Optimization of Airflow Organization in Bidirectional Air Supply Data Centers in China
Source abstract
Abstract
Optimizing airflow organization is essential for ensuring the energy-efficient and secure operation of data centers. To address common airflow distribution issues in air-cooled systems, such as uneven air supply and cooling capacity imbalance, this study investigates a bidirectional airflow data center room located in a hot-summer and warm-winter region. A computational fluid dynamics (CFD) model was developed based on field-measured data to analyze the airflow distribution characteristics and evaluate the existing thermal conditions. Three optimization strategies were systematically examined: (1) Installation of rack blanking panels, (2) cold aisle containment with varying degrees of closure, and (3) combined implementations of these measures. Performance evaluation was conducted using three thermal metrics: the Return Temperature Index (RTI), Supply Heat Index (SHI), and Rack Cooling Index (RCIHI). The results demonstrate that among individual optimization strategies, rack blanking panels achieved the most significant improvement, reducing SHI by 42.61% while effectively eliminating local hotspots. For combined optimization strategies, the rack blanking panels and fully contained cold aisle containment showed optimal performance, improving cooling utilization efficiency by 88.26%. The optimal retrofit solution for this data center is the rack blanking panels with fully contained cold aisle containment. When considering budget constraints, the secondary option would be rack blanking panels with cold aisle top-only containment. These findings provide practical guidance for energy efficiency improvements in similar data center environments.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Air Traffic Management and Optimization · Air Quality Monitoring and Forecasting · Simulation Techniques and Applications
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
School of Mechanical and Automotive Engineering, South China University of Technology, Guangzhou 510640, China
Guangzhou Institute of Modern Industrial Technology, Guangzhou 511458, China
Artificial Intelligence and Digital Economy Guangdong Provincial Laboratory (Guangzhou), Guangzhou 511442, China
Funding
Natural Science Foundation of Guangdong Province
References (33)
Show source-provided references
1. The Fourth Industrial Revolution and Environmental Efficiency: The Role of Fintech Industry10.1016/j.jclepro.2022.135196 ↗
2. Research on High-Quality Development of Computing Power Network: Practical Challenges, Institutional Foundations and Technological Supports
3. Optimizing Energy Consumption for Data Centers10.1016/j.rser.2015.12.283 ↗
4. A Review on Efficient Thermal Management of Air- and Liquid-Cooled Data Centers: From Chip to the Cooling System10.1016/j.apenergy.2017.08.037 ↗
5. Energy Savings of Hybrid Dew-Point Evaporative Cooler and Micro-Channel Separated Heat Pipe Cooling Systems for Computer Data Centers10.1016/j.energy.2018.07.172 ↗
6. System-Level Experimental Investigations of the Direct Immersion Cooling Data Center Units with Thermodynamic and Thermoeconomic Assessments10.1016/j.energy.2020.119373 ↗
7. A Review on Airflow Distribution and Management in Data Center10.1016/j.enbuild.2018.08.050 ↗
8. Investigation of Air Management and Energy Performance in a Data Center in Finland: Case Study10.1016/j.enbuild.2011.08.034 ↗
9. An Experimental and Theoretical Investigation of the Extent of Bypass Air within Data Centres Employing Aisle Containment, and Its Impact on Power Consumption10.1016/j.apenergy.2016.03.076 ↗
10. Optimization of the Thermal Environment of a Small-Scale Data Center in China10.1016/j.energy.2020.117080 ↗
11. A Critical Review on the Thermal Management of Data Center for Local Hotspot Elimination10.1016/j.enbuild.2023.113486 ↗
12. CFD Investigation of Airflow Management in a Small Container Data Center10.1109/TCPMT.2019.2916017 ↗
13. Effects of Airflow on the Thermal Environment and Energy Efficiency in Raised-Floor Data Centers: A Review10.1016/j.scitotenv.2019.133801 ↗
14. Simulation Study on the Influence of Air Supply Methods on Airflow Organization in Data Centers
15. Review of Optimization Measures for Static Pressure Box in Data Centers
16. Comprehensive study on the effects of plenum depths on air flow and thermal managements in data centers10.1016/j.ijthermalsci.2017.09.001 ↗
17. Yu, F., Chen, H., Wang, W., and An, J. (2025). Optimization Strategies for Underfloor Air Distribution in a Small-Scale Data Center. Buildings, 15.10.3390/buildings15030428 ↗
18. Effect of CRAC Units Layout on Thermal Management of Data Center10.1016/j.applthermaleng.2017.03.003 ↗
19. Effect of Raised Floor Height on Different Arrangement of Under-Floor Air Distribution Performance in Data Center10.1016/j.proeng.2017.10.425 ↗
20. Simulation Study on the Effect of Baffles on the Thermal Environment of Data Centers
21. Mohsenian, G., Khalili, S., and Sammakia, B. (2019, January 28–31). A design methodology for controlling local airflow delivery in data centers using air dampers. Proceedings of the 2019 18th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), Las Vegas, NV, USA.10.1109/ITHERM.2019.8757270 ↗
22. Intelligent Rack-Level Cooling Management in Data Centers with Active Ventilation Tiles: A Deep Reinforcement Learning Approach10.1109/MIS.2021.3049865 ↗
23. Air flow management in a contained cold aisle using active fan tiles for energy efficient data center operation10.1080/01457632.2015.1051386 ↗
24. Design and Optimization Analysis of Airflow Organization in Underfloor Ventilation Data Centers
25. Optimization of airflow organization in fan-wall data center via baffles10.1016/j.applthermaleng.2024.122745 ↗
26. Experimental characterization of various cold aisle containment configurations for data centers
27. Experimental and numerical study of airflow distribution optimisation in high-density data centre with flexible baffles10.1016/j.buildenv.2018.05.043 ↗
28. Experimental and numerical investigation of an airflow management system in data center with lower-side terminal baffles for servers10.1016/j.buildenv.2019.03.039 ↗
29. (2017). Code for Design of Electronic Information System Room (Standard No. GB 50174-2017).
30. Ni, J., Jin, B.W., Zhang, B., and Wang, X.W. (2017). Simulation of Thermal Distribution and Airflow for Efficient Energy Consumption in a Small Data Centers. Sustainability, 9.10.3390/su9040664 ↗
31. A review on airflow management in data centers10.1016/j.apenergy.2019.02.041 ↗
32. A Review on Evaluation Metrics of Thermal Performance in Data Centers10.1016/j.buildenv.2020.106907 ↗
33. American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) (2014). Measurement of Energy, Demand, and Water Savings, ASHRAE. ASHRAE Guideline 14.