Discharge characterization and altitude correction of shielding sphere-plate gap at an altitude of 3400 m
Source abstract
Abstract
Southeast Tibet in China is rich in clean energy such as water energy, light energy, and wind energy. As the key means of large-scale clean energy transmission in southeast Tibet, the ultra-high voltage (UHV) power transmission projects will be constructed at an altitude of nearly 4000 m. To accurately acquire the external insulation strength of electrical equipment operating at different altitudes, the standard positive switching impulse voltages were applied to a rod electrode and a 1.1 m diameter shielding sphere at the altitude of 3400, 2100, and 80 m. The switching impulse discharge characterization and altitude correction factors of the 1.1 m diameter shielding sphere-plate gap under different clearances at different altitudes were obtained. The discharge voltage of the rod-plate gap at the altitude of 80 m was corrected to the altitude of 3400 m using altitude correction methods recommended by GB 311.1, GB/T 16927.1, and DL/T 2305. Further comparison was made between the calculation results using the three altitude correction methods mentioned above and the test results at an altitude of 3400 m. The discharge characterization and the minimum clearance of the end fittings of the electrical equipment in the valve hall at the altitude of 3800 and 4500 m were obtained by fitting and extrapolating the test data. The research results provide important reference significance for the external insulation configuration of UHV converter stations constructed in areas with an altitude of 3000 m and above.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena · Thermal Analysis in Power Transmission · High-Voltage Power Transmission Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
National Engineering Research Center of UHV Technology and New Electrical Equipment, Electric Power Research Institute, China Southern Power Grid 1 , Guangzhou 510663, China
North China Electric Power University (Baoding) 2 , Baoding 071003, China
Funding
The Research on Long Air Gap Discharge Characteristics and Altitude Correction in High Altitude Areas of the China Southern Power Grid Electric Power Research Institute
References (32)
Show source-provided references
1. Research on key technologies in ±1100 kV ultra-high voltage DC transmission10.1049/hve.2018.5023 ↗
2. Influence of modeling methods on the calculated lightning surge overvoltages at a UHVDC converter station due to backflashover10.1109/tpwrd.2012.2190306 ↗
3. A local discontinuous Galerkin method for 1.5-dimensional streamer discharge simulations10.1016/j.amc.2013.03.118 ↗
4. An efficient and accurate MPI-based parallel simulator for streamer discharges in three dimensions10.1016/j.jcp.2019.109026 ↗
5. Streamer inception time delay characteristics under high altitude positive switching impulse voltage10.13336/j.1003-6520.hve.20210208 ↗
6. Distribution characteristics for initial time delay of streamer of shielding spheres under operating impulse voltage at high altitudes10.1088/1361-6463/ac7114 ↗
7. Statistical time delay characteristics of large diameter sphere-plane gap discharge under positive switching impulse voltage at altitude of 2200 m10.13336/j.1003-6520.hve.20220827 ↗
8. Thermodynamic properties of negative discharge channels in a 1-m air gap measured by optical interferometry10.1109/tps.2018.2882231 ↗
9. 2-D discontinuous Galerkin method for streamer discharge simulations in nitrogen10.1109/tmag.2013.2240669 ↗
10. Streamer-to-leader transition model of sphere-plane long air gap at positive switching impulse voltage10.13334/j.0258-8013.pcsee.202390 ↗
11. Influence of protrusions on the positive switching impulse breakdown voltage of sphere-plane air gaps in high-altitude areas10.1049/iet-smt.2019.0184 ↗
12. Voltage correction factors for air-insulated transmission lines operating in high-altitude regions to limit corona activity: A review10.3390/en11071908 ↗
13. Positive switching impulse discharge performance and voltage correction of rod-plane air gap based on tests at high-altitude sites10.1109/tpwrd.2008.2002969 ↗
14. Computation of breakdown voltage of long rod-plane air gaps in large temperature and humidity range under positive standard switching impulse voltage10.1016/j.epsr.2020.106518 ↗
15. Influence of air density on electrical strength of transmission line insulation10.1109/tpas.1967.291918 ↗
16. Influence of air density on the impulse strength of external insulation10.1109/tpas.1985.319134 ↗
17. 1989
18. 1996
19. 2011
20. 2012
21. Experimental study on branch and diffuse type of streamers in leader restrike of long air gap discharge10.1088/1009-0630/18/3/15 ↗
22. Study on the altitude correction method for external lnsulation parameters in high altitude areas10.13648/j.cnki.issn1674-0629.2011.02.017 ↗
23. The dynamic expansion of leader discharge channels under positive voltage impulse with different rise times in long air gap: Experimental observation and simulation results10.1063/1.5085852 ↗
24. Analysis on altitude correction of switching impulse discharge voltage for long rod-plate air gaps based on the g-method10.13334/j.0258-8013.pcsee.170260 ↗
25. Switching impulse discharge characteristics and altitude corrections for typical long air gaps at high altitude areas10.3969/j.issn.1003-6520.2013.06.022 ↗
26. Influence of front time on positive switching impulse discharge characteristics of UHVDC tower gaps10.1016/j.epsr.2019.02.024 ↗
27. Experimental research on typical air gap test voltage correction10.13334/j.0258-8013.pcsee.2012.28.023 ↗
28. Flashover tests on air gap of ±800kV DC transmission line under composite DC and switching impulse voltage10.1109/tdei.2014.004003 ↗
29. Study on calculation of air clearance for valve Hall and DC field of ±800 kV converter station at the altitude of 3000 m10.15919/j.cnki.qhep.2020.01.003 ↗
30. Air clearance and its altitude correction method for the DC side of converter stations10.3969/j.issn.1674-0629.2009.06.006 ↗
31. Uncertainty in measurement analysis of 50% discharge voltage of long air gap10.13648/j.cnki.issn1674-0629.2022.07.004 ↗
32. 2021