journal article·2024-01-01Open access

Magnetohydrodynamic simulation and test of compression arc-extinguishing device under icing condition

Ping Huang, Shijie Xu, Honglin Qin, Guoting Yang, Junlin Huang, Zhihao Li

AIP Advances· Volume 14· Issue 1

Abstract

When the weather is cold and wet, the insulator and the transmission line components often undergo icing. In order to study the inhibition effect of the compression arc-extinguishing device with icing on the recovery of arc plasma conductivity and air disruptive strength, this paper will verify it through simulation and test. In the simulation part, a two-dimensional geometric model is established, and the magnetohydrodynamic equation group is used as the control equation group. The breakdown characteristics of the device with and without icing are compared, and the dynamic characteristics of the arc are studied in terms of temperature and conductivity. The results show that the temperature of the arc plasma can be reduced to 3000 K within 1 ms, and the conductivity can be reduced to 0 within 250 µs. In the test part, the suppression effect on arc current amplitude after the device with icing is subjected to high current impact is verified, and the coupling triggering method of impulse voltage and power frequency voltage is adopted to further verify the arc extinguishing condition of the device when the power frequency current continues. The results show that the amplitude of the arc produced by high current impulse decreases from 67 to 35 kA and to 0 within 1 ms after passing through the device with icing, and the current amplitude can still drop to 0 at 2.5 ms after adding the power frequency voltage. It is proved that the device with icing can inhibit the recovery of arc plasma conductivity and air disruptive strength.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Vacuum and Plasma Arcs · High voltage insulation and dielectric phenomena · Welding Techniques and Residual Stresses

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Guangxi Key Laboratory of Power System Optimization and Energy Technology, Guangxi University 1 , Nanning, Guangxi 530004, China

School of Electrical Engineering, Guangxi University 2 , Nanning, Guangxi 530004, China

Funding

Natural Science Foundation of Guangxi Zhuang Autonomous Region

References (20)

Show source-provided references
1. Evaluation of a direct lightning strike to the 24 kV distribution lines in Thailand10.3390/en12163193 ↗
2. Analyze the causes of lightning accidents and lightning protection measures of 10kV distribution lines
3. Analysis and discussion of comprehensive lightning protection measures for high-voltage transmission lines10.16660/j.cnki.1674-098X.2019.34.030 ↗
4. Analysis and countermeasures of lightning strike accidents on overhead transmission line10.3969/j.issn.1008-0198.2019.03.006 ↗
5. Concerns of corrosive effects with respect to lightning protection systems10.1016/j.engfailanal.2015.08.019 ↗
6. Melting and breaking characteristics of OPGW strands by lightning10.1109/tpwrd.2004.832410 ↗
7. Fault analysis on MOA used in an old 500 kV station10.16188/j.isa.1003-8337.2022.06.007 ↗
8. Arc-extinguishing effects of jet gas arc-extinguishing lightning protection gaps10.13334/j.0258-8013.pcsee.2015.03.031 ↗
9. Effective installation strategies of fault current interrupting arcing horns considering operational coordination with responses of line protection relays10.1002/eej.22851 ↗
10. Development and research on gas arc-extinguishing lightning protection methods10.3772/j.issn.1002-0470.2021.10.011 ↗
11. Development of gas arcarc-extinguishing lightning protection in overhead lines10.13336/j.1003-6520.hve.20200528023 ↗
12. DC arc suppression in the improved multichamber structure10.1063/1.5097633 ↗
13. Effective research on compression self-energy arc-extinguishing lightning protection device10.19335/j.cnki.2095-6649.2020.06.002 ↗
14. Influence of chamber structure on arc quenching in multigap system10.1049/hve.2019.0064 ↗
15. Arc-extinguishing research on semi-closed multi-compression tube structures10.3390/en16031057 ↗
16. Research on discharge characteristics of GLA with surface pollution/icing10.1016/j.egyr.2022.02.258 ↗
17. AC flashover voltage and arc development of long insulators strings in natural icing environment10.13335/j.1000-3673.pst.2020.1192 ↗
18. Study on the path and thermal characteristics of the spark discharge between ice and electrode gap10.1109/tdei.2023.3243617 ↗
19. Simulation and experimental study on electrode erosion characteristics of wire by DC arc10.13336/j.1003-6520.hve.20211003 ↗
20. MHD heat flux mitigation in hypersonic flow around a blunt body with ablating surface10.1088/1361-6463/aac566 ↗