Electric field distribution analysis of polluted composite insulators based on COMSOL
Source abstract
Abstract
In humid weather conditions, contamination on the surface of composite post insulators becomes wet. Under the thermal effect of leakage current, this wet contamination may lead to the formation of dry bands, which can trigger flashover accidents. Based on this, COMSOL software is used to analyze the electric field distribution of insulators under polluted conditions and after the formation of dry bands. The results indicate that the electric field intensity on the surface of contaminated insulators is significantly higher than that of clean ones, making field distortion more likely. Wet contamination adhering to the insulator surface forms dry bands under the influence of leakage current. The thinner the wet contamination layer and the higher its conductivity, the greater the leakage current density. The leakage current between the sheds is higher than that on the upper and lower surfaces, making dry bands more likely to form in these regions. As the width of the dry band increases, the electric field strength on the upper and lower surfaces of the shed groups increases, while the field strength between the sheds decreases. In all cases, the maximum electric field intensity occurs at both ends of the dry band. When a dry band forms between sheds, it has the most significant impact on the surface electric field of the insulator. Moreover, as the number of dry bands increases, the overall surface electric field intensity tends to decrease.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Guangxi Key Laboratory of Power System Optimization and Energy Technology, Guangxi University 1 , Nanning, Guangxi 530004,
School of Electrical Engineering, Guangxi University 2 , Nanning, Guangxi 530004,
Guangxi University 3 , Nanning, Guangxi 530004,
Wuzhou Bureau of the EHV Power Transmission Company Under China Southern Power Grid 4 , Wuzhou, Guangxi,
Funding
National Natural Science Foundation of China
References (30)
Show source-provided references
1. Research on electric field simulation of composite insulators under polluted conditions10.16188/j.isa.1003-8337.2014.05.010 ↗
2. Influence of dry bands on polluted insulator performance
3. Flashover process and frequency analysis of the leakage current on insulator model under non-uniform pollution conditions10.1109/tdei.2010.5539701 ↗
4. Prediction of pollution flashover voltages of ceramic string insulators under uniform and non-uniform pollution conditions10.1016/j.jesit.2016.01.003 ↗
5. Electric field and potential distribution evaluation of environmentally polluted 11 kV polymeric outdoor insulators
6. Study on local arc development and influencing factors of insulator pollution flashover
7. Effect of pollution performance on an 11 kV post-type insulator considering the simulation of electric potential and field distribution
8. 2018
9. Study on local arc characteristics of contaminated insulation surfaces with attached metal bodies10.13334/j.0258-8013.pcsee.182335 ↗
10. Time-frequency characteristics of dry band discharge on surface of composite insulators under low pressure10.13336/j.1003-6520.hve.2014.08.014 ↗
11. Study on the influence of dry bands on the electric field distribution of substation post insulators
12. Influence of dry bands on the electric field distribution of polluted post insulators10.13336/j.1003-6520.hve.2011.02.009 ↗
13. Flashover voltage of insulator string under various conditions
14. Effect of uneven wetting on E-field distribution along composite insulators
15. The behaviour of insulator strings under dry and wet conditions
16. Study on temperature field of wet polluted insulators10.16790/j.cnki.1009-9239.im.2017.10.008 ↗
17. Influence of RTV coating and creepage-enhancing skirt on electric field distribution of insulators10.13336/j.1003-6520.hve.2007.03.022 ↗
18. Influence of contaminated location on streamer discharge10.1016/j.epsr.2023.109243 ↗
19. Study on surface contamination characteristics of DC insulators under high electric field10.20097/j.cnki.issn1007-9904.2024.08.009 ↗
20. A new method for calculating the surface electric field of high-voltage composite insulators with contaminated thin layers10.19595/j.cnki.1000-6753.tces.2016.10.009 ↗
21. Study on spatial electric field distribution characteristics of composite insulators under different surface conditions
22. Dry band formation and its influence on electric field distribution along polluted insulator
23. Study on leakage current characteristics and influence factors of 110 kV polluted composite insulators
24. Surface contamination detection of composite insulators based on leakage current
25. Live washing test and analysis of surface electric field of substation post insulators in chemical pollution area10.16790/j.cnki.1009-9239.im.2019.01.015 ↗
26. Study on test method of artificial pollution simulating natural pollution for glass insulators10.13296/j.1001-1609.hva.2018.10.012 ↗
27. Simulation study on the surface charge accumulation characteristics of silicone rubber composite insulators
28. Effect of pollution layer discontinuity due to the dry bands presence on potential and electric field along insulator
29. Investigation of pollution severity and dry band characteristics on 11 kV composite insulator
30. Effect of dry band location on electric field distribution along a polymeric insulator under contaminated conditions