Effect of Shunt Resistor Value on the Performance of Resistive Superconducting Fault Current Limiters

Hamoud Alafnan, Diaa-Eldin A. Mansour, Xiaoze Pei, Moanis Khedr, Mansoor Alturki, Abdullah Albaker, Ibrahim Alsaleh, Xianwu Zeng

Applied Sciences· Volume 13· Issue 20

Abstract

Resistive-type superconducting fault current limiters (r-SFCLs) have generated great interest for research and technical applications. This is attributed to their superior features, which include self-action, fast response, and simple operation. In low line impedance systems, r-SFCLs are seen as a viable protective mechanism for limiting high-magnitude fault currents. However, overcurrent caused by faults results in an increased temperature of the r-SFCL, possibly damaging the coils. Thus, the r-SFCL must be appropriately engineered to protect it while still allowing for effective fault current limitation. To achieve this goal, an appropriately sized shunt resistor must be used. Adding a shunt resistor benefits the r-SFCL in several ways, from lowering its maximum temperature to speeding up its recovery. Additionally, the shunt resistor protects the r-SFCL from excessive surges in temperature by giving the current an alternative path to flow down, thus saving it from further damage. A multilayer thermoelectric model was developed to examine the thermoelectrical behavior of the r-SFCL coil throughout a fault occurrence and the subsequent recovery period using three shunt resistors ranging from 4 to 16 Ω. MATLAB®/Simulink was used as the simulation platform in this study. The dependence of the current limitation capability and the voltage profile on the shunt resistor value was studied compared to the basic case without an r-SFCL. Increasing the shunt resistor value led to an enhanced ability to limit fault currents, although at the cost of higher temperatures and a longer recovery time. This study also presents guidance for optimizing the design parameters of r-SFCLs.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: HVDC Systems and Fault Protection · Cardiac Structural Anomalies and Repair · Electrical Fault Detection and Protection

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Electrical Engineering, College of Engineering, University of Ha’il, Ha’il 55476, Saudi Arabia

Department of Electrical Power Engineering, Faculty of Engineering, Egypt-Japan University of Science and Technology (E-JUST), Alexandria 21934, Egypt

Department of Electrical Power and Machines Engineering, Faculty of Engineering, Tanta University, Tanta 31511, Egypt

Department of Electronic and Electrical Engineering, University of Bath, Bath BA2 7AY, UK

Department of Mechanical Engineering, University of Bath, Bath BA2 7AY, UK

Funding

Scientific Research Deanship at the University of Ha’il, Saudi Arabia

References (36)

Show source-provided references
1. Impact of distributed generation on protection and voltage regulation of distribution systems: A review10.1016/j.rser.2019.01.050 ↗
2. Analysis of R-SFCL with Shunt Resistor in MMC-HVDC System Using Novel R-Q Method10.1109/TASC.2020.2975748 ↗
3. Superconducting fault current limiter (SFCL): Experiment and the simulation from finite-element method (FEM) to power/energy system software10.1016/j.energy.2021.121251 ↗
4. The discovery of superconductivity10.1063/1.3490499 ↗
5. Lightweight Design of Tens-MW Fully-Superconducting Wind Turbine Generators with High-Performance REBa2Cu3Oy Wires10.1109/TASC.2020.2979157 ↗
6. Transient Test and AC Loss Study of a Cryogenic Propulsion Unit for All Electric Aircraft10.1109/ACCESS.2021.3073071 ↗
7. Commissioning of the World’s First Full-Scale MW-Class Superconducting Generator on a Direct Drive Wind Turbine10.1109/TEC.2020.2982897 ↗
8. Challenges for developing high temperature superconducting ring magnets for rotating electric machine applications in future electric aircrafts10.1016/j.jmmm.2020.167543 ↗
9. Superconducting Synchronous Motors for Electric Ship Propulsion10.1109/TASC.2020.2980844 ↗
10. High temperature superconducting cables and their performance against short circuit faults: Current development, challenges, solutions, and future trends10.1088/1361-6668/ac7ae2 ↗
11. Energy-saving superconducting magnetic energy storage (SMES) based interline DC dynamic voltage restorer
12. New Technique for Using SMES to Limit Fault Currents in Wind Farm Power Systems10.1109/TASC.2018.2810512 ↗
13. Mishra, D.K., Złotecka, D., and Li, L. (2022). Significance of SMES Devices for Power System Frequency Regulation Scheme considering Distributed Energy Resources in a Deregulated Environment. Energies, 15.10.3390/en15051766 ↗
14. Analysis of Impacts of Superconducting Fault Current Limiter (SFCL) Placement on Distributed Generation (DG) Expansion10.1109/TASC.2016.2550598 ↗
15. Application of Superconducting Fault Current Limiter as a Virtual Inertia for DC Distribution Systems10.1109/ACCESS.2021.3115989 ↗
16. Study on Resistive SFCL for Fault Ride-Through Fulfillment of Power Electronic Transformer Interconnecting MV and LV Power Systems10.1109/TASC.2021.3101746 ↗
17. Elshiekh, M. (2020). Increasing Wind Energy Integration into Power Grids Using Multifunctional Superconducting Devices Design. [Ph.D. Thesis, University of Bath].
18. Alam, S., Abido, M.A.Y., and El-Amin, I. (2018). Fault Current Limiters in Power Systems: A Comprehensive Review. Energies, 11.10.3390/en11051025 ↗
19. Comparison Between the Fault Current Limiting Performance of Bi-2212 Bifilar Components and 2G YBCO Coils10.1109/TASC.2013.2238275 ↗
20. Naderi, S.B., Davari, P., Zhou, D., Negnevitsky, M., and Blaabjerg, F. (2018). A Review on Fault Current Limiting Devices to Enhance the Fault Ride-Through Capability of the Doubly-Fed Induction Generator Based Wind Turbine. Appl. Sci., 8.10.20944/preprints201809.0538.v1 ↗
21. Comparison of Inductive and Resistive SFCL to Robustness Improvement of a VSC-HVDC System with Wind Plants Against DC Fault10.1109/TASC.2016.2595622 ↗
22. Analysing Faults and SFCL Response in Electric Aircraft10.1088/1742-6596/1559/1/012103 ↗
23. Experimental and Simulation Study of Resistive Helical HTS Fault Current Limiters: Quench and Recovery Characteristics10.1109/TASC.2021.3061958 ↗
24. Development and test of a 220 kV/1.5 kA resistive type superconducting fault current limiter10.1016/j.physc.2019.06.004 ↗
25. Influencing Factors on Quench and Recovery of YBCO Tapes for DC Superconducting Fault Current Limiter10.1109/TASC.2018.2887336 ↗
26. Alafnan, H., Pei, X., Mansour, D.-E.A., Khedr, M., Song, W., Alsaleh, I., Albaker, A., Alturki, M., and Zeng, X. (2023). Impact of Copper Stabilizer Thickness on SFCL Performance with PV-Based DC Systems Using a Multilayer Thermoelectric Model. Sustainability, 15.10.3390/su15097372 ↗
27. Study on the influencing factors to reduce the recovery time of superconducting tapes and coils for the DC superconducting fault current limiter applications10.1049/hve2.12158 ↗
28. The Structure, Performance and Recovery Time of a 10 kV Resistive Type Superconducting Fault Current Limiter10.1109/TASC.2012.2231899 ↗
29. American Superconductor (2023, August 05). Amperium® Stainless Steel Laminated Wire Type 8602. Available online: https://www.amsc.com/wp-content/uploads/SSAMP8602_DS_A4_0414_WEB.pdf.
30. Thermal and Electrical Analysis of Coated Conductor Under AC Over-Current10.1109/TASC.2007.897199 ↗
31. Effectiveness of Superconducting Fault Current Limiting Transformers in Power Systems10.1109/TASC.2018.2805693 ↗
32. Electrical resistivity of copper, gold, palladium, and silver10.1063/1.555614 ↗
33. Thermal conductivity of materials used for preparation of the hybrid layered conductors based on high temperature superconductors10.1063/1.4712107 ↗
34. Electrical resistivity and thermal conductivity of nine selected AISI stainless steels
35. Generic Model of Three-Phase (RE)BCO Resistive Superconducting Fault Current Limiters for Transient Analysis of Power Systems
36. Short-circuit fault current-limiting characteristics of a resistive-type superconducting fault current limiter in DC grids10.1088/1361-6668/ab6244 ↗