Vacuum arc characteristics of an AMF–TMF composite contact with fixed AMF contacts under different opening velocities
Source abstract
Abstract
The objective of this paper is to determine the vacuum arc characteristics of a novel axial magnetic field (AMF)–transverse magnetic field (TMF) composite contact under different opening velocities. The AMF–TMF composite contact consists of a pair of outer fixed AMF contacts and a pair of inner movable TMF contacts. Drawn arc experiments were carried out in an L–C discharging circuit with this composite contact system to observe the differences in the arc development process under different opening velocities. The opening velocity of the inner movable contact was set to 1.3, 1.8, and 2.3 m/s. The arc current was up to 20 kA rms. In the experiments, the arc behavior was recorded using a high-speed camera. The arc current of each contact and the arc voltage were measured. Then the arc characteristics, including the arc current transfer characteristics, diffused arc duration, and mental droplet distribution before zero current, were quantitatively analyzed. Furthermore, magnetic field calculation was carried out to explain why the arc characteristics are different under different opening velocities. Experimental results show that with an increase in the opening velocity from 1.3 to 2.3 m/s, the diffused arc duration before zero current increases from 1.05 to 1.75 ms when the cathode is on the fixed side and increases from 1.30 to 1.90 ms when the anode is on the fixed side. In addition, the quantity of mental droplets between contacts before zero current is less with high opening velocity. It indicates stronger short-current breaking capacity under higher opening velocity. From the simulation results, it can be seen that during the arcing period, more current transfers to the fixed AMF contact under higher opening velocity and generates a stronger AMF. It could explain the earlier diffusion of the vacuum arc column under higher opening velocity.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Vacuum and Plasma Arcs · Electrical Fault Detection and Protection · Advanced Sensor Technologies Research
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Key Laboratory of Electrical Insulation and Power Equipment, Xi’an Jiaotong University , Xi’an 710049, China
Funding
Science and Technology Project of China State Grid Co., Ltd.
References (24)
Show source-provided references
1. Vacuum interrupters: The new technology for switching and protecting distribution circuits10.1109/28.649962 ↗
2. Development and technology of high voltage VCBs; breaf history and state of art
3. Distribution of cathode current density and breaking capacity of medium voltage vacuum interrupters with axial magnetic field10.1109/tps.2005.856531 ↗
4. Development of power vacuum interrupters10.1109/aieepas.1962.4501379 ↗
5. Motion of high-current vacuum arcs on spiral-type contacts10.1109/27.41226 ↗
6. Numerical simulation of a moving high-current vacuum arc driven by a transverse magnetic field (TMF)10.1109/tps.2007.896756 ↗
7. Vacuum arc under an axial magnetic field and its interruption ability10.1049/piee.1979.0079 ↗
8. Estimation of critical axial magnetic field to prevent anode spots in vacuum interrupters10.1109/tps.2014.2341744 ↗
9. High-current vacuum arc mode transition of a horseshoe-type axial magnetic field contact with long contact gap10.1109/tps.2017.2703810 ↗
10. Design optimization of a 3/4 coil-type axial magnetic field contact for 126 kV vacuum interrupter
11. Interrupting capability of the AMF electrodes in the external transverse field
12. Vacuum arcing behavior between transverse magnetic field contacts subjected to variable axial magnetic field10.1063/1.4954301 ↗
13. Theoretical and experimental investigation of new innovative TMF-AMF contacts for high-current vacuum arc interruption10.1109/tps.2013.2273178 ↗
14. A novel vacuum interrupter contact design for improved high current interruption performance based on a double-TMF arc control system10.1109/tps.2015.2416517 ↗
15. New arc control design for vacuum interrupters10.1109/tps.2013.2265414 ↗
16. Vacuum arc behavior and its voltage characteristics in drawing process controlled by composite magnetic fields along axial and transverse directions10.1063/1.4933306 ↗
17. Experimental investigation and numerical simulation of triggered vacuum arc behavior under TMF/RMF-AMF contact10.1088/0022-3727/49/23/235206 ↗
18. Transformation characteristics of high-current vacuum arcs with still-spaced contacts under TMF-AMF combined magnetic fields10.1109/tps.2019.2920946 ↗
19. 2008 · 189
20. Design parameter optimization of a 126 kV horseshoe type axial magnetic field vacuum interrupter
21. Interruption ability of vacuum interrupters subjected to axial magnetic fields10.1049/piee.1972.0356 ↗
22. Numerical simulation of the residual charge of vacuum interrupters10.1109/27.964469 ↗
23. Recovery of breakdown strength of a vacuum interrupter after extinction of high currents10.1109/94.993737 ↗
24. Vacuum interrupters equipped with TMF contacts and contact material different from each other; a study under short circuit current conditions and high-speed arc observation during current interruption