Analysis of contact ablation of circuit breaker after short circuit current breaking
Source abstract
Abstract
During the opening and closing process of the contact, it will undergo repeated arc ablation and wear. After each ablation and wear, the composition, performance, and shape of the contact surface constantly change, leading to cracks, slag drop, melting, evaporation, and other phenomena on the contact surface, ultimately causing the contact to fail, resulting in the switch not being able to open and close normally. In order to study the failure mechanism of arc contacts caused by arc erosion after breaking short-circuit current, a pair of arc contacts for the cumulative breaking short circuit current test was selected as the research object. The metallographic, microscopic morphology, and energy spectrum analysis of the arc contacts were conducted, and the analysis results were compared with the new arc contacts to reveal the evolution and development process of arc contacts from cumulative arc erosion to failure during breaking.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Electrical Contact Performance and Analysis · Vacuum and Plasma Arcs · Tunneling and Rock Mechanics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Grid Hubei Electric Power Co., Ltd. Electric Power Research Institute 1 , Wuhan, Hubei 430077, China
Hubei Fangyuan Dongli Electric Power Science & Research Co., Ltd. 2 , Wuhan, Hubei 430077, China
References (6)
Show source-provided references
1. Summary of CIGRE 13.06 working group worldwide reliability data and maintenance cost data on high voltage circuit breakers above 63 kV
2. Diagnosis techniques on contact electrical endurance of high voltage circuit breakers
3. A new measurement method of the moving contact resistance of HV circuit breakers
4. Research on the interaction of primary plasma and main electrode for laser triggered vacuum switch10.1109/tps.2014.2362612 ↗
5. A complete strategy for conducting dynamic contact resistance measurements on HV circuit breakers10.1109/tpwrd.2008.917694 ↗
6. Research on the prebreakdown current of the laser-triggered vacuum switch10.1109/tps.2018.2792010 ↗