Influence of Selected Parameters of Medium-Voltage Network on the Value of Voltage Asymmetry Factors

Grzegorz Hołdyński, Zbigniew Skibko

Applied Sciences· Volume 15· Issue 3

Abstract

The correct and safe operation of electricity grids is a fundamental consideration in guaranteeing the supply of electricity with the correct parameters to consumers. One of the key aspects is how neutral point earthing works. In grids with the neutral point grounded by a Petersen coil, it is very important to properly tune its inductance in relation to the natural capacitance of the power grid. This is important both for the proper operation of earth fault protection and from the point of view of power quality, especially voltage asymmetry. Asymmetry of phase voltages in MV networks has a very negative impact on the operation of the railway network supplied by 12-pulse rectifiers. In this paper, the authors present the influence of the detuning factor of the earth fault compensation and the length and cross-section of the line on the value of voltage asymmetry factors. As the analyses carried out have shown, significant (up to 90%) values of the zero-sequence asymmetry factor can occur at low detuning, which can contribute not only to a decrease in the quality of the transmitted electricity but also to the unnecessary activation of protections. The values of the negative-sequence voltage asymmetry factor are much smaller (do not exceed 0.5% in the analysed cases) and do not depend on the network detuning factor. As the distance from the substation increases, an increase in the values of both types of asymmetry factors is also observed, with the relationship already negligibly small at considerable distances (above 20 km).
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Renewable energy and sustainable power systems · Transportation Systems and Safety · Power Quality and Harmonics

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Faculty of Electrical Engineering, Bialystok University of Technology, 15-351 Białystok, Poland

Funding

Bialystok University of Technology

References (39)

Show source-provided references
1. Rafał, K., Biskupski, J., Bykuć, S., and Chaja, P. (2022). Dynamic Voltage Regulation and Unbalance Compensation in a Low-Voltage Distribution Network Using Energy Storage System. Appl. Sci., 12.10.3390/app122211678 ↗
2. Estimation of the Domestic Agricultural Sector Potential for the Growth of Energy Cultures for Bioenergy Fuel Production
3. Zajkowski, K., Duer, S., Paś, J., and Pokorádi, L. (2023). Cooperation of a Non-Linear Receiver with a Three-Phase Power Grid. Energies, 16.10.3390/en16031418 ↗
4. Zajkowski, K., and Duer, S. (2023). Decomposition of the Voltages in a Three-Phase Asymmetrical Circuit with a Non-Sinusoidal Voltage Source. Energies, 16.10.3390/en16227616 ↗
5. Olczykowski, Z. (2021). Electric Arc Furnaces as a Cause of Current and Voltage Asymmetry. Energies, 14.10.3390/en14165058 ↗
6. Möller, F., and Meyer, J. (June, January 29). Survey of voltage unbalance and unbalanced power in German public LV networks. Proceedings of the 2022 20th International Conference on Harmonics & Quality of Power (ICHQP), Naples, Italy.10.1109/ICHQP53011.2022.9808568 ↗
7. Hołdyński, G., Skibko, Z., Firlit, A., and Walendziuk, W. (2024). Analysis of the Impact of a Photovoltaic Farm on Selected Parameters of Power Quality in a Medium-Voltage Power Grid. Energies, 17.10.3390/en17030623 ↗
8. Al-Shetwi, A.Q., Hannan, M.A., Jern, K.P., Alkahtani, A.A., and PG Abas, A.E. (2020). Power Quality Assessment of Grid-Connected PV System in Compliance with the Recent Integration Requirements. Electronics, 9.10.3390/electronics9020366 ↗
9. Skibko, Z., Tymińska, M., Romaniuk, W., and Borusiewicz, A. (2021). Impact of the Wind Turbine on the Parameters of the Electricity Supply to an Agricultural Farm. Sustainability, 13.10.3390/su13137279 ↗
10. Hołdyński, G., Skibko, Z., and Borusiewicz, A. (2023). Analysis of the Influence of Load on the Value of Zero-Voltage Asymmetry in Medium-Voltage Networks Operating with Renewable Energy Sources. Energies, 16.10.3390/en16020580 ↗
11. Roy, R.B., Alahakoon, A., and Arachchillage, S.J. (2021). Grid impacts of uncoordinated fast charging of electric ferry. Batteries, 7.10.3390/batteries7010013 ↗
12. Probabilistic assessment of the impact of electric vehicles and nonlinear loads on power quality in residential networks10.1016/j.ijepes.2021.106807 ↗
13. Bozalakov, D., Mnati, M.J., Laveyne, J., Desmet, J., and Vandevelde, L. (2019). Battery storage integration in voltage unbalance and overvoltage mitigation control strategies and its impact on the power quality. Energies, 12.10.3390/en12081501 ↗
14. Distribution Voltage Regulation Through Active Power Curtailment With PV Inverters and Solar Generation Forecasts10.1109/TSTE.2016.2577559 ↗
15. Flexible Unbalanced Compensation of Three-Phase Distribution System Using Single-Phase Distributed Generation Inverters10.1109/TSG.2017.2778508 ↗
16. Kaur, M., and Ghosh, S. (2017). Effective Loss Minimization and Allocation of Unbalanced Distribution Network. Energies, 10.10.3390/en10121931 ↗
17. Verification of the Measurement System in a Production Organization
18. Shigenobu, R., Nakadomari, A., Hong, Y.-Y., Mandal, P., Takahashi, H., and Senjyu, T. (2020). Optimization of Voltage Unbalance Compensation by Smart Inverter. Energies, 13.10.3390/en13184623 ↗
19. Load balancing with EV chargers and PV inverters in unbalanced distribution grids10.1109/TSTE.2015.2402834 ↗
20. A Study of Load Imbalance Influence on Power Quality Assessment for Distribution Networks10.3390/electricity2010005 ↗
21. Kahingala, T.D., Perera, S., Agalgaonkar, A.P., and Jayatunga, U. (2018, January 27–30). Determining the Impact of Line Asymmetries on Network Voltage Unbalance based on Balanced Load Flow Studies. Proceedings of the 2018 Australasian Universities Power Engineering Conference (AUPEC), Auckland, New Zealand.10.1109/AUPEC.2018.8757897 ↗
22. Kuliński, K., and Heyduk, A. (2024). Ground Fault in Medium-Voltage Power Networks with an Isolated Neutral Point: Spectral and Wavelet Analysis of Selected Cases in an Example Industrial Network Modeled in the ATP-EMTP Package. Energies, 17.10.3390/en17071532 ↗
23. Sołjan, Z., Hołdyński, G., and Zajkowski, M. (2021). CPC-Based Minimizing of Balancing Compensators in Four-Wire Nonsinusoidal Asymmetrical Systems. Energies, 14.10.3390/en14071815 ↗
24. Lin, X., Chen, H., Xu, K., and Xu, J. (2023). Time Estimation Algorithm of Single-Phase-to-Ground Fault Based on Two-Step Dimensionality Reduction. Energies, 16.10.3390/en16134921 ↗
25. Influence of neutral point work on the voltage asymmetry in MV power network
26. Toader, D., Greconici, M., Vesa, D., Vintan, M., Solea, C., Maghet, A., and Tatai, I. (2021). The Influence of the Characteristics of the Medium Voltage Network on the Single Line-to-Ground Fault Current in the Resistor Grounded Neutral Networks. Designs, 5.10.3390/designs5030053 ↗
27. Şolea, C., Toader, D., Vintan, M., Greconici, M., Vesa, D., and Tatai, I. (2023, January 21–23). The influence of insulation active power losses on the single line-to-ground fault in medium voltage electrical networks with resonant grounding. Proceedings of the 10th International Conference on Modern Power Systems (MPS), Cluj-Napoca, Romania.10.1109/MPS58874.2023.10187515 ↗
28. Yang, D., Lu, B., and Lu, H. (2023). High-Resistance Grounding Fault Detection and Line Selection in Resonant Grounding Distribution Network. Electronics, 12.10.3390/electronics12194066 ↗
29. (2022). Voltage Characteristics of Electricity Supplied by Public Electricity Networks (Standard No. EN 50160).
30. Modified method of the automated earth fault compensation in mv network with earth fault asymmetry
31. A Method for Measuring and Adjusting the Detuning of Resonant Grounding Systems With Transient Information After Arc Extinction10.1109/TPWRD.2022.3194946 ↗
32. A new fault location algorithm for radial distribution systems using modal analysis10.1016/j.ijepes.2012.08.053 ↗
33. A new method for non-unit protection of power transmission lines based on fault resistance and fault angle reduction10.1016/j.ijepes.2013.10.027 ↗
34. Hołdyński, G., Skibko, Z., and Walendziuk, W. (2024). Power and Energy Losses in Medi-um-Voltage Power Grids as a Function of Current Asymmetry—An Example from Po-land. Energies, 17.10.3390/en17153706 ↗
35. Asymmetry parameters for zero sequence component in medium voltage networks
36. Raunig, C., Schmautzer, E., Fickert, L., Achleitner, G., and Obkircher, C. (2009, January 8–11). Displacement voltages in resonant grounded grids caused by capacitive coupling. Proceedings of the CIRED 2009—20th International Conference and Exhibition on Electricity Distribution—Part 1, Prague, Czech Republic.10.1049/cp.2009.0692 ↗
37. Raunig, C., Obkircher, C., Achleitner, G., Schmautzer, E., and Fickert, L. (2008, January 27–29). Calculation of neutral to earth voltage levels in compensated high voltage networks influenced by cross coupling. Proceedings of the 2008 Power Quality and Supply Reliability Conference, Parnu, Estonia.10.1109/PQ.2008.4653752 ↗
38. Ground Fault Compensation Effectiveness Conditions in MV Grids with Significant To-Ground Unbalance
39. Andruszkiewicz, J., Lorenc, J., Olejnik, B., Weychan, A., and Staszak, B. (2024). Method of Reducing the Effects of Repeated Ignition during Earth Faults in Compensated Medium Voltage Networks. Energies, 17.10.3390/en17010093 ↗