journal article·2025-07-01Open access

Research on optimization strategy of differential protection for inrush current in converter transformer considering magnetic flux restraint

Ran Deng, Haotian Kong, Liangchuang Li, Changan Lu, Ao Xu, Chenguang Wang

AIP Advances· Volume 15· Issue 7

Abstract

The converter transformer is a critical component of the HVDC transmission system and its operational stability is essential for the overall safety of the power grid. Inrush current, a non-fault large current phenomenon, can cause the differential protection device to malfunction, thus compromising the normal operation of the transformer. To enhance the accuracy and reliability of differential protection for converter transformers, this paper proposes an optimization strategy for inrush current differential protection based on the Magnetic Flux Restraint principle. First, the generation mechanism of inrush current and the operating principles of the differential protection system are analyzed, with mutual inductance identified as a key parameter for distinguishing between excitation current and fault current. Subsequently, simulations are conducted to study the behavior of the second harmonic, mutual inductance, and magnetic flux under both inrush current and fault conditions. Based on the simulation results, an optimization method for the original differential protection system, utilizing variations in mutual inductance parameters, is established. The feasibility of the proposed approach is validated through simulation studies. The method for optimizing differential protection in converter transformers is presented, which is considered crucial for enhancing the security and stability of power system operations.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Geoscience and Mining Technology · Magnetic Properties and Applications · Power Systems Fault Detection

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Guangzhou Bureau, CSG EHV Power Transmission Company 1 , 510620 Guangzhou,

School of Electrical and Electronic Engineering, Harbin University of Science and Technology 2 , 150080 Harbin,

Funding

China Southern Power Grid Program

References (13)

Show source-provided references
1. Mal-operation risk analysis and countermeasure on zero-sequence differential protection of converter substation during existence of recovery inrush due to fault removal10.13334/j.0258-8013.pcsee.162277 ↗
2. 2016
3. Mechanism and countermeasures of mal-operation of converter transformer zero-sequence overcurrent protection caused by inrush currents10.7500/AEPS20180423003 ↗
4. Analysis of electromagnetic transient and adaptability of second-harmonic restraint based differential protection of UHV power transformer10.1109/tpwrd.2010.2050343 ↗
5. A new differential protection algorithm based on rising rate variation of second harmonic current
6. Analysis of transformer inrush current and comparison of harmonic restraint methods in transformer protection10.1109/TIA.2013.2257155 ↗
7. Improved operation of differential protection of power transformers for internal faults10.1109/61.156994 ↗
8. A method for identifying transformer magnetizing inrush current based on Pearson correlation coefficient10.13296/j.1001-1609.hva.2016.08.009 ↗
9. Identification method of transformer magnetizing inrush current based on decay rate of aperiodic components10.7667/PSPC171046 ↗
10. A new method to identify transformer magnetizing inrush current using waveform curvature
11. Research on transformer inrush current identification using extreme value characteristics of current rate of change10.7667/PSPC151996 ↗
12. A new criterion for the identification of transformer primary side current and fault differential current based on Babbitt coefficient10.19783/j.cnki.pspc.190802 ↗
13. Flux restraint technology of transformer protection for electronic transformer