Thermal-flow characteristics analysis of a novel resilient capacity ceramic insulated winding dry type transformer
Source abstract
Abstract
With the increasing demand for the resilient capacity of transformers in high-proportion renewable energy grids, the overload capacity of transformers and the thermal conductivity of winding insulation materials have been put forward as important requirements. In response to these requirements, a novel ceramic high temperature tolerance insulation winding is proposed in this paper and is applied in a ceramic insulated winding transformer. A combination of simulation and experimentation is used to analyze the thermal-flow characteristics of this transformer. The temperature and flow field distribution characteristics of transformers with both winding insulation methods (ceramic and Nomex paper) are compared. The internal mechanism of reflux near the iron core and high voltage winding under forced air cooling is clarified. A superior outside cooling condition is obtained. A prototype ceramic insulated winding transformer is developed and tested to verify the accuracy of the simulation model. The results show that the hotspot temperature of the ceramic insulated winding transformer under natural cooling is 10.7% lower than that of the Nomex paper insulated winding transformer. With forced air cooling of 2, 3, 4, 5, and 6 m/s applied at the bottom, the hotspot temperature of the ceramic insulated winding transformer is 11.4%, 10.5%, 9.7%, 14.0%, and 17.8% lower than that of the Nomex paper insulation winding transformer, respectively. Under forced air cooling, a reflux phenomenon is observed in both transformers in the vicinity of the iron core and high voltage winding due to the formation of adverse pressure gradient region and wall viscous force blocking. The strength of the reflux is affected by the magnitude of the forced air cooling flow velocity and the construction of the transformer. The optimal range of the external cooling flow velocity for the ceramic insulated winding transformer is 3–4 m/s. The errors between the simulated temperature and the measured temperature at the nine monitoring points of the prototype are all less than 5%, which verifies the effectiveness of the simulation model. The experimental and theoretical basis for the design and application of resilient capacity dry type transformers is provided by this research.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena · Power Transformer Diagnostics and Insulation · Aerosol Filtration and Electrostatic Precipitation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
School of Electrical Engineering, Xi’an Jiaotong University 1 , Xi’an 710049, China
Zhuji Sino-Russian Joint Materials Laboratory 2 , Shaoxing 311800, China
References (25)
Show source-provided references
1. Use of aramid paper in the magnetic pole of hydro-generator
2. Research on thermal aging characteristics of dry-type transformer epoxy resin based on dielectric response and activation energy
3. Assessing the condition of Nomex paper-based insulation in open wound and VPI type dry-type transformer using frequency domain spectroscopy data
4. Effect of higher insulation material thermal conductivity on transformer temperature rise
5. Thermal conductivity of nano-filled epoxy systems
6. The performance improvement of aramid insulation paper by nano-SiO2 modification10.1109/tdei.2017.006560 ↗
7. Effects of thermally conducting particles on resistance to tracking failure of polyimide/BN composites
8. Thermal behaviour of epoxy resin filled with high thermal conductivity nanopowders
9. Influence of fiber diameters on the thermal conductivity of liquid crystal epoxy resin film
10. High thermal conductive epoxy resins with controlled high order structure
11. Optimization of power frequency withstand voltage characteristics of thermal electrochemical oxide ceramic film based on machine learning
12. Semi-empirical model for precise analysis of copper losses in high-frequency transformers10.1109/access.2018.2797359 ↗
13. Improvement and application of dynamic thermal circuit model for oil-immersed power transformer
14. The modified thermal circuit model for three-phase unbalanced operation of distribution transformers
15. Thermal field study of induction rotary transformer based on electric-thermal coupling theory
16. Dynamic analysis of transformers with second-generation high-temperature superconductors10.1109/tasc.2016.2540804 ↗
17. A study of thermal model of the discrete type transformer based on finite element method
18. Thermal analysis of cast-resin dry-type transformers10.1016/j.enconman.2011.02.006 ↗
19. Sensitivity study of transient temperature of cast-resin dry type transformer
20. Modeling method for thermal field of turbulent cooling dry-type on-board traction transformer in EMUs10.1109/tte.2021.3097876 ↗
21. Z. Yan , “Study on insulation characteristics of aluminum alloy micro-arc oxidation ceramic film and optimization of key process parameters,” Master’s Degree Thesis (Xi’an Jiaotong University, Xi’an, 2022).
22. Effects of SiO2 nanoparticles in electrolytes on growth process and surface properties of alumina coatings formed on 7A52 aluminium alloy by micro-arc oxidation
23. Y. Zhou , “Microstructure control and properties of aluminum alloy micro arc oxidation film,” Master’s Degree Thesis (South China University of Technology, 2016).
24. Thermal radiation intensities in mid-infrared region from semiconductor-metal micro-grating structure
25. 2015 · 175