Experimental study on combustion characteristics of fire in data room
Source abstract
Abstract
Through the combustion experiments on the cables and servers in a data room, the combustion characteristic parameters of the materials were obtained, and the materials were analyzed and evaluated from the aspects of heat release rate, gas concentration, flue gas temperature, and so on. The results show that network cable and electric cable can be ignited during the cable combustion test. In the overall fire combustion experiment of single server and the server group with three cabinets, the fire process is divided into three stages: initial growth stage, stable combustion stage, and combustion attenuation stage. The heat release rate, flue gas temperature, and CO 2 concentration of the overall experiment have three peaks, respectively, 58, 98, and 134 kW; 100°C, 152°C, and 232°C; 1314, 2514, and 2988 ppm. The research results can provide some reference for design of fire protection system in data rooms.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Fire dynamics and safety research · Evacuation and Crowd Dynamics · Fire Detection and Safety Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
China University of Mining and Technology, Beijing, China
Funding
fundamental research funds for the central universities
References (18)
Show source-provided references
1. Du JF. · 2021
2. IDC and Corporate USA. Data age 2025. IDC white paper, 2018. https://www.i-scoop.eu/big-data-action-value-context/data-age-2025-datasphere/
3. Ma XY. · 2019
4. Xu X. · 2020
5. 10.1007/s10694-019-00918-510.1007/s10694-019-00918-5 ↗
6. Griger K. · Cabl Instal Maint · 2014 · 40 · 27
7. 10.1016/j.firesaf.2021.10331910.1016/j.firesaf.2021.103319 ↗
8. 10.1016/j.firesaf.2020.10309410.1016/j.firesaf.2020.103094 ↗
9. 10.1023/B:FIRE.0000003314.77005.2110.1023/B:FIRE.0000003314.77005.21 ↗
10. 10.1016/j.firesaf.2018.05.00110.1016/j.firesaf.2018.05.001 ↗
11. 10.1007/s10973-019-09039-110.1007/s10973-019-09039-1 ↗
12. Kim MO · Fire Safety J · 2020 · 115 · 103
13. 10.1016/j.jhazmat.2010.03.01510.1016/j.jhazmat.2010.03.015 ↗
14. 10.1016/j.fusengdes.2013.01.02610.1016/j.fusengdes.2013.01.026 ↗
15. 10.1007/s10694-019-00833-910.1007/s10694-019-00833-9 ↗
16. 10.1007/s10973-018-7556-510.1007/s10973-018-7556-5 ↗
17. 10.1007/s10694-018-0788-x10.1007/s10694-018-0788-x ↗
18. Shi L · 2009