Measurement Method and Experimental Analysis of Liquid Entrainment for a Flooded Evaporator of a Water-Cooled Centrifugal Chiller Based on Energy Balance
Source abstract
Abstract
Liquid entrainment in a flooded evaporator has an important impact on the performance and safety of a water-cooled centrifugal chiller. In this paper, two methods for measuring the liquid entrainment factor in the evaporator of a centrifugal chiller based on energy balance are proposed. Method 1 involves only the heat exchange capacity of the evaporator and Method 2 involves both evaporator and condenser. The applicable conditions of the methods are discussed. Experimental measurements on the flooded evaporator of a single-stage water-cooled centrifugal chiller with refrigerant R134a show that, for a system with good thermal balance, there is little difference in the entrainment factor values obtained by the two methods. Method 2 was found to have slightly higher measurement accuracy, compared to Method 1. The uncertainty propagation analysis shows that for Method 2, the inlet and outlet water temperatures of the evaporator and condenser, motor input power, motor efficiency, transmission power loss and compressor suction and discharge temperatures are important factors. The experimental results show that the variation of the evaporator entrainment factor with refrigerant charge amount is different for different cooling capacity. At 700 and 800 refrigeration ton (RT), the entrainment factor of the test evaporator increases with the increase of refrigerant charge and the growth rate gradually accelerates. For the chiller tested, when the entrainment factor reaches 0.89% and 1.02%, respectively, at 700 ton and 800 ton, the rapid increase of the entrainment factor leads to a significant decrease in the coefficient of performance (COP) during the charging process. Based on the analysis of the experimental results, it is recommended that the maximum entrainment factor for efficient operation of the centrifugal chiller should be controlled within 1%.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Heat Transfer and Boiling Studies · Heat Transfer and Optimization · Refrigeration and Air Conditioning Technologies
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Department of Thermal Energy and Power Engineering, Shanghai University of Engineering Science, Shanghai 201620, China
Chongqing Midea General Refrigeration Equipment Co., Ltd., Chongqing 401336, China
School of Civil Engineering, Chongqing University, Chongqing 400044, China
School of Environment and Architecture, University of Shanghai for Science and Technology, Shanghai 200093, China
References (22)
Show source-provided references
1. Modeling of droplet entrainment in co-current annular two-phase flow: A new approach10.1016/j.ijmultiphaseflow.2011.10.008 ↗
2. Correlation of entrainment for annular flow in horizontal pipes10.1016/S0301-9322(01)00074-X ↗
3. Correlation of entrainment for annular flow in vertical pipes10.1016/S0301-9322(01)00073-8 ↗
4. Droplet entrainment correlation in vertical upward co-current annular two-phase flow10.1016/j.nucengdes.2007.10.005 ↗
5. Experimental investigation and theoretical modeling of liquid entrainment in a horizontal tee with a vertical-up branch10.1016/j.ijmultiphaseflow.2004.08.001 ↗
6. Experimental and theoretical investigation of liquid entrainment through small-scaled ADS-4 in AP100010.1016/j.expthermflusci.2014.04.022 ↗
7. Models development of liquid drops entrainment at a T-junction with a large vertical up branch10.1016/j.ijheatmasstransfer.2017.03.016 ↗
8. Mechanistic modeling of pool entrainment phenomenon10.1016/0017-9310(84)90187-X ↗
9. Experimental investigation of upper plenum entrainment in AP100010.1016/j.pnucene.2014.12.003 ↗
10. An experimental study of pool entrainment with side exit10.1016/j.anucene.2017.06.048 ↗
11. Experimental and theoretical investigation on pool entrainment under small air flow rate10.1016/j.expthermflusci.2019.03.005 ↗
12. Characterization of liquid refrigerant R-123 flow emerging from a flooded evaporator tube bundle10.1080/23744731.2018.1464349 ↗
13. Characterization and numerical simulation of liquid refrigerant R-134a flow emerging from a flooded evaporator tube bundle10.1016/j.ijrefrig.2019.07.001 ↗
14. Anish, S., and Kim, H.D. (2014, January 16–20). Effects of Wet Compression on the Flow Behavior of a Centrifugal Compressor: A CFD Analysis. Proceedings of the ASME Turbo Expo 2014: Turbine Technical Conference and Exposition, Dusseldorf, Germany.
15. Halbe, C.V., O’Brien, W.F., Cousins, W.T., and Sishtla, V. (2018, January 11–15). A Numerical Analysis of the Effects of Liquid Carryover on the Performance of a Two-Stage Centrifugal Compressor. Proceedings of the ASME Turbo Expo 2018: Turbomachinery Technical Conference and Exposition, Oslo, Norway.10.1115/GT2018-77015 ↗
16. AHRI (2018). Standard 550/590, Performance Rating of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle, Air-Conditioning and Refrigeration Institute.
17. Moran, M.J., Shapiro, H.N., Boettner, D.D., and Bailey, M.B. (2010). Fundamentals of Engineering Thermodynamics, John Wiley & Sons, Inc.. [7th ed.].
18. Zhang, C.L., Yang, L., and Shao, L.L. (2015). Refrigeration and Air-Conditioning System Modeling and Analysis Using Greatlab, Chemical Industry Press.
19. Describing the uncertainties in experimental results10.1016/0894-1777(88)90043-X ↗
20. Klein, S.A. (2000). Engineering Equation Solver, F-Chart Software, LLC. Available online: https://fchartsoftware.com/ees/.
21. Lemmon, E.W., Huber, M.L., and McLinden, M.O. (2013). NIST Standard Reference Database 23: Reference Fluid Thermodynamic and Transport Properties-Refprop, Version 9.1, National Institute of Standards and Technology, Standard Reference Data Program.
22. ASHRAE (2012). 2012 ASHRAE Handbook HVAC Systems and Equipment (SI Edition), ASHRAE.