Research on propagation law of partial discharge ultrasonic signal in converter transformer
Source abstract
Abstract
When local discharge occurs inside the transformer, it will be accompanied by a burst sound to generate an ultrasonic signal, which can be used for fault monitoring and diagnosis inside the transformer. This paper focuses on studying the converter transformer and simulating and analyzing the location where local discharge is likely to occur in the converter transformer. The provided information includes the distribution of sound pressure within and outside the converter transformer and the impact of the winding on this distribution. Furthermore, the investigation focuses on the testing of local discharge in converter transformers using ultrasonic signals. A local discharge detection device for converter transformers has been developed. The experiment and analysis have been conducted, and what was learned was compared to the simulated outcomes. The determination of the local discharge position in converter transformers is based on the analysis of the time-varying waveform obtained at the observation point. This approach offers a novel method for finding and identifying local discharge.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: High voltage insulation and dielectric phenomena · Power Transformer Diagnostics and Insulation · Ultrasonics and Acoustic Wave Propagation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Corporation Limited 1 , Beijing 100031, China
Nanrui Group (State Grid Electric Power Research Institute) Co., LTD 2 , Nanjing 211106, China
State Grid Electric Power Research Institute Wuhan Nanrui Co., LTD 3 , Wuhan 430074, China
Tbea Hengyang Transformer Co., LTD 4 , Hengyang 421007, China
References (20)
Show source-provided references
1. Comparison of orientation algorithms of ultrasonic receiving array for partial dis-charge localization in oil
2. Partial discharge plant-monitoring technology: Present and future-developments10.1049/ip-smt:19951438 ↗
3. Diagnostic analysis of internal discharge of 500 kV transformer based on double joint positioning method10.16527/j.issn.1003-6954.20240116 ↗
4. Analysis of metal discharge defect of 35 kV SVG station transformer
5. Principle and modeling of partial discharge pattern recognition in power transformer10.19432/j.cnki.issn1006-2394.2024.01.008 ↗
6. Experimental study on propagation characteristics of high frequency pulse current in power transformer based on 110 kV solid model10.13296/j.1001-1609.hva.2023.12.018 ↗
7. Research on the application of ultrasonic partial discharge detection technology in power transformers10.1109/ei250167.2020.9347006 ↗
8. Research on ultrasonic array location of two PD sources in power transformer
9. Research on partial discharge signal denoising of transformer based on improved CEEMD and adaptive wavelet threshold10.1109/IAECST54258.2021.9695898 ↗
10. Propagation behaviour of acoustic partial discharge signals in oil-filled transformers
11. Analysis of acoustic wave propagation in a power transformer model10.12693/aphyspola.116.428 ↗
12. Partial discharge. XIII. Acoustic partial discharge detection-fundamental considerations10.1109/57.145095 ↗
13. Signal direction finding method of partial discharge ultrasonic array based on signal subspace conversion and fast subspace direction finding algorithm10.13335/j.1000-3673.pst.2011.10.040 ↗
14. Ultrasonic signal characteristics and discharge source location of transformer partial dis-charge10.3969/j.issn.1003-6520.2003.05.005 ↗
15. Study on ultrasonic phased receiving array sensor for partial discharge localization in oil
16. GCC-MSSA-based PD ultrasonic internal localization method for transformers10.19651/j.cnki.emt.2210596 ↗
17. Comparative study of PD ultrasonic and UHF detection methods for power transformers10.3969/j.issn.1004-289X.2014.03.007 ↗
18. Comparison of the acoustic performance and positioning accuracy of three kinds of planar partial discharge ultrasonic array sensors10.1049/iet-rsn.2015.0097 ↗
19. Analysis and treatment of an abnormal partial discharge test of UHV transformer
20. Diagnosis and analysis of partial Discharge Fault in 220 kV transformer10.19487/j.cnki.1001-8425.2021.07.01 ↗