journal article·2025-08-15Open access

Evaluation of Fire Resistance of Firestop Systems for Floor-Drain-Sleeve Penetrations Based on Geometric Configuration

Hong-Beom Choi, Jin-O Park, A-Yeong Jeong, Hyung-Do Lee, Seung-Yong Hyun

Applied Sciences· Volume 15· Issue 16

Abstract

This study quantitatively analyzed the impact of geometric configuration of floor-drain sleeves penetrating floor slabs on the thermal insulation performance of firestop systems. Eleven square and round sleeve types were tested, with the lower-sleeve length and upper-opening area as key variables. Using identical firestop material, temperatures were measured at specific points within each sleeve. The results showed that temperatures at the water seal and trench center typically remained below 100 °C. However, in a square sleeve (with a 30 mm lower sleeve and 22,500 mm2 opening), the trench center reached 254.9 °C due to heat concentration. As the lower-sleeve length increased from 30 mm to 60 mm, internal temperatures notably decreased—a trend that exhibited a strong statistical relationship, explaining 93% of the thermal variance (R2 = 0.93). While larger upper openings also tended to reduce temperatures, the correlation was weaker (R2 = 0.42). High-temperature responses were predominantly observed in square sleeves, which were also dimensionally less favorable—highlighting the need to distinguish geometric effects from size disadvantages. This study empirically demonstrated that sleeve geometry significantly affects fire resistance performance and provides foundational data for advancing performance-based firestop certification and developing geometry-informed analytical frameworks.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Fire dynamics and safety research · Fire effects on concrete materials · Environmental and Industrial Safety

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Korea Institute of Civil Engineering and Building Technology, Goyang-si 10223, Republic of Korea

Funding

Korea Institute of Civil Engineering and Building Technology (KICT)

References (23)

Show source-provided references
1. UNISDR (2019). Global Assessment Report on Disaster Risk Reduction 2019, United Nations Office for Disaster Risk Reduction. Available online: https://www.undrr.org/publication/global-assessment-report-disaster-risk-reduction-2019.
2. Buchanan, A.H., and Abu, A.K. (2017). Structural Design for Fire Safety, John Wiley & Sons. [2nd ed.].10.1002/9781118700402 ↗
3. Babrauskas, V. (2003). Ignition Handbook, Fire Science Publishers. [1st ed.].
4. Performance-based building regulatory systems: Structure, hierarchy and linkages
5. Gillespie, P.E., Mattes, B., Neese, R.K., O’Leary, P.E., Talbot, J., and Wasilewski, B. (2007). Guideline on Through Penetration Firestopping, SMACNA. [2nd ed.]. Available online: https://www.smacna.org/docs/default-source/resource-documents/guidelines-through-penetration-firestopping.pdf?sfvrsn=6c6e3fa2_1.
6. Fire-stop wraps and collars with intumescent materials—Performance comparison10.1016/j.proeng.2017.02.113 ↗
7. Estimation of effective thermophysical properties of firestopping sealants: Methodology and case study10.1016/j.firesaf.2023.103928 ↗
8. Bezpieczeństwo pożarowe, Cz. 17: Przejścia instalacyjne
9. Temperatura uszczelnień przejść rur metalowych przez ściany i stropy w badaniach odporności ogniowej
10. Problematyka prawidłowego odbioru wybranych oddzieleń przeciwpożarowych
11. Problematyka prawidłowego odbioru uszczelnień przejść instalacyjnych
12. Choi, H.-B., Jeong, A.-Y., Park, J.-O., Hyun, S.-Y., and Lee, H.-D. (2025). Experimental study on fire-resistance performance depending on the applied volume of firestop material in metallic and nonmetallic penetration systems. Appl. Sci., 15.10.3390/app15116259 ↗
13. A study on assessment of penetration seals performance of nuclear power plants
14. Standard supporting and F-class structures for improving the firestop recognition system10.9798/KOSHAM.2019.19.5.127 ↗
15. (2024). Standard Test Method for Fire Tests of Penetration Firestop Systems (Standard No. ASTM E814).
16. (2021). Standard for Fire Tests of Through-Penetration Firestops (Standard No. UL 1479).
17. (2021). Fire Resistance Tests for Service Installations—Part 3: Penetration Seals (Standard No. EN 1366-3).
18. Promat (2017). The Passive Fire Protection Handbook, Promat. Available online: https://www.promat.com/en-gb/construction/tools-services/fire-protection-handbook/.
19. Analysis of causes of casualties in Jecheon Sports Center fire—Focus on structural factors of building10.7731/KIFSE.2018.32.4.086 ↗
20. (2013). Fire Resistance Tests—Elements of Building Construction—Part 1: Requirements and Recommendations for Measuring Fire Resistance of Penetration Seals (Standard No. KS F ISO 10295-1:2013 (Confirmed 2023)).
21. (1999). Fire-Resistance Tests—Elements of Building Construction—Part 1: General Requirements (Standard No. ISO 834-1:1999).
22. Heo, I., Darkhanbat, K., Han, S.-J., Choi, S.-H., Jeong, H., and Kim, K.S. (2021). Experimental and numerical investigations on fire resistance performance of precast concrete hollow-core slabs. Appl. Sci., 11.10.3390/app112311500 ↗
23. Wickström, U. (2016). Temperature Calculation in Fire Safety Engineering, Springer. Available online: https://link.springer.com/book/10.1007/978-3-319-30172-3.10.1007/978-3-319-30172-3 ↗