The Effect of Hydrophilic Surface Coating of Fins on the Performance of Fin-and-Tube Heat Exchangers
Source abstract
Abstract
With the rapid progress in data mining, deep learning, and artificial intelligence, the demand for datacenters of various sizes increases globally. Datacenters typically require an environment with properly controlled temperature and humidity conditions for their proper operations. These needed environmental conditions are always provided by an air conditioning system. In humid and hot regions, both energy consumption and the splash of water condensate in using the fin-and-tube heat exchangers are of concern because reliability issues can occur. In this study, the effects of fin surface hydrophilic/hydrophobic coatings on the performance of the fin-and-tube heat exchangers, including the heat transfer rate, pressure drop, and water-condensate splash, were investigated experimentally. By varying the cooling air speeds and fin pitches, the results show that hydrophilic surface coating is an effective method in reducing both the pressure drop (thus saving energy) and the condensate splash, while not affecting the heat transfer rates significantly. The water splash reduction is achieved by both the increased air speed for splashing and a smaller amount of splashing. Water splash can even be completely eliminated if the airspeed was below about 3 m/s. In contrast, hydrophobic surface coating will increase both pressure drop and water splash; thus, should be applied with caution.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Heat Transfer and Optimization · Heat Transfer and Boiling Studies · Solar-Powered Water Purification Methods
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Industrial Technology Education, National Kaohsiung Normal University, Kaohsiung 82444, Taiwan
Department of Electronic Engineering, Minghsin University of Science and Technology, Hsinchu 30401, Taiwan
Funding
Ministry of Science and Technology, Taiwan, Republic of China
References (23)
Show source-provided references
1. (2005). Telecommunications Infrastructure Standard for Data Centers (Standard No. TIA-942).
2. (2010). 2010 Unitary Air-Conditioners for Computer and Data Processing Room (Standard No. GBT 19413).
3. Effects of hydrophilic coating on air side heat transfer and friction characteristics of wavy fin and tube heat exchangers under dehumidifying conditions10.1016/j.enconman.2007.03.017 ↗
4. Airside characteristics of heat, mass transfer and pressure drop for heat exchangers of tube-in hydrophilic coating wavy fin under dehumidifying conditions10.1016/j.ijheatmasstransfer.2009.03.066 ↗
5. Air-Side Surface Wettability Effects on the Performance of Slit-Fin-and-Tube Heat Exchangers Operating Under Wet-Surface Conditions10.1115/1.2994722 ↗
6. Heat and mass transfer for plate fin-and-tube exchangers with and without hydrophilic coating10.1016/S0017-9310(98)00060-X ↗
7. Wetting Coatings for Dehumidifying Heat Exchangers10.1080/10789669.2000.10391260 ↗
8. Condensate carryover phenomena in dehumidifying, finned-tube heat exchangers10.1016/S0894-1777(00)00024-8 ↗
9. Characteristic analysis of condensate carry-over according to the surface tensions in the wet and the dry conditions on the fin surfaces of heat exchangers10.1007/BF03027587 ↗
10. Analysis of the Condensate Carryover Phenomenon on Fin and Tube Evaporators
11. A fractal dropwise condensation heat transfer model including the effects of contact angle and drop size distribution10.1016/j.ijheatmasstransfer.2014.11.083 ↗
12. Numerical model for liquid droplet motion on vertical plain-fin surface10.1080/10789669.2014.890460 ↗
13. Condensing droplet behaviors on fin surface under dehumidifying condition: Part I: Numerical model10.1016/j.applthermaleng.2015.02.082 ↗
14. Condensing droplet behaviors on fin surface under dehumidifying condition. Part II: Experimental validation10.1016/j.applthermaleng.2015.05.088 ↗
15. (2000). Methods of Salt Spray Testing (Standard No. JIS Z 2371).
16. Low-bond axisymmetric drop shape analysis for surface tension and contact angle measurements of sessile drops10.1016/j.colsurfa.2010.04.040 ↗
17. A numerical investigation of the geometric effects on the performance of plate finned-tube heat exchanger10.1016/j.enconman.2010.10.026 ↗
18. Kashif, N., and Khan, M.S. (2018). Thermal-Hydraulic Performance of Wavy-Fin Heat Exchanger Under Dehumidifying Condition, USDOE Office of Energy Efficiency and Renewable Energy (EERE).
19. Fin and tube heat exchanger: Constructal thermo-economic optimization10.1016/j.ijheatmasstransfer.2021.121257 ↗
20. ASHRAE (1985). ASHRAE Handbook Fundamentals, American Society of Heating, Refrigerating, and Air-Conditioning Engineers. SI ed Atlanta, Ga.
21. Influence of Surface Modification on the Transient Dehumidification Performance of Fin-and-tube Heat Exchanger10.1016/j.ijheatmasstransfer.2021.121202 ↗
22. Hewitt, G.F. (1998). Heat Exchanger Design Handbook, Begell House. Chapter 2.2.4.
23. New Correlation Equations for Finned Tube Heat Exchangers10.36478/jeasci.2019.1538.1548 ↗