Heat blockage of air gap for inner overheating of high-voltage power cable and delay of early detection
Source abstract
Abstract
Early detection for inner overheating of high-voltage cable is important for safe power supply. A new radial heat transfer model is developed for a typical 110 kV cable with an air gap layer. Numerical analyses are conducted for dynamic temperature field in cable induced by hot copper core with different thicknesses of air gap. The results show that the air gap has an important heat blockage for the outward heat transfer in cable. The air gap causes the temperature inside the overheated cable to rise faster and the temperature outside slower. The air gap not only reduces the response sensitivity of the surface temperature on inner overheating but also induces the inner layers to heat up and even break down. Finally, the non-dimensional temperatures on cable surface indicate that the detection of inner overheating cable would be delayed if the air gap is not considered in calculation models.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Thermal Analysis in Power Transmission · High voltage insulation and dielectric phenomena · Lightning and Electromagnetic Phenomena
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
State Key Lab of Fire Science, University of Science and Technology of China, Hefei, China
Shanghai Fire Research Institute of MEM, Shanghai, China
Funding
fundamental research funds for the central universities · key technologies research and development program
References (24)
Show source-provided references
1. 10.1016/j.jhazmat.2016.09.04210.1016/j.jhazmat.2016.09.042 ↗
2. 10.1016/j.tust.2015.11.01210.1016/j.tust.2015.11.012 ↗
3. Power loss in several areas by the 66 kV cable fire in Dalian. Dalian News, 19 August 2016, https://ln.qq.com/a/20160819/005426.htm
4. Poitras C. Underground fire attributed to overheating of cable, 1 June 1994, https://www.courant.com/news/connecticut/hc-xpm-1994-06-01-9406010445-story.html
5. Holborn electrical fire causes mass evacuation. BBC News, 1 April 2015, https://www.bbc.com/news/uk-england-london-32150554
6. Officials: explosion by city hall result of underground fire. AP News, 7 November 2018, https://apnews.com/d4bc980f618640898c10b2519b83a591
7. Jaros J · Proc SPIE · 2015 · 9450 · 137
8. GB/T22078.2-2008. Power cables with cross-linked polyethylene insulation and their accessories for rated voltage of 500 kV—part 2: power cables with cross-linked polyethylene insulation for rated voltage of 500 kW.
9. 10.1109/59.78091610.1109/59.780916 ↗
10. 10.1109/57.90161310.1109/57.901613 ↗
11. 10.1109/TDEI.2018.00754510.1109/TDEI.2018.007545 ↗
12. 10.1016/j.sna.2005.06.02410.1016/j.sna.2005.06.024 ↗
13. 10.1016/j.firesaf.2015.02.00210.1016/j.firesaf.2015.02.002 ↗
14. 10.1002/fam.266910.1002/fam.2669 ↗
15. 10.1007/s10973-019-08526-910.1007/s10973-019-08526-9 ↗
16. 10.1016/j.firesaf.2017.10.00510.1016/j.firesaf.2017.10.005 ↗
17. 10.1007/s10694-019-00918-510.1007/s10694-019-00918-5 ↗
18. Simmons DM · Elect J · 1932 · 29 · 395
19. Neher JH · AIEE Trans · 1957 · 76 · 752
20. 10.1109/TIA.2003.81064810.1109/TIA.2003.810648 ↗
21. Zhao JH · Proc CSEE · 1999 · 11 · 53
22. 10.1109/TIA.1983.450422010.1109/TIA.1983.4504220 ↗
23. 10.1016/j.applthermaleng.2016.05.00810.1016/j.applthermaleng.2016.05.008 ↗
24. Incropera FP · 2006