Energy Performance Analysis of an Integrated Distributed Variable-Frequency Pump and Water Storage System for District Cooling Systems
Source abstract
Abstract
In a district cooling system (DCS), the distribution system (i.e., cooling water system or chilled water system) will continue to be a critical consideration because it substantially contributes to the total energy consumption. Thus, in this paper, a new distributed variable-frequency pump (DVFP) system with water storage (WS) for cooling water is adapted to a DCS with large end-use cooling load fluctuations. The basic principle and energy saving potential of the new system is analyzed. A case study of a DCS with a conventional central circulating pump (CCCP) system is presented to compare the energy consumption and the operating performance of CCCP and DVFP systems that are exposed to various weather conditions. The methods to perform this case study include, cooling load simulation and the modeling of two water distribution networks and systems via several commercial software packages. By replacing the throttling valves with a DVFP, the pump efficiency is increased and transportation energy consumption is reduced. Additionally, by introducing water tank storage, the cooling water is cooled at night and is released at a peak hour during the daytime, thereby further reducing the energy cost. As compared to the field test results of the CCCP system, the daily electrical energy saved by the DVFP and WS system is approximately 57% for a cooling water pump system on the hottest day in summer. This value also corresponds to approximately 10% of the energy saved for the entire system. Furthermore, additional energy could be saved under partial loading conditions.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Building Energy and Comfort Optimization · Integrated Energy Systems Optimization · Smart Grid Energy Management
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Building Science, School of Architecture, Tsinghua University, Beijing 100084, China
Funding
Natural Science Foundation of China · 13th Five-Year National Key Technology R&D Program of China
References (29)
Show source-provided references
1. The European cold market
2. Fuel savings and CO2 emissions for tri-generation systems10.1016/S1359-4311(03)00068-1 ↗
3. Applying district-cooling technology in Hong Kong10.1016/j.apenergy.2004.01.002 ↗
4. Energy conservation in buildings: Cogeneration and cogeneration coupled with thermal energy storage10.1016/S0306-2619(03)00100-4 ↗
5. Eley, C., and Hydeman, M. (1992). Water-Loop Heat Pump Systems, Eley (Charles) Associates.
6. Conception of combination of gas-engine-driven heat pump and water-loop heat pump system10.1016/j.ijrefrig.2005.02.004 ↗
7. Heat Recovery in Buildings Using Water-Loop Heat Pump Systems: Part I—Energy Requirements and Savings
8. Design and operation of a commercial water-loop heat pump system with a ground-loop heat exchanger
9. Eppelheimer, D.M. (1996). Variable Flow—The Quest For System Energy Efficiency, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
10. Evaluation of temperature degradation in hydraulic flow networks10.1016/j.enbuild.2011.03.025 ↗
11. Energy efficient control of variable speed pumps in complex building central air-conditioning systems10.1016/j.enbuild.2008.09.002 ↗
12. Online adaptive control for optimizing variable-speed pumps of indirect water-cooled chilling systems10.1016/S1359-4311(00)00109-5 ↗
13. Assessing variable speed pump efficiency in water distribution systems10.5194/dwes-5-15-2012 ↗
14. Energy consumption analysis and system optimization of replacing control valves by frequency controlled pumps in terminal system
15. Hydraulic performance of a new district heating systems with distributed variable speed pumps10.1016/j.apenergy.2013.06.031 ↗
16. Electricity consumption and economic analyses of district heating system with distributed variable speed pumps10.1016/j.enbuild.2016.03.005 ↗
17. Improved operation of water distribution systems using variable-speed pumps10.1061/(ASCE)0733-9402(1998)124:3(90) ↗
18. Simulink© simulator for building hydronic heating systems using the Newton–Raphson algorithm10.1016/j.enbuild.2009.03.006 ↗
19. Energy saving factors affecting analysis on district heating system with distributed variable frequency speed pumps10.1016/j.applthermaleng.2017.04.079 ↗
20. Energy use in a district cooling system with stratified chilled-water storage
21. Handbook, A. (1996). HVAC Systems and Equipment, American Society of Heating, Refrigerating, and Air Conditioning Engineers.
22. Kawashima, M., Dorgan, C.E., and Mitchell, J.W. (1996). Optimizing System Control with Load Prediction by Neural Networks for an Ice-Storage System, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
23. Performance evaluation of district cooling plant with ice storage10.1016/j.energy.2005.11.022 ↗
24. Review on sustainable thermal energy storage technologies, Part II: Cool thermal storage10.1016/S0196-8904(98)00024-7 ↗
25. A summary of experience with stratified chilled water tanks
26. DeST—An integrated building simulation toolkit Part I: Fundamentals10.1007/s12273-008-8118-8 ↗
27. Heat demand profiles of energy conservation measures in buildings and their impact on a district heating system10.1016/j.apenergy.2015.10.024 ↗
28. Rotimi, A., Bahadori-Jahromi, A., Mylona, A., Godfrey, P., and Cook, D. (2017). Estimation and Validation of Energy Consumption in UK Existing Hotel Building Using Dynamic Simulation Software. Sustainability, 9.10.3390/su9081391 ↗
29. Hydraulic Regime Analysis of On-Off Valve Regulation10.4028/www.scientific.net/AMM.522-524.1009 ↗