journal article·2021-09-01Open access

Influence of the dissociation unit on pressure and temperature distribution in arc chamber of ACB during the breaking process

Nairui Yin, Hongwu Liu, Zongqian Shi, Ruiliang Guan

AIP Advances· Volume 11· Issue 9

Abstract

To void breakdown between busbars, the dissociation unit is applied in the arc chamber of an air circuit breaker (ACB) to cool down the hot gas exhausted from the vent of the arc chamber in the interrupting process. Cooling efficiency and flow resistance of the dissociation unit have important roles, which can greatly affect the safety of the low voltage switcher and interrupting performance of the arc chamber. The most common structure style of the dissociation unit is a multilayer metal wire mesh, and it has a complex microstructure. Then, it is unreasonable to directly simulate the dissociation unit due to the huge cost of calculation. In this study, the porous medium model is introduced and a combination of two different porous materials is applied to simplify the simulation model of the dissociation unit. Based on the porous model and simplified arc chamber model, the ACB with the dissociation unit is analyzed. The cooling effect and flow resistance of the dissociation unit are evaluated in the breaking process. By comparing experimental and simulated pressures in the arc chamber, this simulation approach is verified.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Vacuum and Plasma Arcs · Advanced materials and composites · Nuclear Materials and Properties

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University 1 , Xi’an 710049, China

Changshu Switchgear Mfg. Co., Ltd. (Former Changshu Switchgear Plant) 2 , Changshu, Jiangsu 215500, China

References (16)

Show source-provided references
1. Strike phenomena during interruption of low voltage circuit breaker
2. Flow velocity and conductance of hot gas ejected from a molded case circuit breaker
3. Conductance diagnostics in hot gas ejected from a molded case circuit breaker during high current arc interruption10.1541/IEEJPES1990.116.3_338 ↗
4. Electrical and thermal conductivities and enthalpy of air plasma contaminated with Fe, Ca, MG or H2O vapor
5. Influence of copper vapor contamination on dielectric properties of hot air at 300 ∼ 3500 K in atmospheric pressure10.1109/tdei.2005.1453455 ↗
6. Measurement and correlation of friction characteristic of flow through foam matrixes10.1016/j.expthermflusci.2005.07.007 ↗
7. Coupled lattice Boltzmann finite volume method for conjugate heat transfer in porous medium10.1080/10407782.2018.1444868 ↗
8. Numerical simulation analysis of flow field of metal wire mesh
9. Dynamics of fluids in porous medium10.1016/b978-0-444-41012-2.50021-8 ↗
10. Analysis of fluid flow and heat transfer interfacial conditions between a porous medium and a fluid layer10.1016/s0017-9310(00)00217-9 ↗
11. Analysis of variants within the porous medium transport models10.1115/1.521468 ↗
12. Advances in low-voltage circuit breaker modelling10.1088/0022-3727/37/4/011 ↗
13. Arcing phenomena through hot gas ejected from moulded-case circuit breakers during the high-current interruption process10.1088/0022-3727/34/1/318 ↗
15. Gas flow and heat transfer in a moving packed bed of particle
16. Numerical simulation of impact effect of internal gas pressure on chamber housing in low-voltage circuit breaker10.1109/tcpmt.2014.2300093 ↗