Evaluating the impact of air terminal geometry on lightning intercept efficacy under a strong background electric field
Source abstract
Abstract
A comparative analysis of the attachment efficacy of sharpened vs blunted air terminals under a strong background DC electric field, similar to conditions found in naturally occurring lightning events, is presented. Testing was conducted using an oil-free, 17-stage, 1.4 MV bipolar Marx generator with a biased discharge plane that emulated the conditions found prior to the lightning return stroke. The biased discharge plane allowed the introduction of a strong DC electric field and subsequent corona formation on a time scale much longer than the brief duration over which the downward leader propagates. Initial observations indicate that despite a higher background electric field at the sharpened terminals, leading to pre-discharge corona formation where none is seen on the blunt terminal, both the sharpened and blunted terminals exhibit similar attachment probabilities during discharge events, with some discharge events attaching to both terminals.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Lightning and Electromagnetic Phenomena · High voltage insulation and dielectric phenomena · Aerosol Filtration and Electrostatic Precipitation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Electrical and Computer Engineering, Texas Tech University 1 , Lubbock, Texas 79409, USA
Facility Engineering Electromagnetics Group, CNS Pantex 2 , Amarillo, Texas 79068, USA
Funding
U.S. Department of Commerce
References (16)
Show source-provided references
1. Experimental study on lightning attachment manner to wind turbine blades with lightning protection system10.1109/TPS.2018.2873200 ↗
2. Shielding failure of high-voltage substations: A fractal-based approach for negative and positive lightning10.1109/TIA.2021.3064546 ↗
3. The multiscale nature of streamers10.1088/0963-0252/15/2/s14 ↗
4. Modeling of lightning exposure of sharp and blunt rods10.1109/tpwrd.2010.2049384 ↗
5. Glow corona discharges and their effect on lightning attachment: Revisited
6. On the percentage of lightning flashes that begin with initial breakdown pulses10.1002/2013JD020854 ↗
7. 2013
8. Static electricity measurements for lightning warnings - an exploration
9. Electric field values observed near lightning flash initiations10.1029/2006GL028777 ↗
10. Characteristics of upward positive lightning initiated from the Peissenberg tower, Germany10.1109/TEMC.2014.2359584 ↗
11. High-speed video observation, currents, and EM-fields from four negative upward lightning to the Peissenberg tower, Germany10.1109/TEMC.2020.3032781 ↗
12. Electric field during upward connecting leader initiation in negative cloud-to-ground lightning measured at a 50-m distance10.1109/TEMC.2018.2801565 ↗
13. Electric fields preceding cloud-to-ground lightning flashes10.1029/JC087iC07p04883 ↗
14. A polarity-dependent spark-gap operated as a very high-power diode
15. Corona initiated from grounded objects under thunderstorm conditions and its influence on lightning attachment10.1088/0963-0252/17/2/024015 ↗
16. Responses of lightning rods to nearby lightning10.4271/2001-01-2907 ↗