frequency transmission, traditional current transformers face the problem of saturation distortion issues, while utilizing materials with high magnetic saturation intensity could add measurement errors. In order to solve this problem, the mixed materials current transformer (MMCT) is proposed, which uses two cores, one made of conventional silicon steel with an air gap and the other made of nanocrystalline alloy material without an air gap. Theoretical analyses and finite element method simulations are carried out to validate the practicability and effectiveness of the proposed MMCT. Furthermore, the performance is optimized to address the effect of the air gap. The results manifest that the transmission characteristics of the MMCT are outstanding.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: HVDC Systems and Fault Protection · Magnetic Field Sensors Techniques · Silicon Carbide Semiconductor Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Jiangsu Electric Power Co., Ltd. Marketing Service Center 1 , Nanjing 210026,
State Key Laboratory of Power Grid Environmental Protection, School of Electrical Engineering and Automation, Wuhan University 2 , Wuhan 430072,
Department of Electrical and Electronic Engineering, The Hong Kong Polytechnic University 3 , Hong Kong 999077,
Funding
Science and Technology Projects of SGCC
References (7)
Show source-provided references
1. Low frequency ac transmission upgrades with optimal frequency selection10.1109/tpwrs.2021.3107193 ↗
2. Framework for current transformer saturation detection and waveform reconstruction10.1049/iet-gtd.2017.1742 ↗
3. Current transformer saturation detection with genetically optimized neural networks
4. Avoid current transformer saturation using adjustable switched resistor demagnetization method10.1109/tpwrd.2020.2983484 ↗
5. A novel current transformer based on virtual air gap and its basic measuring characteristics10.1109/tpwrd.2022.3179321 ↗
6. A novel dual-core current transformer based on TMR sensor and its measuring characteristics10.1063/9.0000652 ↗
7. Research on loss characteristic of soft magnetic composites under nonsinusoidal excitations with DC bias field10.1063/5.0211218 ↗