journal article·2023-12-01Open access

A method for fault location using the phase difference of current in the protective layer at both ends of a cable section

Shiqiang Mi, Zhao Fang, Xuefeng Yang, Haiqiong Liu, Du Li, Wei Zhu, Dingchao Tang

AIP Advances· Volume 13· Issue 12

Abstract

This paper is based on the distribution characteristics of the protective layer current under the fault state of high-voltage cables, and discovers the monotonic variation law between the fault point position and the power frequency phase difference of the protective layer current at both ends of the cable fault section. A method for fault location using the phase difference of the protective layer current at both ends of the cable section is proposed. For a long cable line composed of multiple complete cross-connected sections, the cross-connected section can be located through the current power frequency phase difference P (section) at both ends of the metal sheath section, just like the section positioning within the complete cross-connected section. If P (section) ∈ (90°, 270°), then the section is a fault section; otherwise, it is a non-fault section. Finally, the relationship curve between the power frequency phase difference of the protective layer current at both ends of the fault section and the distance from the fault point is used to determine the fault location.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Electrical Fault Detection and Protection · Power Line Inspection Robots · High-Voltage Power Transmission Systems

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

State Grid Tibet Electric Power Co., Ltd. Shannan Power Supply Company 1 , Shannan, Tibet 856100, China

State Grid Hubei Electric Power Co., Ltd. Wuhan Power Supply Company 2 , Wuhan, Hubei 430013, China

Liling Huaxin Insulator Technology Co., Ltd. 3 , Hunan, Liling 412200, China

Funding

State Grid Wuhan Power Supply Company Technology Project

References (5)

Show source-provided references
1. Research progress in condition monitoring and insulation diagnosis of XLPE cable10.13336/j.1003-6520.hve.20200430028 ↗
2. 275 kV cable discharge field measurement and analysis of SVLs chain failure using ATP10.1016/j.epsr.2018.04.009 ↗
3. Electrical-thermal failure of metal-oxide arrester by successive impulses10.1109/tpwrd.2015.2506785 ↗
4. Numerical modelling of MOV with Voronoi network and finite element method10.1049/hve2.12072 ↗
5. Experimental verification of monitoring techniques for metal-oxide surge arrester10.1049/iet-gtd.2019.1398 ↗