journal article·2021-03-01Open access

Numerical simulation and detection of dry-type air-core reactor temperature field based on laminar–turbulent model

Chuan Li, Han Wang, Chuan Luo, Dacheng Zhang, Xiaorong Wan, Zhengang Zhao, Yingna Li

AIP Advances· Volume 11· Issue 3

Abstract

The hot-spot temperature of a dry-type air-core reactor is a crucial factor that determines the service life of the reactor. Although the environment elevation has a significant influence on the reactor’s heat dissipation performance and hot-spot temperature, studies seldom focus on the temperature distribution for different altitude scenarios. To this end, this paper proposes a temperature field simulation model with multi-parameter coupling constraints based on the laminar–turbulent flow state. The calculation of the temperature field with the hot-spot temperature at different altitudes is finally achieved. The simulation results show that the hot-spot is located at 6.3% from the top of the sixth encapsulated-winding. It also shows that the hot-spot temperature of the reactor increases by 5 K–11 K with the altitude ascending by 1 km. Moreover, the hot-spot temperature of the reactor exceeds the temperature index at an altitude of 3.25 km, which will result in a shortened service life. Fiber Bragg grating temperature sensors are embedded in encapsulated-windings to detect the temperature for verifying the validity of the temperature field model, which could provide critical temperature rise evaluation rules for the operation safety of the dry-type air-core reactor.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Radiative Heat Transfer Studies · Fluid Dynamics and Turbulent Flows · Meteorological Phenomena and Simulations

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Faculty of Information Engineering and Automation, Kunming University of Science and Technology 1 , Kunming 650500, China

Yunnan Key Laboratory of Computer Technology Applications 2 , Kunming 650500, China

Funding

Foundation for Innovative Research Groups of the National Natural Science Foundation of China · Applied Basic Research Program of Yunnan

References (21)

Show source-provided references
1. Influence of the multi-component electrical feed of air-core industrial reactors on their sound radiation10.1051/aacus/2020015 ↗
2. Vibroacoustic models of air-core reactors10.20855/ijav.2016.21.4440 ↗
3. Breaking overvoltage of dry-type air-core shunt reactors and its cumulative effect on the interturn insulation10.1109/access.2019.2913763 ↗
4. Analysis and countermeasure of burnout of electromagnetic voltage transformer of high altitude area in western China10.1088/1757-899x/366/1/012063 ↗
5. Inter-turn short-circuit detection of dry-type air-core reactor based on spatial magnetic field distribution10.19595/j.cnki.1000-6753.tces.L80674 ↗
6. IEEE recommended practice for establishing liquid-immersed and dry-type power and distribution transformer capability when supplying nonsinusoidal load currents · 2018 · 1
7. IEEE draft standard requirements, terminology, and test code for dry-type aircore series-connected reactors · 2010 · 1
8. Thermal analysis of air-core power reactors10.1155/2013/865015 ↗
9. Research on temperature field simulation of dry type air core reactor
10. Thermal analysis of dry-type air-core coils for the optimization of passive filtering systems10.3390/en13174540 ↗
11. Thermal and electromagnetic combined optimization design of dry type air core reactor10.3390/en10121989 ↗
12. Research on electromagnetic and heat processes in dry type air core current-limiting reactors
13. Electromagnetic-fluid-temperature coupling calculation and analysis of dry-type air-core10.13336/j.1003-6520.hve.20170831033 ↗
14. Temperature field calculation and experimental analysis of dry-type air-core reactor10.19595/j.cnki.1000-6753.tces.2017.03.025 ↗
15. Theoretical and experimental evaluation of the temperature distribution in a dry type air core smoothing reactor of HVDC station10.3390/en10050623 ↗
16. Simulation and analysis of temperature field of high voltage reactor based on multi physical field coupling10.7667/PSPC180220 ↗
17. 2012 · 215
18. The dependence of local Nusselt number on Prandtl number in the case of free convection along a vertical surface with uniform heat flux10.1016/0017-9310(76)90020-x ↗
19. 2006 · 41
20. Calculation and analysis of fluid field and temperature field for high-altitude type doubly-fed wind generators10.13334/j.0258-8013.pcsee.2012.24.011 ↗
21. Insulation temperature increase in power transformers due to stationary disturbances: Comparison of methods