Analysis of an accident of abnormal increase in pole bus differential current caused by DC line faults
Source abstract
Abstract
This paper analyzes an accident of abnormal increase of pole bus differential current and pole differential current of a converter station caused by line fault of a ±800 kV extra high-voltage direct current transmission project. After a lightning strike caused a short circuit and grounding of the DC line, the sudden voltage change protection of the DC line was triggered and the DC full voltage restart was successful. The pole bus differential current and pole differential current of the converter station have reached the protection set but have not reached the protection delay set; therefore, the differential protection has not acted. This paper first introduces the configuration principles of pole differential protection, pole bus differential protection, and line voltage sudden change protection for extra-high voltage converter stations. Second, the operation of the DC protection under this fault was analyzed in detail, and the reasons for the occurrence of pole bus differential current and pole differential current were also analyzed in this paper. Then, the range of equipment that caused the abnormal increase in differential current was identified. Finally, the lightning strike model was built on the real-time digital system, and the fault was simulated and replicated. It was determined that the abnormal increase in differential current was caused by the discharge of the pole bus surge arrester caused by the second lightning strike on the DC line.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: HVDC Systems and Fault Protection · High-Voltage Power Transmission Systems · Power Systems Fault Detection
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Hubei Electric Power Research Institute 1 , Wuhan 430077, China
State Grid Hubei DC Company 2 , Yichang 443000, China
References (15)
Show source-provided references
1. Development and engineering application of HVDC transmission technology
2. Development status and application prospect of VSC-HVDC
3. Engineering application and development prospect of VSC-HVDC transmission technology
4. Friendly HVDC transmission technologies for large-scale renewable energy and their engineering practice
5. Analysis of UHVDC line protection principle and operation strategy
6. Scheme and engineering application of flexible DC control and protection system
7. Discussion of ±800 kV UHVDC transmission control and protection system
8. Overview on research of fault clearing and recovery strategy for HVDC transmission lines
9. Comments on fault handling and protection technology for VSC-HVDC transmission lines10.7500/AEPS20150125002 ↗
10. Review and prospect on transmission line protection in flexible DC system10.13335/j.1000-3673.pst.2020.1572 ↗
11. Application research on fast line protection and adaptive restarting methods for multi-terminal hybrid LCC/MMC HVDC transmission lines
12. Novel restart scheme of DC fault for flexible DC transmission system10.7500/AEPS20170328003 ↗
13. Lightning current mathematical model simulation and comparative analysis
14. Lightning current mathematical model simulation and comparative analysis
15. Study on the modeling approach of lightning current and its influence on overhead line lightning withstand performance analysis