Research on transportation vibration and short-circuit resistance of mobile transformer
Source abstract
Abstract
With the increase in power demand and the rising requirements for power supply reliability, the flexible advantages of on-board mobile substations have become prominent. However, the existing transformer transportation monitoring only records the maximum values of vibration and impact acceleration, has a low speed limit, and the research on short-circuit resistance is mostly static analysis, which is difficult to meet actual needs. This paper conducts research on the transportation vibration and short-circuit resistance of mobile transformers. The main content and results are as follows: A model is established using shell elements, and a simulation of land transportation intensity is conducted to calculate the displacement and equivalent stress of the transformer and the housing body, which all meet the structural strength requirements. The short-circuit resistance calculation is carried out according to the GB1094.5-2008 standard. The results show that both thermal stability and dynamic thermal stability are met. Furthermore, mobile transformation optimization measures were proposed. After optimization, in the 3G transportation condition, the X-direction displacement of the transformer was reduced, meeting the requirements. In summary, the transportation vibration monitoring and simulation method, short-circuit resistance calculation system, and structural optimization scheme constructed in this paper can ensure the safety of mobile transformer transportation and its short-circuit resistance capability, meeting engineering requirements.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Power Transformer Diagnostics and Insulation · Magnetic Properties and Applications · Thermal Analysis in Power Transmission
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Qinzhou Power Supply Bureau of Guangxi Power Grid Co., Ltd. , Qinzhou, Guangxi,
References (14)
Show source-provided references
1. Review and prospect of scheduling operation and control of large-scale pumped storage in new power system10.13334/j.0258-8013.pcsee.240723 ↗
2. Diagnosis and prediction analysis of mobile transformer monitoring system based on artificial intelligence10.19339/j.issn.1674-2583.2023.08.188 ↗
3. High power density mobile transformer factory tests
4. Transport vibration and shock characteristics of a 110 kV/40 MVA vehicular mobile transformer10.1002/tee.23602 ↗
5. On-line monitoring of transportation condition for 110 kV vehicular mobile transformers10.1109/CICED50259.2021.9556745 ↗
6. Transportation monitoring of geo-location, speed, vibration, and shock acceleration for 110-kV vehicular mobile transformers10.1109/tim.2020.3022443 ↗
7. Prediction of transformer winding performance under short circuit impulse
8. Short circuit electromagnetic force analysis of 500 kV autotransformer based on field-circuit coupling10.1007/978-981-99-7405-4_65 ↗
9. Development of a sudden short-circuit test device for power transformers10.19768/j.cnki.dgjs.2021.17.032 ↗
10. Research on verification method of short-circuit withstand capability of power transformer based on finite element10.12067/ATEEE2203025 ↗
11. 2024 · 1
12. 2023 · 5010.1145/3586185.3586197 ↗
13. Calculation of short-circuit electromagnetic force in a power transformer under the short-circuit condition
14. Radial stability evaluation and cumulative test of transformer windings under short-circuit condition10.1016/j.epsr.2023.109112 ↗