journal article·2017-05-01Open access

Transformer sound level caused by core magnetostriction and winding stress displacement variation

Chang-Hung Hsu, Yi-Mei Huang, Min-Fu Hsieh, Chao-Ming Fu, Shiva Adireddy, Douglas B. Chrisey

AIP Advances· Volume 7· Issue 5

Abstract

Magnetostriction caused by the exciting variation of the magnetic core and the current conducted by the winding wired to the core has a significant result impact on a power transformer. This paper presents the sound of a factory transformer before on-site delivery for no-load tests. This paper also discusses the winding characteristics from the transformer full-load tests. The simulation and the measurement for several transformers with capacities ranging from 15 to 60 MVA and high voltage 132kV to low voltage 33 kV are performed. This study compares the sound levels for transformers by no-load test (core/magnetostriction) and full-load test (winding/displacement ε). The difference between the simulated and the measured sound levels is about 3dB. The results show that the sound level depends on several parameters, including winding displacement, capacity, mass of the core and windings. Comparative results of magnetic induction of cores and the electromagnetic force of windings for no-load and full-load conditions are examined.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Magnetic Properties and Applications · Power Transformer Diagnostics and Insulation · Power Quality and Harmonics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Fortune Electric Company 1 Research and Development Center, , Taoyuan 320, Taiwan

National Central University 2 Department of Mechanical Engineering, , Taoyuan 320, Taiwan

National Cheng Kung University 3 Department of Systems and Naval Mechatronic Engineering, , Tainan 701, Taiwan

National Taiwan University 4 Department of Physics, , Taipei 10617, Taiwan

Tulane University 5 Department of Physics and Engineering Physics, , New Orleans, Louisiana 70118, USA

References (7)

Show source-provided references
1. The impact of vibration due to magnetostriction on the core losses of ferrite toroidals under DC bias10.1109/tmag.2011.2129523 ↗
2. Magnetic flux distributions in transformer core joints10.1109/61.847251 ↗
3. Influence of geometric parameters on the magnetic properties of model transformer cores10.1016/0304-8853(96)00099-6 ↗
4. Correlation of magnetostriction variation on magnetic loss and noise for power transformer10.1063/1.4919122 ↗
5. Suppressing magneto-mechanical vibrations and noise in magnetostriction variation for three-phase power transformers10.1063/1.4919040 ↗
6. Aspects of design of power transformer for noise reduction
7. Reducing audible noise for distribution transformer with HB1 amorphous core10.1063/1.3553939 ↗