journal article·2025-03-01Open access

Research on electromagnetic vibration and noise of transformer under short circuit conditions

Zhongxiang Li, Wenxing Sun, Duanjiao Li, Dezhi Chen, Linglong Cai, Xian Yang, Shuo Jiang, Ziyuan Xin, Xianghui Chang, Sunjing Gong

AIP Advances· Volume 15· Issue 3

Abstract

For an open-type 50 kV A three-dimensional laminated core transformer, this paper establishes a research framework for inter-turn short-circuit faults from the perspective of the power system. First, the B–H curve and magnetostriction curve of the silicon steel sheets were measured using a single-sheet silicon steel magnetostriction measurement system, providing data support for electromagnetic, vibration, and noise analysis. Based on finite element analysis, electromagnetic and vibration characteristics of the three-dimensional laminated core transformer were simulated and analyzed, establishing a steady-state model and verifying its validity. Second, an equivalent circuit model and a finite element model for the transformer winding under inter-turn short-circuit conditions were established. Simulations were conducted to analyze current, leakage magnetic field, and electrodynamic forces. Through simulation, the effects of different short-circuit timings on the transformer’s status were examined, revealing the size and distribution of axial and radial leakage magnetic fields, as well as axial and radial electrodynamic forces under different numbers of shorted turns. Finite element simulation software was used to calculate the magnetic field, vibration, and noise in the three-dimensional laminated core transformer following an inter-turn short circuit. This study delves into the magnetic field, vibration, and noise during normal operation and under varying numbers of shorted turns, analyzing the impact of inter-turn short circuits on the performance and stability of the transformer.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Magnetic Properties and Applications · Power Transformer Diagnostics and Insulation · Geoscience and Mining Technology

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Guangdong Electric Power Science Institute, Guangdong Province 1 , 510080 Guangzhou, Guangdong,

Guangdong Power Grid Co., Ltd. 2 , Guangzhou 510000,

Key Laboratory of Special Motors and High Voltage Electrical Appliances, Ministry of Education, Shenyang University of Technology 3 , Liaoning 110870,

Dongguan Power Supply Bureau, Guangdong Power Grid Co., Ltd. 4 , Dongguan 523008,

References (14)

Show source-provided references
1. Optimizing method of measuring point position of transformer core vibration sensor
2. Three-dimensional vibration analysis of single-phase transformer winding under inter-disc fault
3. Diagnosing winding and core condition of power transformer by vibration signal analysis
4. Noise and vibration analysis of a distribution transformer10.23919/PTZE.2019.8781735 ↗
5. Diagnostic techniques used in power transformer turn to turn faults identification based on Sweep Frequency Response Analysis (SFRA)
6. Fault identification method of interturn short circuit in dry transformer based on difference of voltage and current unbalance10.19783/j.cnki.pspc.220782 ↗
7. Transformer inrush current discrimination method based on the change of excitation impedance10.13334/j.0258-8013.pcsee.2001.07.020 ↗
8. Inter-turn short circuit fault identification method of oil-immersed transformer based on electro-thermal characteristics fusion analysis10.13335/j.1000-3673.pst.2020.2054 ↗
9. Transformer inter-turn short circuit modeling and its practical application
10. Analysis of inter-turn short circuit parameters and characteristics of transformer primary side10.7500/AEPS20180702003 ↗
11. Radial stability evaluation and cumulative test of transformer windings under short-circuit condition
12. Small sample transformer fault diagnosis method based on DGA and enhanced SMOTE
13. Multi-feature fusion detection method for interturn short-circuit faults of transformers
14. Transformer fault voiceprint recognition based on repeating pattern extraction and Gaussian mixture model