Research on the process of arc deionization under explosive high-speed airflow in semienclosed space
Source abstract
Abstract
To study the process by which an explosive high-speed airflow extinguishes an arc and the characteristics of arc dielectric recovery in a semienclosed space, this study investigates the principles and processes of the formation, development, and extinction of an arc under the action of a high-speed airflow. When the impact arc occurs in a semienclosed arc-extinguishing chamber, the high-speed air suppresses arc development. Due to the high-speed airflow, the arc cools at an accelerated rate; the arc energy weakens, breakpoints occur, and the continuity of the arc energy channel is broken, preventing the arc from forming in the arc-extinguishing chamber and extinguishing it. This article employs AUTODYN software to establish a model for high-speed airflow arc extinguishing in a semienclosed space and then reveals a process by which a high-speed airflow extinguishes an arc in such a space. To verify whether a high-speed airflow can extinguish an arc, we conduct experiments in which high-speed airflow extinguishes a large impact arc and a power frequency arc. We recorded the arc extinguishing process with high-speed and ordinary cameras. The time taken to extinguish the arc is approximately 7 ms, and the arc does not regenerate.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Electrical Fault Detection and Protection · Vacuum and Plasma Arcs · Welding Techniques and Residual Stresses
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
School of Electrical Engineering, Guangxi University , Nanning 530004, China
Funding
Innovation Project of Guangxi Education · National Natural Science Foundation of China
References (19)
Show source-provided references
1. Time dependence of anode spot formation threshold current in vacuum arcs10.1109/tps.1978.4317120 ↗
2. Study on shunt gap lightning protection for 110 kV and 220 kV composite insulators10.13335/j.1000-3673.pst.2002.10.011 ↗
3. Experimental research on large power frequency current of parallel gap of insulator strings10.13336/j.1003-6520.hve.2008.07.032 ↗
4. Lightning protection study of transmission line, Part III: Protection measures10.13336/j.1003-6520.hve.2009.12.007 ↗
5. Influence of chamber structure on arc quenching in multigap system10.1049/hve.2019.0064 ↗
6. Study on impulse quenching based multichamber arc quenching structure10.1063/1.5113853 ↗
7. Modelling of metal oxide arrester for very fast transients10.1049/iet-smt.2010.0129 ↗
8. CFD calculation of pressure rise due to internal AC and DC arcing in a closed container10.1109/tpwrd.2011.2108320 ↗
9. Numerical analyses on the interaction of arc and flow field for SF6 circuit breaker10.1109/tmag.2006.872476 ↗
10. Flashover characteristics of upper air clearances and lightning withstand level for ±500 kV DC double-circuit transmission line towers10.13334/j.0258-8013.pcsee.2010.28.010 ↗
11. Analysis of aspects of lightning strokes to large-sized transmission lines10.1109/tdei.2011.5704509 ↗
12. Overhead lines lightning protection by multi-chamber arresters and insulator-arresters10.1109/tpwrd.2010.2076368 ↗
13. Influence of an explosion air shock wave on arc quenching inside a cylinder10.1063/1.5129426 ↗
14. An approach to suppress lightning overvoltage of 35 kV overhead transmission line by air-blast arc-quenching gap10.13335/j.1000-3673.pst.2012.02.034 ↗
15. Experimental studies of breakdown characteristics of a 12-kV arcing horn under a lightning impulse superimposed on AC voltage
16. Arc extinguishing mechanism of jet stream interrupter gap lightning protection device10.13335/j.1000-3673.pst.2011.05.030 ↗
17. Lightning impulse discharge performance and voltage correction of long air gaps at lower atmospheric pressure10.13334/j.0258-8013.pcsee.2005.11.028 ↗
18. The arc energy process simulation of the high voltage self-blast SF6 circuit breaker
19. Arc motion and gas flow in current limiting circuit breakers operating with a low contact switching velocity10.1109/tcapt.2002.804607 ↗