The global energy impact of raising the space temperature for high-temperature data centers
Source abstract
Abstract
Ever-increasing energy consumption of data centers is a growing global concern. To tackle this problem, a high-temperature data center is proposed as a fundamental solution. It adopts a different cooling mechanism and makes “chiller-free” data centers possible, facilitating the transition from chiller-based cooling to completely free cooling in data centers. Here, we report the global energy impacts of adopting high-temperature data centers and critically analyze the trade-off between cooling-energy savings and server power rise using worldwide weather data and server performance data. Quantitative guidance and targets are established for developing “ideal” and “recommendable” servers, considering the server performance associated with the thermal environment. When raising the space temperature to 41°C (namely, the “global free-cooling temperature”), nearly all the land area can achieve 100% free cooling year round globally. Operating at this space temperature, up to 56% cooling-energy savings could be achieved compared with operating at a current typical space temperature of 22°C.
Source: openalex_inverted_index · Quality: baseline
Research context
OpenAlex topics: Heat Transfer and Optimization · Building Energy and Comfort Optimization · Cloud Computing and Resource Management
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
References (44)
Show source-provided references
1. Mitigating Curtailment and Carbon Emissions through Load Migration between Data Centers10.1016/j.joule.2020.08.001 ↗
2. 2009
3. Recalibrating global data center energy-use estimates10.1126/science.aba3758 ↗
4. Sources of data center energy estimates: A comprehensive review10.1016/j.joule.2022.07.011 ↗
5. Data center power requirements: measurements from Silicon Valley10.1016/S0360-5442(03)00009-4 ↗
6. A decision support system for waste heat recovery and energy efficiency improvement in data centres10.1016/j.apenergy.2019.05.029 ↗
7. 2021
8. Seaton · 2017
9. Research and Technologies for next-generation high-temperature data centers – State-of-the-arts and future perspectives10.1016/j.rser.2022.112991 ↗
10. 2004
11. 2008
12. 2011
13. De-risking data center temperature increases, Part 1
14. De-risking data center temperature increases, Part 2
15. Fitch · 2012
16. Seaton · 2017
17. 2022 Best Practice Guidelines for the EU Code of Conduct on Data Centre Energy Efficiency. https://e3p.jrc.ec.europa.eu/publications/2022-best-practice-guidelines-eu-code-conduct-data-centre-energy-efficiency.
18. Cooling our insatiable demand for data10.1126/science.abe5318 ↗
19. Niemann · 2011 · 135 · 1
20. Multi-objective efficiency enhancement using workload spreading in an operational data center10.1016/j.apenergy.2014.10.083 ↗
21. A gray-box model for real-time transient temperature predictions in data centers10.1016/j.applthermaleng.2020.116319 ↗
22. Gözcü · 2017 · 968
23. Simplified server model to simulate data center cooling energy consumption10.1016/j.enbuild.2014.10.058 ↗
24. Statistical analysis for predicting location-specific data center PUE and its improvement potential10.1016/j.energy.2020.117556 ↗
25. ASHRAE (2021). Standard 169-2021, Climatic Data for Building Design Standards.
26. Optimizing design & control of chilled water plants: Part 4: Chiller & cooling tower selection
27. 2020
28. Huang · 2015 · 150
29. Sankar · 2011 · 530
30. Reducing Data Center Cost with an Air Economizer. https://www.intel.com/content/dam/doc/technology-brief/data-center-efficiency-xeon-reducing-data-center-cost-with-air-economizer-brief.pdf.
31. Effect of a micro heat sink geometric design on thermo-hydraulic performance: A review10.1016/j.applthermaleng.2020.114974 ↗
32. Two-phase spray cooling for high ambient temperature data centers: Evaluation of system performance10.1016/j.apenergy.2021.117816 ↗
33. Piezotronics and Piezo-phototronics of Third Generation Semiconductor Nanowires10.1021/acs.chemrev.8b00599 ↗
34. Niemann · 2011 · 160
35. Potts · 2011
36. Waterside and Airside Economizers Design Considerations for Data Center Facilities
37. Braun · 1988
38. How to design & control waterside economizers
39. TRNSYS 18, A transient systems simulation program, http://sel.me.wisc.edu/trnsys.
40. A supervisory control strategy for building cooling water systems for practical and real time applications10.1016/j.enconman.2008.01.019 ↗
41. Renewable energy system optimization of low/zero energy buildings using single-objective and multi-objective optimization methods10.1016/j.enbuild.2014.12.032 ↗
42. Optimal design of data center cooling systems concerning multi-chiller system configuration and component selection for energy-efficient operation and maximized free-cooling10.1016/j.renene.2019.05.127 ↗
43. Analysis of the effect of seasonal climate changes on cooling tower efficiency, and strategies for reducing cooling tower power consumption10.1016/j.applthermaleng.2019.114148 ↗
44. Evans · 2012 · 59