Research on the electric life evaluation technology of the arc extinguishing chamber of the 550 kV circuit breaker
Source abstract
Abstract
When the circuit breaker is switched on and off, the phenomenon of arc ablation will occur. Under the action of the electric arc, the surface of the contact is constantly damaged, resulting in deformation and material evaporation. With the increase in the electric arc temperature, the material loss on the contact surface of the circuit breaker increases. In this paper, according to the three major factors affecting the electrical life of the circuit breaker arc extinguishing chamber—the state of the arc contact, the nozzle, and the SF6 gas—the corresponding test detection methods and evaluation methods are proposed. With the continuous accumulation of the breaking current, the effective contact displacement between the arc contacts decreases and the average contact resistance increases. The effective contact displacement decreases exponentially with the increase in the cumulative breaking energy. The content of CF4 can be used not only to characterize the discharge ablation on the surface of the nozzle insulating material but also to characterize the discharge decomposition degree of SF6 in the system by adding carbonaceous compounds. Through the experiment, it is suggested that CF4 should reach 600 µl/l as the threshold for judging whether the arc extinguishing chamber needs maintenance. This method can be extended to the working condition evaluation of the arc extinguishing chamber of other types of the SF6 circuit breaker.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Vacuum and Plasma Arcs · Electrical Contact Performance and Analysis · Electrical Fault Detection and Protection
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Hubei Electric Power Co., Ltd., Electric Power Research Institute 1 , Wuhan, Hubei 430077, China
State Grid Hubei Transmission and Transformation Engineering Co., Ltd. 2 , Wuhan, Hubei 430077, China
References (9)
Show source-provided references
1. Summary of CIGRE 13.06 working group worldwide reliability data and maintenance cost data on high voltage circuit breakers above 63 kV
2. Diagnosis techniques on contact electrical endurance of high voltage circuit breakers
3. A new measurement method of the dynamic contact resistance of HV circuit breakers
4. A complete strategy for conducting dynamic contact resistance measurements on HV circuit breakers10.1109/tpwrd.2008.917694 ↗
5. Study on trigger lifetime of electrode on laser-triggered vacuum switch10.1109/tps.2018.2837343 ↗
6. Research on the time delay characteristics of the laser triggered vacuum switch10.1109/tps.2015.2409196 ↗
7. Research on the pre-breakdown current of the laser-triggered vacuum switch10.1109/tps.2018.2792010 ↗
8. Investigation on erosion of Cu/W contacts in high-voltage circuit breakers10.1109/tcapt.2006.880476 ↗
9. Research on the interaction of primary plasma and main electrode for laser triggered vacuum switch10.1109/tps.2014.2362612 ↗