Study on insulation defect discharge features of dry-type reactor based on audible acoustic
Source abstract
Abstract
The audible signal (20 Hz to 20 kHz) generated during the operation of a dry-type reactor is one of the key features to evaluate its operation state. However, at present, the time/frequency domain features of the audible signal under typical insulation defects are not clear, which makes it difficult to effectively carry out the fault diagnosis of the dry-type reactor based on audible signals. Based on this, the audible signal features under typical insulation defect discharge of the dry-type reactor are studied in this paper. Three typical insulation defect discharge models (metal protrusion defect, pollution defect, and metal foreign bodies defect) are simulated; then, the discharge acoustic signals are collected under the voltage of 8 kV. Analysis of acoustic signal features shows that the acoustic signal of metal protrusion defect discharge occurs in the positive half cycle of power frequency with the cycle of 20 ms. Both pollution defect discharge and metal foreign bodies defect discharge show intermittent discharge; during the discharge, the discharge acoustic signal of pollution defect has features similar to that of metal protrusion defect, while the discharge of metal foreign bodies defect shows randomness with a larger amplitude of discharge acoustic signal (up to 110 dB). Based on the frequency domain feature vectors’ extraction, it is found that the odd harmonic component of the metal protrusion defect discharge acoustic signal accounts for more than twice the even-order harmonic, and the high-frequency energy (12.5–25 kHz) is the main component. The discharge acoustic signal of the metal foreign bodies defect is mainly low-frequency energy, and the high-frequency energy proportion of pollution defect discharge acoustic signal is similar to that of low-frequency energy. In addition, the variance of high-frequency energy ratio (Rhf) of the metal foreign bodies defect discharge acoustic signal is 5.25 and 21 times that of the metal protrusion defect and pollution defect. This study provides some technical support for further detection and assessment of the operation state of the dry-type reactor based on audible signals.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Power Transformer Diagnostics and Insulation · High voltage insulation and dielectric phenomena · Non-Destructive Testing Techniques
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Power Science Research Institute of State Grid Ningxia Power Co. 1 , Yinchuan 750011, China
Hubei Engineering Research Center for Safety Monitoring of New Energy and Power Grid Equipment, Hubei University of Technology 2 , Wuhan 430068, China
References (23)
Show source-provided references
1. Acoustic aspects of dry-type air-core reactors-specification, design, testing, field measurements10.1007/s00502-016-0452-4 ↗
2. Numerical simulation and detection of dry-type air-core reactor temperature field based on laminar-turbulent model10.1063/5.0037955 ↗
3. AC and DC temperature rise characteristics of large capacity dry-type air-core reactors based on isothermal isobaric design method10.13648/j.cnki.issn1674-0629.2019.12.011 ↗
4. A wireless differential protection system for air-core inductors10.1109/tpwrd.2005.844351 ↗
5. Air-core dry-type shunt reactor protection based on an alternative current alpha plane10.1049/gtd2.12005 ↗
6. Sound field calculation of shunt reactor based on vibration measurement10.13296/j.1001-1609.hva.2019.11.015 ↗
7. Condition monitoring of electrical equipment using thermal image processing
8. On-site partial discharge test technology of ultra high voltage converter transformer10.13336/j.1003-6520.hve.2011.09.033 ↗
9. Influence of the multi-component electrical feed of air-core industrial reactors on their sound radiation10.1051/aacus/2020015 ↗
10. Non-contact detection method for series dry-type reactor10.3969/j.issn.1007-1547.2014.24.062 ↗
11. Reactor abnormal noise analysis based on sound source localization
12. Inter-turn fault detection of dry-type transformers using core-leakage fluxes10.1109/tpwrd.2018.2878460 ↗
13. Online detection of inter-turn short circuit faults in dry-type air-core reactor10.3233/jae-2012-1494 ↗
14. Operation and maintenance of dry air-core reactor10.3969/j.issn.1001-1609.2004.03.029 ↗
15. Research on the online measuring technology of inter-turn insulation of dry air-core reactor10.1049/iet-smt.2019.0553 ↗
16. Analysis of the influence of electric field on the insulation of dry-type air-core reactor10.14044/j.1674-1757.pcrpc.2015.06.017 ↗
17. Discussion on operation and maintenance of dry-type air-core reactor10.3969/j.issn.1007-3175.2017.04.018 ↗
18. Feasibility analysis of impedance monitoring method for turn-to-turn insulation fault of dry-type air-core reactor
19. Cause analysis and solution of burning failure of 10 kV dry-type air-core series reactor
20. An investigation of surface tracking characteristics and factors influencing epoxy resin pouring insulation for dry-type reactors10.1007/s13233-019-7038-z ↗
21. Optimized sleeve monopole antenna for detection of electrostatic discharge radiation of spacecraft solar array10.1063/1.5027881 ↗
22. Statistics and analysis of audible noise features of 110 kV transformers10.13296/j.1001-1609.hva.2019.11.016 ↗
23. Vibration mechanism and influence factors in power transformers10.7652/xjtuxb201506019 ↗