Impact Characteristic Analysis of Tower Foundation Under Concealed Conductive Paths with Grounding Grid Based on a Scaled Model
Source abstract
Abstract
Concealed conductive connections between a transmission tower’s grounding grid and its foundation can cause a portion of the lightning strike current to enter the foundation and concentrate at the concealed conduction locations, thereby increasing the risk of foundation deterioration. To investigate the impact characteristics of such currents on the foundation under this operating condition, this study first establishes an electro-thermal-mechanical coupled finite-element model of the tower foundation that incorporates a subsurface concealed conductive loop, and compares the foundation’s temperature rise and mechanical characteristics under lightning currents and under power-frequency follow currents. The results indicate that power-frequency follow current poses a substantially greater hazard to the foundation than lightning current. Based on similarity theory, scaling laws for the foundation subjected to the impacts of power-frequency follow current are then derived. Considering that the intrinsic electro-thermal properties of the foundation cannot be altered in the scaled model, a parameter correction method is proposed according to quasi-similarity criteria. The corrected scaled-model results are compared with those of the prototype in simulation, and principal indicators exhibit deviations within 3%. A physical scaled model was subsequently designed and fabricated for impact testing, and ultrasonic inspection was used to assess potential damage in the concealed conduction region. The results show that under the action of power-frequency follow currents, the maximum temperature at the concealed conductive region reaches 124 °C, with deviations of 2.83% from the prototype simulation and 3.58% from the scaled-model simulation. The tower foundation was subjected to 20 power-frequency follow current impacts. After each impact and subsequent cooling, ultrasonic measurements of wave propagation velocity at the concealed conduction center decreased from 3.797 km/s to 3.571 km/s. The observed reduction in wave speed indicates a loss of local concrete structural integrity and suggests the risk of performance degradation and initiation of microcracks. These findings provide a reference basis for assessing the safety of tower foundations under concealed conduction conditions.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Lightning and Electromagnetic Phenomena · Structural Response to Dynamic Loads · Earthquake Detection and Analysis
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
College of Electrical Engineering and New Energy, China Three Gorges University, Yichang 443002, China
Hubei Provincial Engineering Technology Research Center for Power Transmission Line, China Three Gorges University, Yichang 443002, China
Funding
National Natural Science Foundation of China
References (30)
Show source-provided references
1. State of art and prospect of grounding technology in power system
2. Fu, Z., Wang, X., Wang, Q., Xu, X., Fu, N., and Qin, S. (2019). Advances and Challenges of Corrosion and Topology Detection of Grounding Grid. Appl. Sci., 9.10.3390/app9112290 ↗
3. The analysis, modeling, and capabilities of grounding system designs10.1109/TIA.2022.3186290 ↗
4. Source and transmission line maintenance outage scheduling in a power system using teaching learning based optimization algorithm10.1016/j.asoc.2014.03.015 ↗
5. Fan, R., Zeng, W., Ming, Z., Zhang, W., Huang, R., and Liu, J. (2023). Risk Reliability Assessment of Transmission Lines under Multiple Natural Disasters in Modern Power Systems. Energies, 16.10.3390/en16186548 ↗
6. Grounding resistance measurement analysis of grounding system in vertical-layered soil10.1109/TPWRD.2004.835283 ↗
7. Liu, W., Hu, Y., Tian, H., Jiang, Z., Su, X., Xiong, J., Su, W., and Wang, Y. (2023). Research on Lightning Overvoltage Protection of Line-Adjacent Pipelines Based on Solid-State Decoupling. Appl. Sci., 13.10.3390/app132212529 ↗
8. Analysis of damage characteristics of steel fiber-reinforced concrete based on acoustic emission10.1016/j.engfailanal.2023.107166 ↗
9. Investigation on the lateral impact responses of circular concrete-filled double-tube (CFDT) members10.1016/j.compstruct.2020.112993 ↗
10. Effect of loading rate on damage of concrete10.1016/j.cemconres.2004.03.022 ↗
11. Uniaxial behavior of UHPC under cyclic compression: Experimental investigation and constitutive model10.1016/j.conbuildmat.2024.136132 ↗
12. Liu, J., Huimin, H., Renbo, Z., and Xiuli, D. (2020). Meso-scale simulations on dynamic splitting tensile behaviors of concrete at elevated temperatures. Explos. Shock. Waves, 40.
13. Cui, D., Wang, L., Zhang, C., Xue, H., Gao, D., and Chen, F. (2024). Dynamic Splitting Performance and Energy Dissipation of Fiber-Reinforced Concrete under Impact Loading. Materials, 17.10.3390/ma17020421 ↗
14. Nie, P., Liu, H., Wang, Y., and Han, S. (2024). Seismic Response and Collapse Analysis of a Transmission Tower Structure: Assessing the Impact of the Damage Accumulation Effect. Buildings, 14.10.3390/buildings14072243 ↗
15. Gidrão, G.D.M.S., Krahl, P.A., Bosse, R.M., Silvestro, L., Ribeiro, R.S., Lima, G.T.D.S., and Carrazedo, R. (2024). Internal Damping Ratio of Normal- and High-Strength Concrete Considering Mechanical Damage Evolution. Buildings, 14.10.20944/preprints202407.0773.v1 ↗
16. Krentowski, J.R. (2022). Assessment of Destructive Impact of Different Factors on Concrete Structures Durability. Materials, 15.10.3390/ma15010225 ↗
17. Prognosis of fatigue and impact induced damage in concrete using embedded piezo-transducers10.1016/j.sna.2018.03.005 ↗
18. Wang, Y., Li, H., Jiang, C., Zhang, J., Li, T., Zhang, H., and Wang, Q. (2023, January 26–28). Research on Concrete Installation Grounding Scattering Characteristics and External Application Resistance Reduction Strategy. Proceedings of the International Symposium on Insulation and Discharge Computation for Power Equipment, Wuhan, China.10.1007/978-981-99-7401-6_67 ↗
19. Thermal effect analysis of tower conductive concrete foundation under ontinuous lightning strike
20. Analysis of electrothermal characteristics of conductive concrete foundation of power tower10.1088/1755-1315/571/1/012057 ↗
21. Mao, H., Tian, H., Hu, Y., Gao, T., Chen, Y., and Mu, M. (2023, January 26–28). Study on Temperature Rise Characteristics of Tower Grounding Electrode Under Lightning Strike and Power Frequency Short-Circuit Conditions. Proceedings of the International Symposium on Insulation and Discharge Computation for Power Equipment, Wuhan, China.10.1007/978-981-99-7401-6_64 ↗
22. Impulse grounding resistance analysis of typical tower grounding device under continuous lightning impulse
23. Wang, H., Zhang, L., Sun, Y., Zhang, Z., and Wang, D. (2022, January 9–12). Modeling and Modification of Converter Transformer Similarity Model Based on Finite Element And Similarity Theory. Proceedings of the 2022 4th International Conference on Smart Power & Internet Energy Systems (SPIES), Beijing, China.10.1109/SPIES55999.2022.10082243 ↗
24. Lightning surge characteristics on inclined incoming line to substation based on reduced-scale model experiment10.1109/TDEI.2013.6518943 ↗
25. Numerical simulation and mechanism analysis of GPR-based reinforcement corrosion detection10.1016/j.conbuildmat.2021.125913 ↗
26. Bu, J., Guo, Z., Zhang, J., and Zhang, Y. (2023). Experimental Study on the Damage Mechanism of Reinforced Concrete Beams Based on Acoustic Emission Technique. Appl. Sci., 13.10.3390/app13169207 ↗
27. Experimental study on the detection of internal damage of concrete by impact-echo method
28. Assessment of uncertainty in damage evaluation by ultrasonic testing of composite structures10.1016/j.compstruct.2018.06.109 ↗
29. Concu, G., and Trulli, N. (2018). Concrete Defects Sizing by Means of Ultrasonic Velocity Maps. Buildings, 8.10.3390/buildings8120176 ↗
30. Camara, L.A., Wons, M., Esteves, I.C.A., and Medeiros-Junior, R.A. (2019). Monitoring the Self-healing of Concrete from the Ultrasonic Pulse Velocity. J. Compos. Sci., 3.10.3390/jcs3010016 ↗