A novel method for measuring residual flux density of the single-phase transformer core based on phase difference
Source abstract
Abstract
A serious inrush current may occur when a power transformer is re-energized, which will cause many adverse effects on power equipment and the power grid. The corresponding potential hazards can be reduced if the existing residual flux density (Br) can be accurately measured. Combined with the field-circuit coupling analysis method, a novel method for measuring the Br based on the phase difference between the applied AC voltage and resulting transient current is proposed in this paper. When the same AC voltage is applied to the transformer winding, the Br affects the resulting transient current. The phase difference between the applied voltage and the resulting current can be calculated by the cross-correlation technique. Based on the finite element method (FEM), the empirical formula for the quantitative measurement of Br in the transformer core is determined. Finally, an experimental study is performed on the square core of single-phase transformers. The experimental results reveal that the proposed measurement method is with high accuracy.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Magnetic Properties and Applications · Non-Destructive Testing Techniques · Power Transformer Diagnostics and Insulation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Key Laboratory of Reliability and Intelligence of Electrical Equipment, Hebei University of Technology 1 , Tianjin 300130, China
Laboratory of Electromagnetic Field and Electrical Apparatus Reliability of Hebei Province, Hebei University of Technology 2 , Tianjin 300130, China
Funding
National Natural Science Foundation of China
References (12)
Show source-provided references
1. Remanent flux negative effects on transformer diagnostic test results and a novel approach for its elimination10.1109/tpwrd.2018.2827179 ↗
2. Three- and two-dimensional finite-element computation of inrush current and short-circuit electromagnetic forces on windings of a three-phase core-type power transformer10.1109/tmag.2008.917819 ↗
3. Elimination of residual flux in transformers by the application of an alternating polarity DC voltage source10.1109/TPWRD.2014.2377199 ↗
4. Three-phase transformer inrush current reduction strategy based on prefluxing and controlled switching10.1109/access.2021.3062143 ↗
5. Study on residual flux evaluation method based on variable-regional integral during the voltage attenuation process
6. Determining the residual magnetic flux value of a single-phase transformer using a minor hysteresis loop10.1109/tpwrd.2020.3019407 ↗
7. Residual flux measurement of power transformer based on transient current difference10.1109/tmag.2021.3082699 ↗
8. Research on residual flux prediction of the transformer10.1109/tmag.2017.2664886 ↗
9. Parameter identification of Preisach model based on velocity-controlled particle swarm optimization method10.1063/9.0000030 ↗
10. A novel strategy for reducing inrush current of three-phase transformer considering residual flux10.1109/tie.2016.2540583 ↗
11. State of charge and state of health estimation using electrochemical acoustic time of flight analysis10.1149/2.1411712jes ↗
12. Analysis and Reduction of Magnetizing Inrush Current for Switch-On Unloaded Transformer