Experimental testing of an innovative steel chimney with expanded perlite insulation in the context of fire safety of buildings

Krzysztof Drozdzol

Abstract

This study examines the thermal performance of a prototype double-walled steel chimney system insulated with expanded perlite, proposed as an environmentally sustainable alternative to conventional mineral wool insulation. Expanded perlite is a chemically inert material that does not emit harmful substances, addressing the environmental and health concerns associated with mineral wool. This research aimed to evaluate whether perlite provides sufficient thermal insulation to meet the requirements for chimney systems under both normal operating and soot fire conditions. Two full-scale experimental tests were conducted: a normal operating condition test with a flue gas temperature of up to 700 °C and a soot-fire test, in which the temperature was increased to 1000 °C for 30 minutes. Under normal operating conditions, the wooden ceiling and roof components reached approximately 40 °C, comparable to values reported for mineral-wool-insulated chimneys operating at lower flue gas temperatures. During the soot-fire test, the maximum temperatures recorded on wooden elements were 64 °C (ceiling) and 52 °C (roof), demonstrating adequate thermal protection. The chimney casing temperature did not exceed 130 °C during operation and remained below 200 °C during the soot-fire test, despite internal flue gas temperatures exceeding 750 °C. These results confirm the high thermal resistance of expanded perlite insulation and its capacity to limit heat transfer to adjacent structures. Overall, the tested chimney system satisfies the requirements of PN-EN 1856-1 and PN-EN 1859, indicating its suitability for certification and potential commercial implementation. The findings support the use of expanded perlite as a viable and environmentally favourable replacement for mineral wool in chimney insulation applications. • Fire safety assessment confirmed the applicability of perlite-insulated chimneys in buildings • Expanded perlite can replace mineral wool insulation in chimneys • Perlite-insulated chimneys kept wood at 40 °C under 700 °C flue gas. • Wood stayed below 64 °C under 1000 °C flue gas.
Source: openalex_inverted_index · Quality: baseline

Research context

OpenAlex topics: Fire effects on concrete materials · Masonry and Concrete Structural Analysis · Wood Treatment and Properties

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (34)

Show source-provided references
1. An implementation framework to attain 6R-based sustainable lean implementation—a case study10.1109/ACCESS.2019.2936056 ↗
2. EN 1859:2009+A1:2013: Chimneys - Metal chimneys - Test methods, 2013.
3. EN 1856-1:2009: Requirements for metal chimneys - Part 1: System chimney products, (n.d.).
4. Assessment of the fire toxicity of building insulation materials10.1016/j.enbuild.2010.10.015 ↗
5. Toxicity characteristics and fire retardant performance of commercially manufactured organic insulation materials for building applications10.1016/j.conbuildmat.2022.127898 ↗
6. Smoke toxicity of rainscreen façades10.1016/j.jhazmat.2020.123694 ↗
7. Assessment of toxic gas emissions from flammable building thermal insulation materials upon fire conditions
8. Man-made mineral fibers (MMMF): Human exposures and health risk assessment10.1177/074823379000600203 ↗
9. Mineral wool waste in Austria, associated health aspects and recycling options10.31025/2611-4135/2020.13904 ↗
10. Occupational risk resulting from exposure to mineral wool when installing insulation in buildings10.13075/ijomeh.1896.01637 ↗
11. Mineral wool waste in Europe: a review of mineral wool waste quantity, quality, and current recycling methods
12. The role and place of traditional chimney system solutions in environmental progress and in reducing energy consumption10.3390/en14164720 ↗
13. K. Drozdzol, Development of Modern Chimney Systems Designed for Solid Fuel Devices, in: INCREaSE 2019, 2020. https://doi.org/10.1007/978-3-030-30938-1_39..10.1007/978-3-030-30938-1_39 ↗
14. An experimental study on the effect of design flue gas temperature on the fire safety of chimneys10.1007/s10694-014-0415-4 ↗
15. Comparison between European chimney test results and actual installations10.1177/0734904116680222 ↗
16. Effects of the coupling of insulating and conductive materials to limit the temperature at chimney-roof penetration10.1007/s10694-020-00947-5 ↗
17. Analysis of the temperatures measured in very thick and insulating roofs in the vicinity of a chimney10.1088/1742-6596/655/1/012019 ↗
18. Experimental and computational study of the temperatures field around a chimney roof penetration10.1007/s10694-015-0540-8 ↗
19. Heat transfer and safety risks in horizontal chimney installations through walls10.1007/s10694-025-01804-z ↗
20. Experimental fire testing of an innovative three-layer chimney for residential buildings
21. Thermal and mechanical studies of perlite concrete casing for chimneys in residential buildings10.3390/ma14082011 ↗
22. CFD thermal analysis of a three-layer chimney used in residential buildings
23. Securing the safety of flue systems in residential property construction
24. Fire safety study of a perlite concrete chimney and wooden ceilings used in buildings based on experimental tests and CFD analysis10.1177/01436244241231357 ↗
25. I.M. Džolev, Chimneys’ influence on fire risk of solid wood structures in residential buildings in rural balkan settlements10.2298/TSCI190525138L ↗
26. Marshal of the Sejm of the Republic of Poland. Announcement of 6 March 2025 on the publication of the consolidated text of the Act – Construction Law Act. Journal of Laws of the Republic of Poland, 2025, item [it. 418, 〈Https://Isap.Sejm.Gov.Pl/Isap.Nsf/DocDetails.Xsp?Id=WDU20250000418〉 (n.d.).
27. Federal Ministry for Economic Affairs and Energy (Germany). Ordinance on the Inspection and Sweeping of Chimneys (Kehr- und Überprüfungsordnung, KÜO). Federal Law Gazette (Bundesgesetzblatt), 2013, Part I, p. [BGBl. I S. 760], as amended, 〈Http://Www.Schornsteinfeger-Pala.de/AllgemeinDownload/K%C3%9CO-8april2013.Pdf〉 (n.d.).
28. UK Government. The Building Regulations 2010: Approved Document J – Combustion appliances and fuel storage systems. HM Government, London, 2010, as amended, 〈Https://Www.Gov.Uk/Government/Publications/Combustion-Appliances-and-Fuel-Storage-Systems-Approved-Document-j?Utm_source=chatgpt.Com〉 (n.d.).
29. Limiting the temperature at the chimney-roof penetration: Innovative roof passage with fins and case to meet the latest European standards and enhance heat recovery
30. Data on temperature-time curves measured at chimney-roof penetration10.1016/j.dib.2018.08.017 ↗
31. Device for limiting the temperature at chimney-roof penetration in very critical chimney operating conditions10.1007/s10694-019-00837-5 ↗
32. Experimental study on the smouldering combustion of mineral wool insulation in chimney penetrations10.1007/s10694-019-00849-1 ↗
33. A comprehensive study of perlite in building materials: balancing sustainability and performance10.1007/s10973-025-14410-6 ↗
34. Characterization of perlite and expanded perlite from West Sumatera, Indonesia10.1088/1755-1315/882/1/012010 ↗