Ventilation Effectiveness Measurements in Clean and Dry Rooms Based on Tracer Gas Techniques—A Preliminary Measurement Development
Source abstract
Abstract
Battery cell manufacturing is highly energy intensive, with clean and dry rooms being among the largest consumers of electricity and thermal energy. Due to the moisture sensitivity of most advanced cathode materials (e.g., NMC 811) and sulfide-based solid-state materials, production environments must operate at extremely low humidity, requiring energy-intensive HVAC systems to remove moisture introduced mainly by workers and infiltration. To reduce energy consumption, a detailed understanding of the airflow patterns in the room is essential. Because of complex flow patterns (exhaust air demands, energy dissipation), tracer gas techniques using CO2 as a marker provide an operation-integrated method for determining local air age. The studies presented in this paper apply tracer gas techniques for the first time to a room in which air is almost completely recirculated at high air change rates of approximately 27 h−1, with the supply air being conditioned by removing all process-relevant contaminants such as moisture and particles. Measurements in a separate flow box show successful air age calculations that agree with simplified CFD simulations. For the clean and dry room, the empirical variable relative exposure (REX) was introduced. The measurements indicate an inhomogeneous air distribution inside the room, accompanied with short-circuit flows, partial displacement flow, and mixing, and therefore have the potential to provide a cost-effective first-hand insight into the prevailing airflow patterns. Nevertheless, the presented measurement technique must be further optimized and validated for rooms with air recirculation and high air change rates.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Hygrothermal properties of building materials · Infection Control and Ventilation · Adsorption and Cooling Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Fraunhofer Institute for Solar Energy Systems (ISE), 79110 Freiburg, Germany
References (24)
Show source-provided references
1. The Influence of Calendering on the Moisture Sorption Behavior of Electrodes for Lithium-Ion Batteries10.1149/MA2022-012284mtgabs ↗
2. Investigation of Moisture Content, Structural and Electrochemical Properties of Nickel-Rich NCM Based Cathodes Processed at Ambient Atmosphere10.1149/1945-7111/ac7358 ↗
3. The effects of ambient storage conditions on the structural and electrochemical properties of NMC-811 cathodes for Li-ion batteries10.1016/j.electacta.2020.137358 ↗
4. Diagnosis tools for humidity-born surface contaminants on Li[Ni0.8Mn0.1Co0.1]O2 cathode materials for lithium batteries10.1016/j.jpowsour.2022.231111 ↗
5. Lorenz, P., Marius, H., Benedict, I., Hasibe, T., Matthias, B., Sarah, W., Achim, K., and Marc, K. (2023). Mini-Environments in Lithium-Ion Battery Cell Production A Survey on Current State Challenges and Trends. Proceedings of the Conference on Production Systems and Logistics: CPSL 2023—2, Publish-Ing.
6. Michaelis, S., Schütrumpf, J., Zienow, J., and Persichetti, A. (2023). Roadmap Battery Production Equipment 2030: Update 2023, VDMA Battery Production.
7. Kreher, T., Jäger, P., Heim, F., and Birke, K. (2023). Investigating the Production Atmosphere for Sulfide-Based Electrolyte Layers Regarding Occupational Health and Safety. Batteries, 9.10.3390/batteries9090472 ↗
8. Energy consumption of current and future production of lithium-ion and post lithium-ion battery cells10.1038/s41560-023-01355-z ↗
9. (2015). Cleanrooms and Associated Controlled Environments—Part 1: Classification of Air Cleanliness by Particle Concentration (Standard No. ISO 14644-1:2015).
10. Jinasena, A., Burheim, O.S., and Strømman, A.H. (2021). A Flexible Model for Benchmarking the Energy Usage of Automotive Lithium-Ion Battery Cell Manufacturing. Batteries, 7.10.3390/batteries7010014 ↗
11. Simulation-based assessment of the energy demand in battery cell manufacturing10.1016/j.procir.2019.01.097 ↗
12. Heller, M., Hasibe, T., Niels, H., and Matthias, M. (2023). Energieeffiziente und Qualitätsorientierte Anlagenkonzepte für die Batteriezellfertigung, Fraunhofer-Gesellschaft.
13. (2015). Berechnung der Thermischen Lasten und Raumtemperaturen (Auslegung Kühllast und Jahressimulation) (Standard No. VDI 2078).
14. Han, H. (2012). Ventilation Effectiveness Measurements Using Tracer Gas Technique. Fluid Dynamics Computational Modeling and Applications, IntechOpen.10.5772/26294 ↗
15. Auerswald, S. (2023). Dezentrale Fassaden-Integrierte Wohnungslüftungsgeräte: Kombinierte Bewertung des Erzielten Luftaustausches und der Energieeffizienz. [Ph.D. Dissertation, Albert-Ludwigs-Universität Freiburg].
16. What is ventilation efficiency?10.1016/0360-1323(81)90028-7 ↗
17. The Ventilation of Operating-Theatres
18. Tracer-gas techniques for measuring ventilation in a single zone10.1016/0360-1323(90)90010-O ↗
19. The use of moments for assessing air quality in ventilated rooms10.1016/0360-1323(83)90026-4 ↗
20. Measured influence of overhead HVAC on exposure to airborne contaminants from simulated speaking in a meeting and a classroom10.1111/ina.12917 ↗
21. Computational fluid dynamics (CFD) modelling of local mean age of air distribution in forced-ventilation food plants10.1016/j.jfoodeng.2008.06.014 ↗
22. Computational fluid dynamics modeling of contaminant transport with adsorption filtration inside planar-shaped air-purifying respirator canister10.1016/j.cherd.2023.06.020 ↗
23. Two-equation eddy-viscosity turbulence models for engineering applications10.2514/3.12149 ↗
24. Demonstration of a novel tracer gas method to investigate indoor air mixing and movement10.1016/j.indenv.2025.100081 ↗