Estimation the remaining service-lifetime of wooden structure of geothermal cooling tower

Effendi Tri Bahtiar, Naresworo Nugroho, Mohamad Miftah Rahman, Arinana, Rita Kartika Sari, Wilis Wirawan, Dede Hermawan

Abstract

Similar with other construction materials, wood strength is decreasing when applied by long term loading. Wooden cooling tower structure at Star Energy Geothermal (Wayang Windu) Ltd was built in 1998 and it should be evaluated to avoid sudden structural failure. Evaluation conducted through several steps: wood species identification, the physical and mechanical properties testing, and estimation for remaining service-lifetime by generating mathematical models derived from creep test and reduction of cross sectional area of the wood. Identification result that the wood are redwood (Sequoia sempervirens) and Douglas fir (Pseudotsuga menziesii). The wood density value has degraded from the surface until 0.25 cm depth. Strength characteristics of the wood have considerably decreased, but the allowable stress for bending, tension parallel to grain, and shear were still higher than NDS2005 requirements. The allowable stress for compression parallel to grain was slightly lower than NDS, while compression perpendicular to grain was much lower. Average modulus of elasticity reduces become lower than the value stated by the code, but the minimum value of modulus of elasticity (Emin) of redwood was still higher than the code value, while Emin of Douglas fir is slightly lower. Then, in accordance with those findings, the construction would not failure yet but the deformation and vibration will occur in higher rate than design planning. This research develops mathematical models for estimating the remaining service-lifetime of the wooden cooling tower structure in geothermal power plant based on the wood performance in resisting long term loading and its deterioration rate. The deterioration rate of wood member of cooling tower structure at Star Energy Geothermal (Wayang Windu) Ltd is 0.0147 cm depth per year, so equation for the residual service life estimation is σlaterσtoday=bh2(b−0.0147T)(h−0.0147T)2, and σlater must be lower than allowable stress.
Source: openalex_inverted_index · Quality: baseline

Research context

OpenAlex topics: Tree Root and Stability Studies

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

References (16)

Show source-provided references
1. Ozelton · 2006
2. Bending strength and stiffness of in-grade Douglas-fir and southern pine no. 2 2×4 lumber10.1139/x2012-041 ↗
3. Stanford · 2003
4. [AF&PA] American Forest and Paper Association · 2005
5. [ASTM] American Society for Testing and Materials · 2003
6. Schulze · 2006
7. Hoadley · 1990
8. Pendugaan sisa umur pakai kayu komponen cooling tower di pembangkit listrik tenaga panas bumi (PLTP) unit II kamojang10.5614/jts.2012.19.2.2 ↗
9. Wood deterioration of cooling tower structure at geothermal power plant10.3923/ajaps.2017.79.87 ↗
10. [ASTM] American Society for Testing and Materials · 2003
11. Daily cycle of air temperature and relative humidity effect to creep deflection of wood component of low-cost house in cibeureum –Bogor, west java, Indonesia10.3923/ajsr.2014.501.512 ↗
12. Human comfort period outside and inside bamboo stands10.3923/jest.2014.245.265 ↗
13. Load duration effects in wood members and connections: order statistics and critical loads10.1016/S0167-4730(02)00031-0 ↗
14. Erosion rate of wood during natural weathering part III. effect of exposure angle on erosion rate
15. Causes and control of wood decay
16. [FPL] Forest Products Laboratory · 2010