journal article·2023-10-01Open access

Study on the flashover mechanism of bird droppings in the transmission line

Xiaopo Mao, Jianfeng Ye, Ze Tian, Kuan Hu, Jiaqiang Wang, Fali Tan

AIP Advances· Volume 13· Issue 10

Abstract

In recent years, bird droppings flashover faults frequently occur on transmission lines. Based on the existing conditions of the laboratory, this paper explores the flashover mechanism of 110 kV bird droppings. A new type of bird droppings propulsion device was designed and developed, and the process of bird droppings falling in the natural state was simulated without voltage. According to several typical forms of bird droppings, the main findings are ① the bird droppings connected to the two poles are the most serious short circuit situation; ② the bird droppings flashover fault of the 110 kV line is actually a single-phase grounding fault of the line through a resistance, and the grounding resistance is between 20 and 300 kΩ; and ③ the conductivity is the most sensitive factor affecting bird droppings flashover.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: High voltage insulation and dielectric phenomena · High-Voltage Power Transmission Systems · Lightning and Electromagnetic Phenomena

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

State Grid Hubei Electric Power Co., Ltd., Electric Power Research Institute 1 , Wuhan, Hubei 430077, China

Wuhan University 2 , Wuhan, Hubei 430072, China

References (6)

Show source-provided references
1. Preventive measures to reduce bird-related power outages—Part I: Electrocution and collision10.1109/tpwrd.2003.822947 ↗
2. Electric field calculation for HV insulators on the head of transmission tower by coupling CSM with BEM10.1109/tmag.2006.871373 ↗
3. Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towers10.1109/61.847268 ↗
4. Effects of liquids immersion and drying on the surface properties of HTV silicone rubber: Part I-contact angle and surface chemical properties10.1109/tdei.2017.006891 ↗
5. Surface flashover characteristics of PPLP according to its orientation in cryogenic environment10.1109/tasc.2018.2800033 ↗
6. Research progress of self-cleaning, anti-icing, and aging test technology of composite insulators10.3390/coatings12081224 ↗