Study on the influence of building aerodynamic shadows on the heat transfer performance of natural draft dry cooling towers
Source abstract
Abstract
Previous studies have shown that the heat transfer of air cooling towers is mainly affected by crosswind. To improve the cooling performance of air-cooled towers under crosswind and the efficiency of power plants, this paper studies the influence mechanism of buildings on the heat dissipation performance of natural draft dry cooling towers (NDDCTs). The numerical simulation of a 2 × 1000 MW NDDCT is carried out to analyze the distribution of the aerodynamic shadow area and its influence on the heat transfer performance of the NDDCT. The study found that at a wind speed of 12 m/s, the heat dissipation efficiency of the NDDCT under the influence of the original building decreased by 4.74%, and the total ventilation volume decreased by 2595.76 kg/s. When the NDDCT was located in the aerodynamic shadow wake area of the building, the heat dissipation efficiency increased by 8.36%. This shows that the aerodynamic shadow area of the building will lead to deflection deceleration and a steady flow effect of the flow field near the tower base, which has a double-sided effect on the heat transfer of the NDDCT. By adjusting the interference of the aerodynamic shadow wake area of the building on the NDDCT, the high wind speed sensitivity and the heat dissipation deviation of the two towers can be reduced.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Wind and Air Flow Studies · Solar Energy Systems and Technologies · Adsorption and Cooling Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Huaneng Jiuquan Power Generation Co., Ltd. 1 , Jiuquan 735000, Gansu, China
Hebei Key Laboratory of Low Carbon and High-Efficiency Power Generation Technology, North China Electric Power University 2 , Baoding 071003, Hebei, China
Funding
Hebei Province Outstanding Youth Fund
References (34)
Show source-provided references
1. Technical and economic analysis of indirect air cooling and direct air cooling systems
2. Dimensional characteristics of wind effects on the performance of indirect dry cooling system with vertically arranged heat exchanger bundles10.1016/j.ijheatmasstransfer.2013.08.085 ↗
3. A new theoretical method for predicating the part-load performance of natural draft dry cooling towers10.1016/j.applthermaleng.2015.08.104 ↗
4. A study of the unfavorable effects of wind on the cooling efficiency of dry cooling towers10.1016/0167-6105(94)00078-R ↗
5. Numerical simulation of fluid flow and thermal performance of a dry-cooling tower under cross wind condition10.1016/s0167-6105(98)00121-4 ↗
6. Effects of ambient winds on the thermo-flow performances of indirect dry cooling system in a power plant10.1016/j.ijthermalsci.2012.08.010 ↗
7. Numerical simulation of operating characteristics of air-cooled radiator in indirect air-cooled system
8. Influences of height to diameter ratios of dry-cooling tower upon thermo-flow characteristics of indirect dry cooling system10.1016/j.ijthermalsci.2015.03.004 ↗
9. A proposed stack configuration for dry cooling tower to improve cooling efficiency under crosswind10.1016/j.jweia.2010.08.004 ↗
10. Alternative geometry for cylindrical natural draft cooling tower with higher cooling efficiency under crosswind condition10.1016/j.enconman.2013.09.022 ↗
11. Proposing a new technique to enhance thermal performance and reduce structural design wind loads for natural drought cooling towers10.1016/j.energy.2013.09.033 ↗
12. The effect of the heat exchanger arrangement and wind-break walls on the performance of natural draft dry-cooling towers subjected to cross-winds10.1016/0167-6105(95)00026-7 ↗
13. Flow and heat transfer characteristics of indirect dry cooling system with horizontal heat exchanger A-frames at ambient winds10.1016/j.ijthermalsci.2014.01.007 ↗
14. Study of heat rejection in triple natural draft dry cooling towers under crosswind using radiator-type windbreakers10.4028/www.scientific.net/AMM.598.265 ↗
15. Heat rejection enhancement in natural draft cooling tower using radiator-type windbreakers10.1016/j.enconman.2013.03.031 ↗
16. Numerical and experimental study on a single cone saline water spray in a wind tunnel10.1016/j.ijthermalsci.2017.06.011 ↗
17. Experimental study of the application of two trickle media for inlet air pre-cooling of natural draft dry cooling towers10.1016/j.enconman.2014.10.031 ↗
18. A review on the performance evaluation of natural draft dry cooling towers and possible improvements via inlet air spray cooling10.1016/j.rser.2017.05.151 ↗
19. Investigations on the influence of nozzle arrangement on the pre-cooling effect for the natural draft dry cooling tower10.1016/j.applthermaleng.2017.10.171 ↗
20. A performance enhancement of a natural draft dry cooling tower in crosswind via inlet flow field reconstruction10.1016/j.enbuild.2018.01.003 ↗
21. Ventilation enhancement for a natural draft dry cooling tower in crosswind via windbox installation10.1016/j.applthermaleng.2018.03.059 ↗
22. Performance recovery of natural draft dry cooling systems by combined air leading strategies10.3390/en10122166 ↗
23. Selection of wetted media for pre-cooling of air entering natural draft dry cooling towers10.1016/j.applthermaleng.2016.11.179 ↗
24. The adoption of windbreak wall partially rotating to improve thermo-flow performance of natural draft dry cooling tower under crosswind10.1016/j.ijthermalsci.2018.08.005 ↗
25. An overview about the study of downwash effects on dispersion of airborne pollutants10.1016/j.envsoft.2003.11.011 ↗
26. Wind tunnel experiments on cooling tower plumes: Part 1—In uniform crossflow10.1115/1.3250809 ↗
27. Wind tunnel experiments on cooling tower plumes: Part 2—In a nonuniform crossflow of boundary layer type10.1115/1.3250810 ↗
28. Numerical simulation of wind load on cooling towers under double-tower condition
29. Interference of wind loading between two neighboring cooling towers
30. X. L. Liang , “Study on wind field around high-rise building,” M.A. thesis, Wuhan University of Science and Technology, 2004.
31. Development and evaluation of the PRIME plume rise and building downwash model10.1080/10473289.2000.10464017 ↗
32. A wind tunnel study of dense gas dispersion in a stable boundary layer over a rough surface10.1016/s1352-2310(01)00073-5 ↗
33. Numerical calculation of aerodynamic shaded areas of high-rise buildings
34. Flow and heat transfer characteristics of air outside the elliptical tube bundle of air condenser elliptical fin