New Dimensionless Correlations for the Evaluation of the Thermal Resistances of a District Heating Twin Pipe System
Source abstract
Abstract
The heat losses from pre-insulated double-pipe district heating (DH) systems buried in a homogeneous soil are studied numerically. The study is conducted using the diameter of the pipes and their distance, the size of the insulation, the thermal conductivity ratio between the insulation and the soil, as well as the burial depth of the double-pipe system, as controlling parameters. A computational code based on a control-volume formulation of the finite-difference method has been developed using the open-source framework OpenFOAM with the purpose to compute the heat transfer rate across adjacent solid regions with different thermophysical properties. The main scopes of the study are: (a) to investigate in what measure the geometry and the relative position of the warm and cold pipes, as well as the temperature imbalance, the burial depth and the physical properties of both the insulation and the soil, affect the heat losses; (b) to analyze the existence of an optimal configuration of the DH system by the thermal resistance enhancement viewpoint; and (c) to develop accurate correlating equations for the evaluation of the thermal resistance existing between each pipe and its surroundings, useful for practical thermal engineering applications.
Source: crossref · Quality: baseline
Research context
OpenAlex topics: Integrated Energy Systems Optimization · Geothermal Energy Systems and Applications · Building Energy and Comfort Optimization
SciVX discovery tags are terminology-based. OpenAlex topics are source-provided classifications.
Affiliations
Dipartimento di Ingegneria Astronautica Elettrica ed Energetica, Sapienza Università di Roma, Via Eudossiana 18, 00184 Roma, Italy
Dipartimento di Architettura, Università degli Studi Roma Tre, Via Madonna dei Monti 40, 00184 Roma, Italy
References (19)
Show source-provided references
1. European Commission (2016). An EU Strategy on Heating and Cooling, EU Commission.
2. Developing innovative business models for reducing return temperatures in district heating systems: Approach and first results10.1016/j.energy.2020.116963 ↗
3. Future district heating systems and technologies: On the role of smart energy systems and 4th generation district heating10.1016/j.energy.2018.09.115 ↗
4. Carslaw, H., and Jaeger, J. (1959). Conduction of Heat in Solids, Clarendon Press.
5. Wallentén, P. (1991). Steady-State Heat Loss from Insulated Pipes. [Ph.D. Thesis, Department of Building Physics, Lund Institute of Technology].
6. Multipole method to compute the conductive heat flows to and between pipes in a cylinder
7. Claesson, J., and Javed, S. (2018). Explicit multipole formulas for calculating thermal resistance of single U-tube ground heat exchangers. Energies, 11.10.3390/en11010214 ↗
8. Pre-insulated district-heating pipelines: Design and operational advice10.1016/0306-2619(92)90014-3 ↗
9. Single, twin and triple buried heating pipes: On potential savings in heat losses and costs10.1002/er.1118 ↗
10. Method for optimal design of pipes for low-energy district heating, with focus on heat losses10.1016/j.energy.2011.01.024 ↗
11. Three-dimensional numerical model of heat losses from district heating network pre-insulated pipes buried in the ground10.1016/j.energy.2015.07.012 ↗
12. Modelling steady-state thermal behaviour of double thermal network pipes10.1016/j.ijthermalsci.2017.03.026 ↗
13. Numerical determination of temperature distribution in heating network10.1016/j.energy.2019.06.163 ↗
14. Krawczyk, D., and Teleszewski, T. (2019). Optimization of geometric parameters of thermal insulation of pre-insulated double pipes. Energies, 12.10.3390/en12061012 ↗
15. An investigation into the heat loss characteristics of buried pipes10.1115/1.3247479 ↗
16. On transient heat losses from buried district heating pipes10.1002/1099-114X(200012)24:15<1311::AID-ER648>3.0.CO;2-Q ↗
17. Thermal analysis of buried insulated pipes10.1007/s11668-018-0552-z ↗
18. Teleszewski, T., Krawczyk, D., and Rodero, A. (2019). Reduction of heat losses using quadruple heating pre-insulated networks: A case study. Energies, 12.10.3390/en12244699 ↗
19. Greenshields, C. (2020). OpenFOAM User Guide—Version 8, OpenFOAM Foundation Ltd.