Experimental Studies on Mechanical Smoke Exhaust System in an Atrium
Source abstract
Abstract
Mechanical smoke exhaust systems are usually required in big atria of the Far East. However, the design criteria are not clearly demonstrated to be worked out through systematic full-scale tests. There are many arguments on sizing the exhaust fans, and whether a high exhaust rate is required in an atrium is a puzzle. Atrium hot smoke tests might be required to be carried out occasionally to evaluate their performance, especially when the design does not comply with the prescriptive code in having a high-enough exhaust rate. Experimental studies on mechanical smoke exhaust systems are necessary and have been carried out. The results are reported in this paper. The measured results are also compared with the empirical equations used in designs, following NFPA-92B derived by a two-layer picture. A simple zone model reported earlier is applied to justify the results. This model is also developed based on a two-layer picture. There are significant deviations of the measured results from those predicted by the equations with a two-layer pattern. Mass exchange through the two layers in an atrium fire is suggested to be the key point. By taking the estimated mass flow rate across the two layers by experiments to be 30% of the exhaust rate under high ventilation conditions, the two-layer zone model is modified. Slightly better argument with the experiments was found for the self-developed two-layer zone model, but still there are large deviations for the NFPA-92B equations.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research · Wind and Air Flow Studies · Evacuation and Crowd Dynamics
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei, Anhui, China
References (14)
Show source-provided references
1. Chow, W.K. · 2004
2. NFPA-92B · 2000
3. Klote, J.H. · 2002
4. Codes of Practice for Minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment (1998). Fire Services Department, Hong Kong , p. 120.
5. Hot Smoke Test on Smoke Extraction System. F.S.D. Circular Letters 2/2002, FS 107A (Rev.10/95). Fire Services Department, Hong Kong, 18 November, 2002.
6. AS 4391-1999 Smoke Management Systems - Hot Smoke Test. 1999. Australian StandardTM, Standards Australia (Standards Association of Australia), NSW , p. 25.
7. Atkinson, B. · 1
8. 10.3210/fst.5.3110.3210/fst.5.31 ↗
9. Walton, W.D. · 1993
10. 10.1016/S0360-1323(00)00032-910.1016/S0360-1323(00)00032-9 ↗
11. 10.1115/1.324519410.1115/1.3245194 ↗
12. Li, Y.Z. (2001). Smoke Flow and Control in Large Space Atrium Buildings, PhD Thesis. University of Science and Technology of China, Hefei, Anhui, China.
13. Chow, W.K. · 2004
14. 10.1016/j.buildenv.2004.08.01810.1016/j.buildenv.2004.08.018 ↗