Development of Mixing Temperature Prediction Model for Single-Duct Variable Air Volume System Using CFD
Source abstract
Abstract
The purpose of this study was to determine the annual energy consumption that can be attributed to heating, ventilation, and air conditioning (HVAC) systems’ mixing temperature error. To develop a mixing temperature prediction model for a single-duct variable air volume (VAV) system, the mixing temperature was measured using 15 temperature sensors installed in an HVAC mixing chamber as well as the existing air handling unit’s (AHU) mixing temperature sensor. The mixing chamber was modeled using computational fluid dynamics (CFD), and a coefficient of variation of the root-mean-square error of 7.927% indicated that the model was reliable. Next, CFD simulation cases were formulated, and the temperature distribution of the mixing chamber was analyzed. This revealed that the amount of outdoor airflow input and the change in the temperature distribution of the mixing chamber were directly proportional to each other and that the mixing temperature measurements for the mixing chamber were not accurate. The mixing temperature prediction model was developed through multiple regression analysis and was successfully applied and verified. Compared with the measurements provided by existing mixing temperature sensors, the mixing temperature prediction model indicated an absolute error of 0.008–0.42 °C, confirming the model’s prediction performance.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Building Energy and Comfort Optimization · Refrigeration and Air Conditioning Technologies · Infection Control and Ventilation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Architectural Engineering, Graduate School of Yeungnam University, Gyeongsan 38541, Republic of Korea
R&D Center, BETECH, Daegu 41228, Republic of Korea
Architecture Research Institute, Yeungnam University, Gyeongsan 38541, Republic of Korea
School of Architecture, Yeungnam University, Gyeongsan 38541, Republic of Korea
Funding
2022 Yeungnam University Research · National Research Foundation of Korea (NRF)
References (14)
Show source-provided references
1. Lee, J.H., Kim, Y.S., Jo, J.H., Cho, H., and Cho, Y.H. (2018). Development of Economizer Control Method with Variable Mixed Air Temperature. Energies, 11.10.3390/en11092445 ↗
2. Lee, J.H. (2022). Optimal Free-Cooling Control of VAV System by Data-Driven Prediction of Mixed Air Temperature. [Ph.D. Thesis, Yeungnam University].
3. Development of Passive Air Mixing Chamber for the Improvement of Air Mixing Ratio
4. Predicting Supply Air Temperature in Air Handling Unit Using Machine Learning-Based Automation Algorithm
5. A Smart Mixed-Air Temperature Sensor10.1080/10789669.2009.10390827 ↗
6. Comparative Analysis of Cooling Energy Consumption according to Mixing Temperature Sensor Error in Economizer Control10.21086/ksles.2019.10.26.5.660 ↗
7. Development of Control Algorithm for Economizer System using Load Prediction Model10.7836/kses.2023.43.3.001 ↗
8. Ansys (2024, July 07). Fluent Theory Guide, Release 2024 R2. Available online: https://ansyshelp.ansys.com/public/account/secured?returnurl=////Views/Secured/corp/v242/en/flu_th/flu_th_sec_hxfer_theory.html.
9. Ashrae (2014). Ashrae’s Guideline 14, Measurement of Energy, Demand and Water Savings, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
10. Park, J.K. (2017). A Study on the Ventilation Efficiency Evaluation of the Combined Air-Diffuser Ventilation System Using CFD. [Master’s Thesis, Yeungnam University].10.3130/jaabe.16.647 ↗
11. Ansys (2024, May 26). Engineering Simulation Software. Available online: https://www.ansys.com.
12. Ansys (2024). Ansys Fluent Manual, Ansys Inc.
13. Kim, D.J. (2019). A Study on the Characteristics of Wind Pressure on Roof Form of Large Space Architecture Using Computational Fluid Dynamics. [Master’s Thesis, Yeungnam University].
14. Estimation of Wind Pressure on Apartment Buildings in a Group using a CFD Analysis