As wind power penetration continues to increase, the sub-synchronous control interaction (SSCI) problem caused by the interaction between doubly fed induction generators (DFIGs) and series-compensated transmission lines has become increasingly prominent, posing a serious threat to power system stability. To address this problem, this research proposes a centralized sub-synchronous oscillation damping controller (CSODC) for wind farms. First, a DFIG impedance model was constructed based on multi-operating-point impedance scanning and a Taylor series expansion, achieving impedance prediction with an error of less than 2% under various power conditions. Subsequently, a CSODC comprising a sub-synchronous damping calculator (SSDC) and a power electronic converter is designed. By optimizing feedback signals, phase shift angles, gain parameters, and filter parameters, dynamic adjustment of controllable impedance in the sub-synchronous frequency band is achieved. Frequency-domain impedance analysis demonstrates that the CSODC significantly enhances the system’s equivalent resistance, reversing it from negative to positive at the resonance frequency point. Time-domain simulations validated the CSODC’s effectiveness in scenarios involving series capacitor switching and wind speed disturbances, demonstrating rapid sub-synchronous current decay. The results confirm that the proposed strategy effectively suppresses sub-synchronous oscillations across multiple scenarios, offering an economical and efficient solution to stability challenges in high-penetration renewable energy grids.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Power Systems and Renewable Energy · Microgrid Control and Optimization · Islanding Detection in Power Systems
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
North China Electric Power Research Institution Co., Ltd. (State Grid Jibei Electric Co., Ltd. Research Institution), Xicheng District, Beijing 100045, China
School of Mechanical and Electrical Engineering, China University of Mining and Technology-Beijing, Beijing 100083, China
Funding
Research on Field Testing Technology for Wide-band Frequency Impedance Characteristics of New Energy Generating Units
References (31)
Show source-provided references
1. Wang, W., Li, G., Chen, Y., He, G., Wu, W., Xiao, Y., Guo, Z., and Zhou, D. (2025). Review of Wideband Impedance Measurement Technology and Equipment for New Energy Power Generation. J. Electr. Eng. China, 1–18. Available online: http://kns.cnki.net/kcms/detail/11.2107.TM.20250411.1501.011.html.
2. Research on the Development of Deep-Sea Floating Wind Power Technology10.1016/j.jes.2014.05.032 ↗
3. Research on Complex Oscillation Problems Caused by New Energy Grid-Connected Systems and Countermeasures
4. Review of Subsynchronous Oscillations in Grid-Connected Systems of Large-Scale Wind Farms
5. A Brief Analysis of New Oscillation Problems in Power Systems
6. Irwin, G.D., Jindal, A.K., and Isaacs, A.L. (2011, January 24–28). Sub-synchronous control interactions between type 3 wind turbines and series compensated AC transmission systems. Proceedings of the 2011 IEEE Power and Energy Society General Meeting, Detroit, MI, USA.10.1109/PES.2011.6039426 ↗
7. Sub-Synchronous Interaction Damping Control for DFIG Wind Turbines10.1109/TPWRS.2014.2327197 ↗
8. Application Analysis of Voltage Single-Loop Control Strategy in Zhangbei Flexible DC Project
9. China’s green energy development becomes the engine of global energy transition
10. Short-term prediction of photovoltaic power based on meteorological characteristics and improved Transformer
11. Online Grid Impedance Measurement Using Discrete-Interval Binary Sequence Injection10.1109/JESTPE.2014.2357494 ↗
12. Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak Grid10.1109/TPEL.2016.2533563 ↗
13. Analysis of D-Q Small-Signal Impedance of Grid-Tied Inverters10.1109/TPEL.2015.2398192 ↗
14. Research on a unified analysis method for the stability of grid-connected converters based on impedance analysis
15. Wang, Q., Zhao, Y., Feng, L., Yi, L., Li, Z., Ma, J., and Shen, Y. (2025). Study on Sub/Supersynchronous Oscillation Suppression Strategies for Direct-Drive Wind Farms via Multi-Terminal Flexible DC Grid-Connection Systems Under Sender-Side Fault Scenarios. J. Electr. Eng. China, 1–11. Available online: http://kns.cnki.net/kcms/detail/11.2107.TM.20250312.1758.005.html.
16. Frequency Coupling Characteristic Modeling and Stability Analysis of Doubly Fed Induction Generator10.1109/TEC.2018.2800043 ↗
17. The Impact of Active Power Restoration Control in a Double-Fed Wind Farm on the Initial Stability of a Wind-Fired Bundled System and Its Improved Control Strategy
18. Wideband Oscillation Suppression Strategy for Grid-connected Double-fed Wind Turbines Based on Impedance Reshaping
19. Study on harmonic interaction between paralleled STATCOMs with cascaded H-bridge topology in wind farm clusters10.1049/rpg2.12185 ↗
20. Modeling and Stability Analysis of VSG-type Grid-connected Energy Storage dq Impedance Considering the Influence of Multiple Control Loops
21. Adaptive Suppression of Sub/Supersynchronous Oscillations in AC Transmission Systems for Black/Gray Box New Energy Power Stations10.23919/CJEE.2024.000056 ↗
22. Data-Driven Impedance Identification and Stability Online Assessment of Wind Farm Connected With MMC-HVDC10.1109/TIA.2023.3333760 ↗
23. Meng, F., Guo, C., Zhang, J., and Hu, C. (2024). Online Identification of Vulnerable Points in Multi-Level Oscillations of Wind Farm Grid-Connected Systems Using Gray Box Modeling of Unit Parameters. Power Syst. Autom., 1–15. Available online: http://kns.cnki.net/kcms/detail/32.1180.tp.20241023.0959.002.html.
24. Black-box identification method for the impedance model of grid-connected converters under all operating conditions
25. Research on the Suppression Strategy With SMES of SSO for the Black-Box DFIG System10.1109/ACCESS.2025.3545570 ↗
26. Improved subsynchronous oscillation detection method in a DFIG-based wind farm interfaced with a series-compensated network10.1016/j.ijepes.2020.105930 ↗
27. A Review of Fault Defense Technologies for Phase-Switching Failures in Multi-Feed High-Voltage Direct Current Transmission Systems
28. Wu, W. (2019). Research on the Wideband Oscillation Mechanism and Suppression Methods of New Energy Power Generation Connected to Weak Grids. [Ph.D. Thesis, Hunan University].
29. Gao, Y. (2020). Impedance Modeling of Double-Feedback Wind Power Grid-Connected Systems and Analysis of Sub/Super-Synchronous Oscillation Mechanisms. [Master’s Thesis, North China Electric Power University].
30. Xu, Y. (2021). Modeling of Impedance and Analysis of Grid Stability of Wind Turbines Under Oscillation Frequency Coupling. [Ph.D. Thesis, Zhejiang University].
31. Zhang, X., Xu, S., Huang, H., Zheng, P., Wang, L., Wang, X., and Wang, Y. (2023, January 14–15). Risk prediction of sub-synchronous oscillation based on the black-box impedance model of DFIG for multiple operating conditions. Proceedings of the 12th International Conference on Renewable Power Generation (RPG 2023), Shanghai, China.10.1049/icp.2023.2221 ↗