Experimental and Simulation Study of Micro-Channel Backplane Heat Pipe Air Conditioning System in Data Center

Liping Zeng, Xing Liu, Quan Zhang, Jun Yi, Xiaohua Li, Xianglong Liu, Huan Su

Applied Sciences· Volume 10· Issue 4

Abstract

This paper mainly studies the heat transfer performance of backplane micro-channel heat pipes by establishing a steady-state numerical model. Compared with the experimental data, the heat transfer characteristics under different structure parameters and operating parameters were studied, and the change of heat transfer coefficient inside the system, the air outlet temperature of the back plate and the influence of different environmental factors on the heat transfer performance of the system were analyzed. The results show that the overall error between simulation results and experimental data is less than 10%. In the range of the optimal filling rate (FR = 64.40%–73.60%), the outlet temperature at the lowest point and the highest point of the evaporation section is 22.46 °C and 19.60 °C, the temperature difference does not exceed 3 °C, and the distribution gradient in vertical height is small and the air outlet temperature is uniform. The heat transfer coefficient between the evaporator and the condenser is larger than the heat transfer coefficient under the conditions of low and high liquid charge rate. It increases gradually along the flow direction, and decreases gradually with the flow rate of the condenser. When the width of the flat tube of the evaporator increases from 20 mm to 28 mm, the internal pressure drop of the evaporator decreases by 45.83% and the heat exchange increases by 18.34%. When the number of evaporator slices increases from 16 to 24, the heat transfer increases first and then decreases, with an overall decrease of 2.86% and an increase of 87.67% in the internal pressure drop of the evaporator. The inclination angle of the corrugation changes from 30° to 60°, and the heat transfer capacity and pressure drop increase. After the inclination angle is greater than 60°, the heat transfer capacity and resistance decrease. The results are of great significance to system optimization design and engineering practical application.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Heat Transfer and Boiling Studies · Heat Transfer and Optimization · Heat Transfer Mechanisms

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Hunan Engineering Research Center of Energy Saving and Material Technology of Green and Low Carbon Building, Hunan Institute of Engineering, Xiangtan 411104, China

College of Civil Engineering, Hunan University, Changsha 410082, China

Funding

National Key R&D program of China · Hunan provincial key projects · The provincial Natural Science youth Foundation of Hunan, China · Provincial Natural Science Foundation of Hunan, China

References (35)

Show source-provided references
1. (2017). 2016–2017 China IDC Industry Development Research Report, Zhongke Zhidao Technology Co. Ltd.
2. Koomey, J. (2011). Growth in Data Center Electricity Use 2005 to 2010, Analytics Press.
3. Zhou, Q. (2015, January 8). Status and development trend of data center construction. Proceedings of the 2015 Annual Conference of Tianjin Television Technology Research Association, Tianjin, China.
4. Application of separated heat pipe in data center air conditioning system
5. Start-up and heat transfer of a separate heat pipe with microchannel evaporator
6. Study on the inclination parameters of the evaporation section of a separate heat pipe heat exchanger
7. Experimental research on heat pipe air conditioning performance of microchannel heat exchangers using CO2 as refrigerant
8. Experimental study on the filling rate of a separate heat pipe using a microchannel evaporator
9. Analytical study of impact of the wick’s fractal parameters on the heat transfer capacity of a novel micro-channel loop heat pipe10.1016/j.energy.2018.06.075 ↗
10. Study on thermal performance of micro channel separate heat pipe for telecommunication stations: Experiment and simulation10.1016/j.ijrefrig.2015.08.006 ↗
11. Experimental study on the thermal characteristics of micro channel separate heat pipe respect to different filling ratio10.1016/j.applthermaleng.2016.03.016 ↗
12. Experimental investigation on the thermal performance of water cooled multi-split heat pipe system (MSHPS) for space cooling in modular data centers10.1016/j.applthermaleng.2016.07.006 ↗
13. Yuan, J. (2018). Study on Heat Transfer Performance of Microchannel Separated Heat Pipe, Nanjing Normal University.
14. The numerical investigation of heat transfer and pressure drop of turbulent flow in a triangular microchannel10.1016/j.physe.2017.06.013 ↗
15. Jin, X. (2012). Research on Energy Saving Performance of Microchannel Separated Heat Pipe Communication Base Station, Shanghai Jiao Tong University.
16. Experimental study on air conditioning performance of separate heat pipe type machine room
17. A review on microchannel heat exchangers and potential applications10.1002/er.1720 ↗
18. Analysis of heat transfer characteristics of data center backplane air conditioning
19. Experimental study on heat transfer performance of cabinet server heat pipe backplane
20. Analysis of the influence of factors in cabinet server on the heat exchange performance of heat pipe backplane
21. Research on active anti condensation of heat pipe backplane system in data room
22. Safety research on the application of heat pipe refrigeration backplane system in data room
23. Practical research on the application of heat pipe backplane air conditioning in Data Center—System unbalanced operation analysis
24. Heat pipe back in data center Experimental study on the application of panel air conditioning—Analysis of the air flow field in the machine room
25. Study on the extreme working conditions of the heat pipe backplane system in the data room
26. Application of separated heat pipe system in data center cooling10.1016/j.applthermaleng.2016.08.025 ↗
27. Experimental study on working fluid flow instability in separation heat pipe evaporation section
28. New Equations for Heat and Mass Transfer in Turbulent Pipe and Channel Flows
29. Universal approach to predicting saturated flow boiling heat transfer in mini/micro-channels-Part II. Two-phase heat transfer coefficient10.1016/j.ijheatmasstransfer.2013.04.014 ↗
30. Friedel, L. (1979, January 5–8). Improved friction pressure drop correlation for horizontal and vertical two-phase pipe flow. Proceedings of the European Two-Phase Flow Group Meeting, Ispra, Italy.
31. Air-side thermal hydraulic performance of multi louvered fin aluminum heat exchangers10.1016/S0140-7007(01)00025-1 ↗
32. Experimental Study of Turbulent Flow Heat Transfer and Pressure Drop in a Plate Heat Exchanger with Chevron Plates10.1115/1.2825923 ↗
33. Condensation heat transfer and pressure drop of refrigerant R-134a in a plate heat exchanger10.1016/S0017-9310(98)00217-8 ↗
34. Analysis of the influence of three key geometric parameters on the heat transfer performance of herringbone corrugated brazed plate heat exchangers
35. Designs of the New Type Plate Heat Exchangers and their Heat Transfer Characteristics10.1252/kakoronbunshu1953.35.587 ↗