Efficient Zero-Sequence Impedance Measurement in Autotransformers Using Low-Voltage Excitation
Source abstract
Abstract
In accordance with the IEEE standard, the zero-sequence impedance test of transformers necessitates an open or short circuit test on the high-voltage side winding. Power source excitation is applied to the high-voltage test winding using a high-capacity test power supply. To circumvent the need for a large-capacity, high-voltage test power supply in field tests, this paper proposes a method for measuring zero-sequence impedance in autotransformers based on low-voltage excitation and disconnection testing. By applying a three-phase power supply to the lowest voltage side of the autotransformer and creating a disconnection condition, an unbalanced test scenario is established. Subsequently, the composite sequence network equivalent circuit for one-phase and two-phase disconnections between the high-voltage side and the low-voltage side of the transformer is formulated. Calculation formulas for the zero-sequence impedance of the autotransformer under various conditions are derived. The accuracy of the zero-sequence impedance is verified using MATLAB/Simulink simulation software 2018b, evaluating double-winding and three-winding autotransformers in breaking tests under different connection modes. The error is found to be less than 3%. The results of this study affirm the high accuracy of the proposed method.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Power Quality and Harmonics · Power Systems Fault Detection · Power Transformer Diagnostics and Insulation
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Guangdong Power Grid Co., Ltd., Guangzhou Power Supply Bureau, No. 2, Tianhe South 2nd Road, Tianhe District, Guangzhou 510620, China
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Shapingba District, Chongqing 400044, China
Funding
science and technology project of Guangdong power grid Co., Ltd.
References (18)
Show source-provided references
1. Wang, J., and He, B. (2021). Novel Step-Up Topologies of Zigzag Autotransformer. Electronics, 10.10.3390/electronics10243071 ↗
2. Impact of autotransformer inrush currents on differential protection operation10.1016/j.epsr.2023.109309 ↗
3. Estimating zero-sequence impedance of three-terminal transmission line and Theveninimpedance using relay measurement data
4. Reasearch on transformer fault diagnosis based on a beetle antennae search optimized support vector machine
5. A fault data based method for zero-sequence impedance estimation of mutually coupled transmission lines10.1109/TPWRD.2020.3026672 ↗
6. He, Q., He, G., Li, Z., Lin, M., Zhang, G., and Li, X. (2022). Pilot protection based on zero-sequence current resistance-capacitance component for large-scale inverter-interfaced power stations. Sustainability, 14.10.3390/su142013268 ↗
7. Setting zero-sequence compensation factor in distance relays protecting distribution systems10.1109/TPWRD.2017.2762465 ↗
8. Multi-level transient modeling of the aeronautic asymmetric 18-pulse phase-shifting auto-transformer rectifier in full-cycle design10.1109/TTE.2022.3169981 ↗
9. (2010). IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers (Standard No. IEEE Std C57.12.90).
10. A single-phase-to-ground fault detection method based on the ratio fluctuation coefficient of the zero-sequence current and Voltage differential in a distribution network10.1109/ACCESS.2023.3238072 ↗
11. Positive- and zero-sequence impedance estimation of YNyn0+d-connected main power transformers in wind power applications
12. Fault current levels in 220 and 500 kV autotransformer circuits
13. Kamel, M., Saeed, H., Karrar, A., and Eltom, A.H. (2016, January 17–21). On-site low voltage determination of zero-sequence impedances for station auxiliary transformers. Proceedings of the 2016 IEEE Power and Energy Society General Meeting (PESGM), Boston, MA, USA.10.1109/PESGM.2016.7741771 ↗
14. Determination of Parameters of Zero-Sequence Equivalent Circuits for Three-Phase Three-Legged YNynd Transformers Based on Onsite Low-Voltage Tests10.1109/TPWRD.2013.2259184 ↗
15. Calculation of zero phase sequence impedance for power transformers using numerical methods10.1109/20.376446 ↗
16. Parameter Estimation of Three-Phase Transformer Models for Low-Frequency Transient Studies from Terminal Measurements10.1109/TMAG.2016.2563389 ↗
17. On-Site Low Voltage Determination of Zero-Sequence Impedances for Power Transformers10.1109/TPWRD.2020.2977905 ↗
18. Chapman, S.J. (2004). Electric Machinery Fundamentals, McGraw-Hill.