journal article·2023-08-08Open access

Development of In Situ Refrigeration Cycle Measurement Method Using Air-Side Data of Air Source Heat Pump

Han-Gyeol Lee, Hyo-Jun Kim, Young-Hum Cho

Applied Sciences· Volume 13· Issue 16

Abstract

The refrigeration cycle of an air source heat pump system is an important information that reveals critical operating data, such as the cooling capacity, power consumption, and performance of a system during operation. Operating data, such as refrigerant pressure and enthalpy in situ, can be difficult to measure. Therefore, this study developed an in situ refrigeration cycle measurement method using the airside data of an air source heat pump. A method for measuring the refrigeration cycle is proposed using the characteristics of evaporation, compression, condensation, and expansion processes. The distance function was analyzed by normalizing the difference between the refrigerant pressure and enthalpy of the existing and proposed measurement methods. In addition, the distance function for the maximum error of the pressure and enthalpy measurement devices was analyzed and compared with the distance function of the entire data used in the evaluation. All the evaluation data had low distance function values with a maximum difference of 5%, confirming the reliability of the proposed refrigeration cycle measurement method. The power consumption and calculated COP were also evaluated using the proposed method. The Mean Bias Error (MBE) of power consumption and COP were 0.15% and 0.04%, and the coefficient of variation of root-mean-square error (CvRMSE) was 8.967% and 7.14%, respectively.
Source: crossref · Quality: baseline

Research context

OpenAlex topics: Building Energy and Comfort Optimization · Refrigeration and Air Conditioning Technologies · Heat Transfer and Optimization

SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.

Affiliations

Department of Architecture, Graduate School of Yeungnam University, Gyeongsan 38541, Republic of Korea

Institute of Industrial Technology, Yeungnam University, Gyeongsan 38541, Republic of Korea

School of Architecture, Yeungnam University, Gyeongsan 38541, Republic of Korea

Funding

Korea Institute of Energy Technology Evaluation and Planning (KETEP)

References (39)

Show source-provided references
1. IEA (2009). Key World Energy Statistics.
2. Thermal comfort and building energy consuimption implications—A review10.1016/j.apenergy.2013.10.062 ↗
3. Review of building energy-use performance benchmarking methodologies10.1016/j.apenergy.2010.11.022 ↗
4. Franco, A., Miserocchi, L., and Testi, D. (2021). HVAC Energy Saving Strategies for Public Buildings Based on Heat Pumps and Demand Controlled Ventilation. Energies, 14.10.3390/en14175541 ↗
5. Experimental study of an improved air source heat pump10.1016/j.enconman.2003.11.021 ↗
6. Analysis on key influence factors of air source heat pumps with field monitored data in Beijing
7. Field test investigation of a double-stage coupled heat pumps heating system for cold regions10.1016/j.ijrefrig.2005.01.001 ↗
8. Advances in heat pump systems: A review10.1016/j.apenergy.2010.06.014 ↗
9. Challenges in, and the development of, building energy saving techniques, illustrated with the example of an air source heat pump10.1016/j.tsep.2019.03.002 ↗
10. Breuker, M.S. (1997). Evaluation of a Statistical, Rule-Based Detection an Diagnosis Method for Vapor Compression Air Conditioners. [Master’s Thesis, School of Mechanical Engineering, Purdue University].
11. Chen, B. (2000). Evaluating the Potential of On-Line Fault Detection and Diagnosis for Rooftop Air Conditioners. [Master’s Thesis, School of Mechanical Engineering, Purdue University].
12. Li, H. (2004). A Decoupling-Based Unified Fault Detection and Diagnosis Approach for Packaged Air Conditioners. [Ph.D. Thesis, Purdue University].
13. Li, W.-T., Hassan, N.U., Khan, F., Yuen, C., and Keow, Y.M. (2019, January 13–15). Data Driven Model for Performance Evaluation and Anomaly Detection in Integrated Air Source Heat Pump Operation. Proceedings of the 2019 IEEE International Conference on Industrial Technology (ICIT), Melbourne, Australia.10.1109/ICIT.2019.8755022 ↗
14. A semi-theoretical model for energy efficiency assessment of air source heat pump systems10.1016/j.enconman.2020.113667 ↗
15. Lyons, P., Pukhrem, S., Walsh, A., and Carroll, P. (2019, January 14). Review of LV Network Development and Design for Electrified Domestic Heat and Transport. Proceedings of the 3rd E-Mobility Power System Integration Symposium, Dublin, Ireland.
16. Performance evaluation under the actual operating condition of a vertical ground source heat pump system in a school building10.1016/j.enbuild.2012.02.006 ↗
17. Comparative Evaluation of Different Computational Models for Performance of Air Source Heat Pumps Based on Real World Data10.1016/j.egypro.2016.09.065 ↗
18. Cho, H., Cho, K., Yoo, H., and Hong, H. (July, January 29). Field performance of variable capacity heat pump systems with multi-indoor units during Cooling Season. In Proceeding of the SAREK 2005 Summer Annual Conference, Huston, Pyeongchang, Republic of Korea.
19. New method for measuring field performance of variable refrigerant flow systems based on compressor set energy conservation10.1016/j.applthermaleng.2019.03.122 ↗
20. In-situ method for air-to-air heat pump seasonal performance determination including steady-state and dynamic operation10.1016/j.ijrefrig.2021.03.001 ↗
21. Method for performance metering of indoor units in variable refrigerant flow systems based on built-in sensors10.1016/j.applthermaleng.2021.117268 ↗
22. Air source heat pump in-situ performance10.1016/j.enbuild.2021.111365 ↗
23. Deep learning-based prediction method on performance change of air source heat pump system under frosting conditions10.1016/j.energy.2021.120542 ↗
24. The use of artificial neural networks (ANN) in the prediction of energy consumption of air-source heat pump in retrofit residential housing10.1088/1755-1315/463/1/012165 ↗
25. Refrigerant charge fault detection method of air source heat pump system using convolutional neural network for energy saving10.1016/j.energy.2019.115877 ↗
26. The performance prediction of ground source heat pump system based on monitoring data and data mining technology10.1016/j.enbuild.2016.06.055 ↗
27. Performance analysis of air source heat pump system for office building10.1007/s12206-016-1044-2 ↗
28. Danza, L., Belussi, L., Meroni, I., Mililli, M., and Salamone, F. (2016). Hourly Calculation Method of Air Source Heat Pump Behavior. Buildings, 6.10.3390/buildings6020016 ↗
29. Air Source Heat Pumps field studies: A systematic literature review10.1016/j.rser.2020.110275 ↗
30. Performance Analysis of Vapour Compression Refrigeration System with R404A, R407C and R410A
31. (2014). Measurement of Energy, Demand, and Water Savings. Standard No. ASHRAE 14-2014.
32. Taylor, B.N., and Kuyatt, C.E. (1994). Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results, National Institute of Standards and Technology. NIST Technical Note 1297.10.6028/NIST.TN.1297 ↗
33. Hardware in the loop test bench using Modelica: A platform to test and improve the control of heating systems10.1016/j.apenergy.2016.11.092 ↗
34. Kim, M., Payne, W.V., Domanski, P.A., and Hermes, C.J.L. (2006). Performance of a Residential Heat Pump Operating in the Cooling Mode with Single Faults Imposed, National Institute of Standards and Technology. NIST Interagency/Internal Report (NISTIR) 7350.10.6028/NIST.IR.7350 ↗
35. Measured effect of airflow and refrigerant charge on the seasonal performance of an air-source heat pump using R-410A10.1016/j.enbuild.2011.03.026 ↗
36. Two-stage air-source heat pump for residential heating and cooling applications in northern U.S. climates10.1016/j.ijrefrig.2008.01.006 ↗
37. Bertsch, S.S., and Groll, E.A. (2006, January 17–20). Air source heat pump for northern climates part I: Simulation of different heat pump cycles. Proceedings of the International Refrigeration and Air Conditioning Conference, West Lafayette, IN, USA.
38. (1988). Methods of Testing for Rating Unitary Air-Conditioning and Heat Pump Equipment. Standard No. ANSI/ASHRAE 37-1988.
39. (2006). Standard for Unitary Air Conditioning and Air Source Heat Pump Equipment. Standard No. ARI 210/240-2006.