Effect of moisture on the electric field and breakdown voltage of XLPE cable interconnectors
Source abstract
Abstract
Dampness in the joint is a common defect of power cables, and the influence of moisture on the performance of the intermediate joint is very important. The electric field distribution of the joint is analyzed by simulation, and the XLPE sample is used as an experimental object to test the breakdown voltage under different damp levels. Simulation results show that in the composite interface outside the main insulation, the electric field at the water film is only 20%–60% of normal. However, the electric field around the water film generally increases, and as the degree of moisture increases, the electric field distortion becomes more serious, which is prone to inducing breakdown accidents. The electric field around the water film outside the conductor has no obvious distortion and will not directly induce accidents. Through the breakdown voltage experiment of the damp XLPE sample, it is found that the average breakdown voltage is 85%–94% of normal, and it decreases with the increase of moisture. The experimental results are consistent with the simulation results. The results can be used to guide the cause analysis of cable intermediate joint accidents.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena · Electrostatic Discharge in Electronics · Dielectric materials and actuators
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Beijing Electric Power Company 1 , Beijing,
State Grid Beijing Electric Power Research Institute 2 , Beijing,
Funding
Technology Project of State Grid Beijing Electric Power Company
References (20)
Show source-provided references
1. Improvement of insulation defect identification for DC XLPE cable by considering PD aging10.1016/j.ijepes.2019.105409 ↗
2. A new method for local defect location of power cable based on reflection coefficient spectrum10.13335/j.1000-3673.pst.2016.2859 ↗
3. Current status of research on cable joint internal defect assessment methods
4. Temperature prediction of high-voltage power cable joints based on PSO-LSSVM
5. Research and analysis of transient model of electromagnetic-thermal-mechanical coupling field of cable joints
6. Accelerated water tree aging of crosslinked polyethylene with different degrees of crosslinking10.1016/j.polymertesting.2016.09.014 ↗
7. A possible water tree initiation mechanism for service-aged XLPE cables: Conversion of electrical tree to water tree10.1109/tdei.2016.005405 ↗
8. The effect of moisture at the composite interface of cable joint on its flashover characteristics10.13336/j.1003-6520.hve.20181031032 ↗
9. Research on damp insulation characteristics of 10 kV XLPE cable10.12253/j.issn.2096-3661.2020.14.3112 ↗
10. Research on moisture detection criterion of XLPE cable insulation based on ultra-low frequency dielectric loss
11. Treatment of 110 kV cable terminal damp in Xiamen electric power Bureau10.3969/j.issn.1003-6520.2004.07.026 ↗
12. Insight into the influence of mechanical orientation on the growth of water trees from abnormal water tree morphology10.13334/j.0258-8013.pcsee.152216 ↗
13. Analysis of low-frequency loss characteristics of insulated aging cables based on PDC method
14. Water tree growth characteristics of XLPE cable under different acid and alkali environments from the perspective of ion nature10.13336/j.1003-6520.hve.20181206012 ↗
15. Analysis of interfacial polarization characteristics of water tree aged XLPE cable based on polarization depolarization current method10.19595/j.cnki.1000-6753.tces.190686 ↗
16. Electric field simulation of insulation defects in cable line intermediate joints and partial discharge detection in discharge chamber
17. Research progress on aging and diagnostic methods of XLPE cables10.16790/j.cnki.1009-9239.im.2016.11.006 ↗
18. Electrical tree growth and partial discharge characteristics of XLPE cable under high temperature and high pressure10.13336/j.1003-6520.hve.20180430004 ↗
19. Theoretical analysis and experimental study of partial discharge test of 10 kV cable oscillation wave
20. Temperature and pressure distribution simulations of 3-km-long high-temperature superconducting power cable system with fault current for 66-kV-class transmission lines10.1109/tasc.2017.2656631 ↗